What it means
Alarm A07402 tells you that the drive has switched in its DC link voltage minimum controller (Vdc_min controller). This happens when the DC link voltage drops below the lower switch-in threshold. For vector control and U/f the manual references the switch-in levels r1246 and r1286; for servo operation the lower threshold p1248 applies. While the controller is active, the motor's kinetic energy buffers the DC link, so the drive brakes itself, and a deviation between the speed setpoint and the actual speed can occur. Depending on the drive configuration, the same condition can also be output without any reaction (N).
Why it appears
- The DC link voltage undershot the lower switch-in threshold, and the drive responded by activating the DC link voltage controller.
- The manual names one possible cause for this: the line supply has failed.
What to check
- No remedy is necessary at first: the alarm withdraws on its own once the DC link voltage distinctly exceeds the lower threshold again, and it disappears when the line supply returns.
- If it keeps coming back, check the line supply and the infeed.
- Increase the ramp-up time p1120.
- As a last measure, switch the Vdc_min controller off by setting p1240 = 0.
Parameters the manual names
- p1248 — lower DC link voltage threshold; in servo operation this is the switch-in threshold for the minimum controller.
- r1246 — Vdc_min controller switch-in level (kinetic buffering), which the manual references when the threshold is undershot.
- r1286 — the same switch-in level for U/f control.
- p1240 — Vdc controller configuration; set it to 0 here to shut the Vdc_min controller down.
- p1280 — the Vdc controller configuration for U/f control.
- p1120 — ramp-function generator ramp-up time; the manual's remedy is to increase it when this alarm occurs.
Acknowledging and restarting
The alarm needs no acknowledgement and clears itself: it is withdrawn automatically once the DC link voltage distinctly exceeds the lower threshold again, or when the line supply returns.
What differs between the drive families
Straight from the manuals' own fields — A07402 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2799 |
| S120, S150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2799 |
| G130, G150 | NONE | NONE | Application/technological function faulted (17) | None | SINAMICS G130, G150 List Manual · p. 1545 |
| G120 | NONE | NONE | Application/technological function faulted (17) | — | SINAMICS G120 · p. 877 |
| G120XA | NONE | NONE | — | — | SINAMICS G120XA PN converter · p. 1127 |
The drives this code lives on
A07402 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A07402 mean on a SINAMICS drive?
The DC link voltage minimum controller is active. The DC link voltage fell below its lower switch-in threshold, and the motor's kinetic energy now buffers the DC link, which brakes the drive.
How do I reset alarm A07402?
You do not need to acknowledge it. The alarm withdraws automatically once the DC link voltage distinctly exceeds the lower threshold again, or when the line supply returns.
Why does A07402 keep coming back?
The manual names a failed line supply as a possible cause. Check the line supply and the infeed, increase the ramp-up time p1120, or shut the Vdc_min controller down with p1240 = 0.
Which parameters belong to A07402?
The thresholds and configuration of the minimum controller: p1248 (lower threshold), r1246 and r1286 (switch-in levels), p1240 and p1280 (Vdc controller configuration), plus the ramp-up time p1120.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A07xxx group · SINAMICS manuals · Siemens manuals