Alarm · SINAMICS G130, G150, S120, S150

A01385Topology: Controller Extension incorrectly inserted

What it means

A01385 is an alarm from the drive's topology comparison: a controller extension 32 (CX32) has been found in the actual topology that is inserted incorrectly with respect to the target topology. The manuals title it Topology: Controller Extension incorrectly inserted. While the error is present, the drive system is no longer booted and the drive control (closed-loop) cannot be enabled. The message value names the affected component (Component: %1, to %2, %3, connection: %4), and the alarm value in r2124 identifies the connection and the component that is incorrectly inserted.

Why it appears

  • The topology comparison has found a controller extension 32 (CX32) in the actual topology that is not inserted where the target topology expects it.

What to check

  1. Open Topology → Topology view in the commissioning software, where relevant: it offers improved diagnostics capability, e.g. a setpoint/actual value comparison.
  2. Insert the components involved at the right connection; this corrects the actual topology.
  3. Alternatively, adapt the project/parameterization in the commissioning software; this corrects the target topology.
  4. Alternatively, remove the topology error automatically with p9904.

Reading the message value

  • The alarm value is stored in r2124 and is to be interpreted hexadecimal: ddccbbaa hex.
  • dd = connection number (%4)
  • cc = component number (%3)
  • bb = component class (%2)
  • aa = component number of the incorrectly inserted component (%1)
  • The component involved is described by dd, cc and bb; the component class and the connection number are described under F01375.

Parameters the manual names

  • r2124 (Alarm value): read the alarm value here and interpret it hexadecimal to identify the connection, the component class and the component numbers of the incorrectly inserted CX32.
  • p9904 (Topology comparison acknowledge differences / Topo_compare ackn): the remedy offers this parameter for removing the topology error automatically.

Acknowledging and restarting

No acknowledgment is required for this alarm. Once the discrepancy between the actual and the target topology has been eliminated — the CX32 inserted at the correct connection, the project adapted in the commissioning software, or the topology error removed automatically with p9904 — the alarm is cleared.

The same on every family

Every manual that describes A01385 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1414
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2604

The drives this code lives on

A01385 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A01385 mean on a SINAMICS drive?

The topology comparison has found a controller extension 32 (CX32) in the actual topology that is inserted incorrectly with respect to the target topology. While the error is present, the drive system is no longer booted and the closed-loop control cannot be enabled.

How do I clear alarm A01385?

Insert the CX32 at the connection the target topology expects, or adapt the project/parameterization in the commissioning software so the target topology matches. p9904 removes the topology error automatically.

Does A01385 have to be acknowledged?

No. This alarm requires no acknowledgment; it is cleared once the discrepancy between the actual and the target topology has been corrected.

How do I find out which CX32 connection is wrong?

Interpret the alarm value in r2124 hexadecimal as ddccbbaa: dd is the connection number, cc the component number, bb the component class and aa the component number of the incorrectly inserted component. The component class and the connection number are described under F01375.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.