Alarm · SINAMICS G130, G150, S120, S150

A01386Topology: DRIVE-CLiQ component incorrectly inserted

What it means

The drive's topology comparison has detected a DRIVE-CLiQ component in the actual topology that has been inserted incorrectly with respect to the target topology — the component sits at a connection the project does not expect. The message value names the component and the connection concerned. While the alarm is present, The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.

Why it appears

  • A DRIVE-CLiQ component is inserted in the actual topology at a connection that does not match the target topology.

What to check

  1. Insert the components involved at the right connection, so the actual topology matches the target topology.
  2. Alternatively, adapt the project/parameterization in the commissioning software so the target topology matches the components as they are actually inserted.
  3. Alternatively, remove the topology error automatically with p9904.

Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability where relevant, for example a setpoint/actual value comparison.

Reading the message value

  • Message value: Component: %1, to %2, %3, connection: %4 — the drive fills in the component concerned and the connection at which it is incorrectly inserted.
  • The alarm value is stored in r2124 and is to be interpreted hexadecimal: ddccbbaa hex.
  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the incorrectly inserted component (%1)
  • dd, cc and bb describe the component where the component involved is incorrectly inserted; component class and connection number are described in F01375.

Parameters the manual names

  • r2124 — alarm value: read it hexadecimal as ddccbbaa to identify the connection, the component class, the component number and the incorrectly inserted component.
  • p9904 — Topology comparison acknowledge differences (Topo_compare ackn): used to remove this topology error automatically, as an alternative to re-inserting the component or adapting the project.

Acknowledging and restarting

There is no acknowledgment step for this alarm: it ends when the difference between the actual and the target topology has been eliminated — by re-inserting the component at the right connection, by adapting the project/parameterization, or by removing the topology difference automatically with p9904, so that the drive system boots and closed-loop drive control can be enabled again.

What differs between the drive families

Straight from the manuals' own fields — A01386 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1414
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2604

The drives this code lives on

A01386 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01386 mean on a SINAMICS drive?

The topology comparison has found a DRIVE-CLiQ component in the actual topology that is inserted at a connection other than the one the target topology expects. While the alarm is active, the drive system is not booted and closed-loop control cannot be enabled.

How do I find out which component A01386 refers to?

Read the alarm value in r2124 as hexadecimal ddccbbaa: aa is the number of the incorrectly inserted component, bb its component class, cc the component number and dd the connection number. Component class and connection number are decoded as described for F01375.

How is alarm A01386 cleared?

Either insert the component at the right connection, adapt the project/parameterization in the commissioning software so the target topology matches, or remove the topology error automatically with p9904. Under "Topology --> Topology view" the commissioning software offers improved diagnostics such as a setpoint/actual value comparison.

Does A01386 have to be acknowledged?

There is no acknowledgment step; the alarm ends once the difference between the actual and the target topology has been removed.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.