Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A07400Drive: DC link voltage maximum controller active

What it means

A07400 signals that the DC link voltage maximum controller (Vdc_max controller) has switched in. The DC link voltage has passed the upper switch-in threshold — the level is shown in r1242 (vector control) or r1282 (U/f control), while the SERVO description names p1244 as the threshold. While it is active, the controller lengthens the ramp-down times on its own so that the DC link voltage (r0070) stays within the permissible limits. The drive does not trip, but the manual warns that the actual speed can deviate from the setpoint (a system deviation) for as long as the controller intervenes. The manual also notes a side effect: with the Vdc_max controller switched out (disabled), this message is the reason the ramp-function generator output tracks the speed actual value. Depending on how the drive is configured, the same condition can also be signalled with no reaction (N) instead of as this alarm.

Why it appears

  • The DC link voltage has risen above the upper switch-in threshold of the Vdc_max controller; for vector control this level is shown in r1242, for U/f control in r1282.
  • The SERVO description names the upper switch-in threshold p1244 as the trigger instead, and otherwise reports the same behaviour.

What to check

  1. If the controller should not intervene at all, give the drive more time to ramp down: increase p1121 (ramp-function generator ramp-down time) and p1135 (OFF3 ramp-down time).
  2. Alternatively, switch the Vdc_max controller off: p1240 = 0 for vector control, p1280 = 0 for U/f control (the SERVO remedy names only p1240 = 0).
  3. If the ramp-down times must stay as they are, use a chopper or regenerative feedback unit — the SERVO wording of the same measure says Braking Module or regenerative feedback unit.

Parameters the manual names

  • r1242 — switch-in level of the Vdc_max controller (vector control); the alarm reports that this level was exceeded.
  • r1282 — the same switch-in level for U/f control.
  • r0070 — the DC link quantity the controller holds within the permissible limits while it is active.
  • p1240 — Vdc controller configuration; set it to 0 to switch the controller off under vector control.
  • p1280 — the same configuration for U/f control; 0 switches the controller off.
  • p1244 — upper DC link voltage threshold, named as the activation threshold in the SERVO description.
  • p1121 — ramp-function generator ramp-down time; increase it so the controller need not intervene.
  • p1135 — OFF3 ramp-down time; the second ramp-down time the remedy offers to increase.

Acknowledging and restarting

No acknowledgement is required. This alarm is automatically withdrawn after the upper threshold has been distinctly exceeded. The SERVO text even states a remedy is «Not necessary» for the alarm itself; the measures above are only for keeping the controller out of the ramp-down permanently.

What differs between the drive families

Straight from the manuals' own fields — A07400 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2798
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1544
G120NONENONEApplication/technological function faulted (17)SINAMICS G120 · p. 876
G120XANONENONESINAMICS G120XA PN converter · p. 1127
S120, S150Application/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2797
G115DSINAMICS G115D distributed drive · p. 393
G120CSINAMICS G120C Converters · p. 384

The drives this code lives on

A07400 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07400 mean on a SINAMICS drive?

The DC link voltage maximum controller (Vdc_max controller) has switched in because the DC link voltage passed its upper switch-in threshold. The drive now extends the ramp-down times automatically to hold the voltage within limits.

How do I clear A07400?

No acknowledgement is needed — the manual states the alarm is withdrawn automatically once the upper threshold has been distinctly exceeded. To stop it recurring, lengthen p1121/p1135 or switch the controller off with p1240 = 0 (vector) or p1280 = 0 (U/f).

Why does the actual speed deviate from the setpoint while A07400 is active?

Because the Vdc_max controller intervenes during ramp-down, the manual states a system deviation between setpoint and actual speed can occur while it is switched in.

Which parameters define the switch-in threshold for A07400?

r1242 (vector control) and r1282 (U/f control) show the switch-in level; in the SERVO description the upper threshold is p1244.

Codes next to this one