What it means
A05001 tells you that the alarm threshold for overtemperature of the power semiconductor in the AC converter has been reached — the depletion layer of the chip, called the barrier layer in some of the entries, has become too warm. The operator panel and the commissioning tool show the condition as Power unit: Overtemperature depletion layer chip
. Depending on the drive configuration, the same condition can also be output with no reaction (N).
The alarm is the warning stage ahead of the fault: the response the drive performs in this state is the one set in p0290, and fault F30025 is initiated if the depletion layer temperature increases further. The entries for the S120/S150, G120 and G120XA name the margin as the value set in p0292[1]; the G130/G150 entries state it as an additional 15 K.
Why it appears
- The alarm threshold for the overtemperature of the power semiconductor in the AC converter has been reached at the depletion layer of the chip.
What to check
- Check whether the ambient temperature is within the defined limit values.
- Check whether the load conditions and the load duty cycle have been appropriately dimensioned.
- Check whether the cooling has failed.
- Check whether the pulse frequency is too high.
The entries also cover a special case: if the alarm occurs after reducing the current controller sampling time (p0115[0]) during the motor data identification (standstill measurement), it is recommended to initially perform the identification using the standard sampling time and only then change the sampling time over.
Parameters the manual names
- p0290 (Power unit overload response): here you set how the drive responds once this alarm threshold has been reached.
- p0292 (Power unit temperature alarm threshold): index [1] holds the further temperature rise after which fault F30025 is initiated — the G130/G150 entries give this margin directly as 15 K.
- p0115 (Sampling time for supplementary functions): index [0] is the current controller sampling time; if the alarm appeared after it was reduced for the motor data identification, run the identification with the standard sampling time and change over afterwards.
- r0037 (Control Unit temperature): named in the entries under See also as a related parameter for this alarm.
Acknowledging and restarting
This alarm needs no acknowledgement: nothing has to be reset at the operator panel. What the drive does while the condition is present is defined by p0290, and fault F30025 only follows if the temperature climbs beyond the margin described above. Work through the checks above to remove the cause of the high chip temperature.
What differs between the drive families
Straight from the manuals' own fields — A05001 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Power electronics faulted (5) | Power Module | SINAMICS S120, S150 List Manual · p. 2746 |
| G130, G150 | NONE | NONE | Power electronics faulted (5) | Power Module | SINAMICS G130, G150 List Manual · p. 1518 |
| S120, S150 | NONE | NONE | Power electronics faulted (5) | Power Module | SINAMICS S120, S150 List Manual · p. 2745 |
| G130, G150 | NONE | NONE | Power electronics faulted (5) | Power Module | SINAMICS G130, G150 List Manual · p. 1518 |
| G120 | NONE | NONE | Power electronics faulted (5) | — | SINAMICS G120 · p. 868 |
| G120XA | NONE | NONE | — | — | SINAMICS G120XA PN converter · p. 1117 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 393 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 384 |
The drives this code lives on
A05001 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A05001 mean?
It reports that the alarm threshold for overtemperature of the power semiconductor chip (depletion layer) in the AC converter has been reached. The drive's response to this condition is set in p0290.
Does A05001 require an acknowledgement?
No. The manual specifies no acknowledgement for this alarm; it is the warning stage before fault F30025, which is only initiated if the temperature rises further.
When does A05001 turn into fault F30025?
When the depletion layer temperature increases beyond the alarm threshold — by the value set in p0292[1] according to most entries, or by an additional 15 K according to the G130/G150 entries.
What should I check for A05001?
The ambient temperature limit values, whether the load conditions and load duty cycle are appropriately dimensioned, whether the cooling has failed, and whether the pulse frequency is too high.