Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A07409Drive: U/f control, current limiting controller active

What it means

A07409 signals that the current limiting controller of the U/f control has become active because the set current limit was exceeded. The drive reports this as an alarm and keeps running — no automatic trip is triggered. Depending on the drive configuration, the same condition can also be output without any drive reaction at all.

Why it appears

  • The set current limit was exceeded, so the current limiting controller of the U/f control was activated.

What to check

  1. Increase the current limit (p0640) so the limiting controller no longer engages.
  2. Reduce the load.
  3. Slow down the ramp up to the setpoint speed.

Parameters the manual names

  • p0640 — current limit: raise the limit here if the drive should be allowed more current before the current limiting controller of the U/f control engages.

Acknowledging and restarting

No acknowledgement is required. The alarm is withdrawn automatically after one of the measures above takes effect — the current limit (p0640) has been raised, the load reduced, or the ramp up to the setpoint speed slowed down.

What differs between the drive families

Straight from the manuals' own fields — A07409 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1546
S120, S150NONEApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2801
G120NONENONEApplication/technological function faulted (17)SINAMICS G120 · p. 877
G120XANONENONESINAMICS G120XA PN converter · p. 1128
G115DSINAMICS G115D distributed drive · p. 393
G120CSINAMICS G120C Converters · p. 384

The drives this code lives on

A07409 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07409 mean on a SINAMICS drive?

The current limiting controller of the U/f control has become active because the set current limit was exceeded. The drive reports this as an alarm without tripping.

How do I clear A07409?

No acknowledgement is needed — the alarm disappears by itself once you increase the current limit (p0640), reduce the load, or slow down the ramp up to the setpoint speed.

Which parameter is behind A07409?

p0640, the current limit. Raising it gives the drive more current headroom before the current limiting controller of the U/f control activates.

Why does the drive keep running with A07409?

A07409 is an alarm, not a fault: no automatic trip is triggered, and depending on the configuration the same condition can even be output with no drive reaction at all.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.