What it means
F35407 is raised by the temperature evaluation of the Terminal Module 150 (TM150), channel 11. The drive initiates it when at least one of two conditions is fulfilled: the alarm threshold has been exceeded for longer than the delay time set in the timer, or the fault threshold has been exceeded outright. The same condition can also be output as an alarm (A) or as a message without reaction (N), depending on the drive configuration. Note that this fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal Module.
Why it appears
- The alarm threshold of channel 11 (p4102[22]) has been exceeded longer than the time set in the timer (p4103[11]).
- The fault threshold of channel 11 (p4102[23]) has been exceeded.
What to check
- Read the fault value in r0949 (interpret decimal): it contains the temperature actual value of channel 11 at the time the message was initiated, in 0.1 °C. Compare it with the current temperature at connector output r4105[11].
- Check the sensor type set in p4100[11]. For sensor type "PTC thermistor" or "Bimetallic NC contact" (p4100[11] = 1, 4), read the sensor resistance r4101[11]: if it is greater than 1650 ohms, the drive sets the temperature r4105[11] = 250 °C; if it is 1650 ohms or less, it sets r4105[11] = -50 °C.
- Determine from the settings which of the two trigger conditions applies: the alarm threshold p4102[22] together with the timer p4103[11], or the fault threshold p4102[23].
- Allow the temperature sensor to cool down until it is below the fault threshold p4102[23] minus the hysteresis p4118[11].
- If required, set the fault response to NONE for this fault via p2100 and p2101.
Reading the message value
- r0949, interpret decimal: the temperature actual value at the time the fault was initiated, in 0.1 °C.
- The current temperature actual value of the channel is displayed via connector output r4105[11] and can be interconnected.
Parameters the manual names
- p4102 — holds the channel 11 thresholds: alarm threshold at index [22], fault threshold at index [23]; the sensor must fall below the fault threshold before the fault clears.
- p4103 — delay time p4103[11]: how long the alarm threshold may be exceeded before the fault is initiated.
- p4100 — sensor type of channel 11; the value 1 or 4 selects evaluation of a PTC thermistor or a bimetallic NC contact.
- r4101 — sensor resistance of the channel; for a PTC thermistor or bimetallic NC contact, whether it is above or at most 1650 ohms decides whether 250 °C or -50 °C is reported.
- r4105 — connector output with the channel 11 temperature actual value; can be interconnected.
- p4118 — hysteresis p4118[11]; the cooling target is the fault threshold p4102[23] minus this hysteresis.
- r0949 — fault value; read it with decimal interpretation to see the temperature at initiation.
- p2100 / p2101 — if required, enter this fault there and change its response to NONE.
Acknowledging and restarting
Remove the condition before acknowledging: let the temperature sensor cool down until it reads below the fault threshold p4102[23] minus the hysteresis p4118[11], then acknowledge the fault and restart the drive. When the condition is configured as an alarm (A) or as a message without reaction (N), the manual specifies reaction NONE and acknowledgement NONE, so no acknowledgement is needed in those variants.
What differs between the drive families
Straight from the manuals' own fields — F35407 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (NONE, OFF1, OFF3) Vector: OFF2 (NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3) | — | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3227 |
| G130, G150 | Vector: OFF2 (NONE, OFF1, OFF3) Infeed: OFF2 (NONE, OFF1) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1891 |
The drives this code lives on
F35407 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F35407 in SINAMICS mean?
The Terminal Module 150 temperature evaluation on channel 11 has exceeded its alarm threshold for longer than the timer p4103[11] allows, or the fault threshold p4102[23] has been exceeded. The fault value in r0949 holds the temperature at initiation in 0.1 °C.
How do I fix fault F35407?
Let the temperature sensor cool down below the fault threshold p4102[23] minus the hysteresis p4118[11], then acknowledge the fault and restart the drive.
Why does F35407 report 250 °C or -50 °C?
For a PTC thermistor or bimetallic NC contact (p4100[11] = 1, 4), the drive derives the temperature from the resistance r4101[11]: above 1650 ohms it reports 250 °C, at 1650 ohms or less it reports -50 °C at r4105[11].
Why does the drive not shut down on F35407?
The manual notes this fault only shuts the drive down when at least one BICO interconnection exists between the drive and the Terminal Module. The same condition can also be configured as an alarm (A) or without reaction (N).
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.