Alarm · SINAMICS G130, G150, S120, S150

A01382Topology: Sensor Module incorrectly inserted

What it means

A01382 is an alarm raised by the drive's topology comparison: a Sensor Module has been found in the actual topology — the hardware as it is physically inserted — at a connection that does not match the target topology configured in the project. The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled. The alarm text itself names the component and the connection involved.

Why it appears

  • The topology comparison has detected a Sensor Module in the actual topology that has been incorrectly inserted with respect to the target technology — the module stands at a connection that the target topology does not expect.

What to check

  1. Identify the component and connection from the alarm value (see below); under "Topology --> Topology view" the commissioning software/tool offers, where relevant, improved diagnostics capability (e.g. setpoint/actual value comparison).
  2. Insert the components involved at the right connection (correct the actual topology).
  3. Alternatively, adapt the project/parameterization in the commissioning software/tool (correct the target topology).
  4. Use p9904 to remove the topology error automatically.

Reading the message value

The alarm value is stored in r2124 and must be interpreted as hexadecimal, in the pattern ddccbbaa hex. The alarm text shows Component: %1, to %2, %3, connection: %4; the placeholders are the parts of the alarm value:

  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the incorrectly inserted component (%1)

The component involved is described in dd, cc and bb, where the component involved is incorrectly inserted. Component class and connection number are described in F01375.

Parameters the manual names

  • r2124 — alarm value of this alarm; read it in hexadecimal (ddccbbaa) to identify the connection number, the component number, the component class and the component number of the incorrectly inserted Sensor Module.
  • p9904 — Topology comparison acknowledge differences (Topo_compare ackn); removes the topology error automatically, one of the three ways the remedy lists for adapting topologies.

Acknowledging and restarting

This alarm requires no acknowledgement. While the topology error exists, the drive system is no longer booted and the drive control (closed-loop) cannot be enabled; the error is removed by one of the steps above.

What differs between the drive families

Straight from the manuals' own fields — A01382 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1412
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2602

The drives this code lives on

A01382 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01382 mean on a SINAMICS drive?

The topology comparison has found a Sensor Module in the actual topology that is inserted at a connection which does not match the target topology in the project. While the error exists, the drive system is no longer booted and closed-loop control cannot be enabled.

How do I fix A01382?

Insert the Sensor Module at the right connection, or adapt the project/parameterization in the commissioning software so that the target topology matches the hardware. Alternatively, p9904 removes the topology error automatically.

How is the A01382 alarm value decoded?

Read r2124 as hexadecimal ddccbbaa: dd is the connection number, cc the component number, bb the component class and aa the component number of the incorrectly inserted component. Component class and connection number are described in F01375.

Does A01382 have to be acknowledged?

No. The alarm requires no acknowledgement; it goes away once the topology error is removed by correcting the hardware, the project or with p9904.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals