Alarm · SINAMICS G120XA

A07427Motor switch-in alarm

What it means

A07427 («Motor switch-in alarm») is a G120XA alarm that reports one of two conditions — one concerning the technology controller, one concerning the operating time limits of the external motors. Which condition applies is read from the alarm value in r2124, interpreted as a decimal number.

Why it appears

  • The technology controller is not enabled, or it is enabled but not used to control the main setpoint — the mode is set in p2251.
  • An external motor — at least one of them — has run beyond its operating time limits.

What to check

  1. Read the alarm value in r2124 (interpret it as a decimal number) to find out which of the two conditions raised the alarm.
  2. For alarm value 1: enable the technology controller via p2200, or set the technology controller mode p2251 = 0 (main setpoint).
  3. For alarm value 2: increase p2381 or p2382, or set p2380 = 0.

Reading the message value

  • The drive stores the alarm value in r2124; interpret it as a decimal number.
  • 1: The technology controller is not active or is not being used to control the main setpoint (see p2251).
  • 2: The operating time limits have been exceeded in at least one external motor.

Parameters the manual names

  • r2124 — alarm value: shows as a decimal number which of the two conditions the alarm is reporting.
  • p2200 — BI: technology controller enable: the enable that activates the technology controller; the remedy for alarm value 1.
  • p2251 — technology controller mode: set it to 0 (main setpoint) so the technology controller controls the main setpoint; the remedy for alarm value 1.
  • p2381 — closed-loop cascade control max time for continuous operation: one of the time limits to increase for alarm value 2.
  • p2382 — closed-loop cascade control operating time limit: the other time limit to increase for alarm value 2.
  • p2380 — closed-loop cascade control operating hours: write 0 to it as the remedy for alarm value 2.

Acknowledging and restarting

No acknowledgement is required for this alarm. Clearing it means removing the cause itself: for alarm value 1, enable the technology controller (p2200) or set p2251 = 0 (main setpoint); for alarm value 2, increase p2381 or p2382, or set p2380 = 0.

The same on every family

Every manual that describes A07427 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G120XANONENONESINAMICS G120XA PN converter · p. 1130

Questions technicians ask

What does alarm A07427 Motor switch-in alarm mean on a SINAMICS G120XA?

It reports one of two conditions, distinguished by the alarm value in r2124: 1 — the technology controller is not active or is not being used to control the main setpoint; 2 — the operating time limits have been exceeded in at least one external motor.

How do I fix A07427 with alarm value 1?

Enable the technology controller via p2200, or set the technology controller mode p2251 = 0 (main setpoint).

What clears A07427 alarm value 2?

Increase the time limits p2381 or p2382, or set p2380 (closed-loop cascade control operating hours) = 0.

Does A07427 have to be acknowledged?

No. The alarm requires no acknowledgement; removing the cause is the corrective action.