What it means
A05052 is the alarm Parallel circuit: Illegal current asymmetry. Where power units operate in parallel, the drive monitors the individual current of each power unit; when the deviation between these individual currents exceeds the alarm threshold configured in p7010, the drive raises this alarm. The alarm value in r2124 tells you which phase signalled the asymmetry. The manuals describe the code in the same way for the G130, G150, S120 and S150. Depending on the drive's configuration, the same condition can also be output as a fault (F) instead of an alarm.
Why it appears
- The deviation between the individual currents of the power units connected in parallel exceeds the alarm threshold specified in p7010.
What to check
- Inhibit the pulses of the faulted power unit via p7001 (power units enable).
- Check the connecting cables — loose contacts can cause current spikes.
- Replace the motor reactors if they are non-symmetrical or faulty.
- Calibrate the CTs or replace them.
Reading the message value
- The drive writes the alarm value into r2124; interpret the value as a decimal number. This is the value behind the %1 placeholder in the message value.
- 1 — Phase U
- 2 — Phase V
- 3 — Phase W
Parameters the manual names
- p7010 — current asymmetry alarm threshold of the parallel circuit: the threshold that the deviation of the individual power unit currents has exceeded, which triggered this alarm.
- r2124 — alarm value: read the decimal value here to determine the phase concerned (1 = U, 2 = V, 3 = W).
- p7001 — power units enable: use this parameter to inhibit the pulses of the faulted power unit, the first step of the remedy.
Acknowledging and restarting
Output as an alarm, A05052 requires no acknowledgement. If the drive's configuration outputs the same condition as a fault instead, the fault reaction is NONE — neither on the Infeed nor on the vector drive objects is OFF1, OFF2, OFF3 or STOP2 executed — but the fault must be acknowledged IMMEDIATELY.
What differs between the drive families
Straight from the manuals' own fields — A05052 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | NONE | Application/technological function faulted (17) | Power Module | SINAMICS G130, G150 List Manual · p. 1521 |
| S120, S150 | — | — | Application/technological function faulted (17) | Power Module | SINAMICS S120, S150 List Manual · p. 2748 |
The drives this code lives on
A05052 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A05052 mean?
It is the alarm Parallel circuit: Illegal current asymmetry. The drive raises it when the deviation between the individual currents of paralleled power units exceeds the alarm threshold set in p7010.
Which phase is meant by A05052?
The alarm value in r2124, read as a decimal number, names the phase: 1 means Phase U, 2 means Phase V and 3 means Phase W.
How do I clear A05052?
Inhibit the pulses of the faulted power unit via p7001, then check the connecting cables, since loose contacts can cause current spikes. Replace non-symmetrical or faulty motor reactors and calibrate or replace the CTs. As an alarm, the message itself requires no acknowledgement.
Does A05052 switch the drive off?
No. As an alarm it has no effect on operation, and even when the same condition is output as a fault the reaction is NONE — no OFF1, OFF2, OFF3 or STOP2 is executed. In the fault case the message must then be acknowledged IMMEDIATELY.