Alarm · SINAMICS G130, G150, S120, S150

A01381Topology: Line Module incorrectly inserted

What it means

A01381 is raised by the topology comparison when it finds, in the actual topology, a component that is not inserted where the project expects it. The manual raises the alarm in three variants — the message text, the alarm value and the remedy are identical, only the component differs: for a power unit, for a Motor Module and for a Line Module. For the Motor Module and the Line Module the manual expresses the cause as incorrectly inserted with respect to the target technology. While the alarm is present, The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled. The commissioning tool offers improved diagnostics capability under Topology --> Topology view (e.g. setpoint/actual value comparison).

Why it appears

  • The topology comparison has detected a component in the actual topology that has been incorrectly inserted: a power unit, a Motor Module or a Line Module, depending on which component is affected.
  • For the Motor Module and the Line Module the manuals state that the module was inserted incorrectly with respect to the target technology.

What to check

  1. Identify the component and the connection from the alarm value in r2124, which is interpreted hexadecimal — see the decoding below; component class and connection number are described in F01375.
  2. Open Topology --> Topology view in the commissioning tool; where relevant it offers improved diagnostics capability, e.g. a setpoint/actual value comparison.
  3. Correct the actual topology: insert the components involved at the right connection.
  4. Alternatively, correct the target topology: adapt the project/parameterizing in the commissioning tool.
  5. Alternatively, remove the topology error automatically with p9904.

Reading the message value

The alarm text reads Component: %1, to %2, %3, connection: %4; the same four values are packed into the alarm value, which the manual says to interpret hexadecimal as ddccbbaa:

  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the incorrectly inserted component (%1)

The component is described in dd, cc and bb, where the component involved is incorrectly inserted. Component class and connection number are described in F01375.

Parameters the manual names

  • r2124 (alarm value): holds the alarm value of this alarm; read it hexadecimal as ddccbbaa to find the connection number, component number, component class and the component number of the incorrectly inserted component.
  • p9904 (Topology comparison acknowledge differences / Topo_compare ackn): use it to remove the topology error automatically instead of correcting the hardware insertion or the project.

Acknowledging and restarting

No acknowledgment is required: the alarm is cleared by removing the topology difference itself. Either reinsert the component at the right connection, adapt the project/parameterizing in the commissioning tool so the target topology matches, or acknowledge the topology comparison differences with p9904. As long as the alarm is present the drive system is no longer booted and the closed-loop drive control cannot be enabled in this state.

What differs between the drive families

Straight from the manuals' own fields — A01381 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2601
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2602
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1411
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1411
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1412
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2601

The drives this code lives on

A01381 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01381 mean on a SINAMICS drive?

The topology comparison has detected a power unit, Motor Module or Line Module in the actual topology that is incorrectly inserted — for the Motor Module and Line Module, with respect to the target technology. The component and its connection are identified by the alarm value in r2124.

Why can I not enable the drive while A01381 is active?

Because in this state the drive system is no longer booted and the drive control (closed-loop) cannot be enabled. The topology error must be removed first.

How do I decode the A01381 alarm value?

Read r2124 hexadecimal as ddccbbaa: aa is the component number of the incorrectly inserted component, bb the component class, cc the component number and dd the connection number. Component class and connection number are described in F01375.

Does A01381 have to be acknowledged?

No. It clears when the topology difference is removed — insert the component at the right connection, adapt the target topology in the commissioning tool, or remove the topology error automatically with p9904.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals