Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A05002Power unit: Air intake overtemperature

What it means

A05002 is the alarm Power unit: Air intake overtemperature. It is raised when the air intake temperature at the power unit reaches the alarm threshold; for air-cooled power units that threshold is 42 °C, with a hysteresis of 2 K. In the G120 and G120XA manuals the cause text is expressly limited to chassis power units. What the power unit does once the threshold is reached is set in p0290. The manuals state the escalation verbatim: If the air intake temperature increases by an additional 13 K, then fault F30035 is output. Depending on how the drive is configured, the same condition can also be signalled with no reaction (N).

Why it appears

  • The alarm threshold for the air intake overtemperature has been reached at the power unit.
  • For air-cooled power units the threshold is 42 °C with a hysteresis of 2 K; the G120 and G120XA manuals scope this to chassis power units.

What to check

  1. Check whether the ambient temperature is within the defined limit values.
  2. Check whether the fan has failed — and check its direction of rotation.
  3. On the G115D and G120C the manuals condense the entry to a single question: are the load conditions and duty cycle configured accordingly?

Parameters the manual names

  • p0290 (Power unit overload response / PU overl response) — set here how the power unit responds when the air intake overtemperature alarm threshold is reached.

Acknowledging and restarting

The drive triggers no reaction to this alarm and no acknowledgement is required, so there is nothing to reset at the panel; the overtemperature response itself follows p0290. What matters is dealing with the temperature while it is still only an alarm: if the air intake temperature climbs a further 13 K, the drive outputs fault F30035. The manual's checklist — ambient temperature within the defined limit values, fan and its direction of rotation — is how the condition is dealt with.

What differs between the drive families

Straight from the manuals' own fields — A05002 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEPower electronics faulted (5)Power ModuleSINAMICS S120, S150 List Manual · p. 2746
G130, G150NONENONEPower electronics faulted (5)Power ModuleSINAMICS G130, G150 List Manual · p. 1519
G120NONENONEPower electronics faulted (5)SINAMICS G120 · p. 868
G120XANONESINAMICS G120XA PN converter · p. 1117
G115DSINAMICS G115D distributed drive · p. 393
G120CSINAMICS G120C Converters · p. 384

The drives this code lives on

A05002 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What temperature triggers alarm A05002?

On air-cooled power units the alarm threshold for the air intake temperature is 42 °C, with a hysteresis of 2 K. What the drive does at that threshold is set in p0290.

Does A05002 have to be acknowledged?

No. The drive triggers no reaction to this alarm and no acknowledgement is required; it warns that the intake air has reached the threshold.

What happens if the air intake temperature keeps rising after A05002?

If it rises by a further 13 K, the drive outputs fault F30035.

What should I check for A05002?

Whether the ambient temperature is within the defined limit values, and whether the fan has failed — including its direction of rotation. On the G115D and G120C the manuals also ask whether the load conditions and duty cycle are configured accordingly.