Fault · SINAMICS G130, G150, S120, S150

F35405TM: Temperature fault/alarm threshold channel 9 exceeded

What it means

F35405 reports that the temperature evaluation of channel 9 on a Terminal Module 150 (TM150) has left the permissible range. The monitoring trips either when the alarm threshold has been exceeded longer than the timer allows (p4102[18], p4103[9]) or when the fault threshold p4102[19] is exceeded. The condition is detected on the Terminal Module and reaches the drive object via BICO interconnection. Depending on how the drive is configured, the same condition can also be output as an alarm or without any reaction. The evaluated temperature of the channel is visible at connector output r4105[9] and can be interconnected. Note the manual's remark: This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal Module.

Why it appears

  • The alarm threshold of channel 9 (p4102[18]) was exceeded for longer than the delay time set in p4103[9].
  • The fault threshold of channel 9 (p4102[19]) was exceeded.

What to check

  1. Allow the temperature sensor to cool down until its value is below the fault threshold p4102[19] minus the hysteresis p4118[9].
  2. For sensor type PTC thermistor or Bimetallic NC contact (p4100[9] = 1, 4), read the sensor resistance at r4101[9] to interpret the channel: if r4101[9] is greater than 1650 ohms, the drive shows 250 °C at r4105[9]; if r4101[9] is 1650 ohms or less, it shows -50 °C. The actual value of the channel is at connector output r4105[9].
  3. If required, set the fault response to NONE using p2100 and p2101.

Reading the message value

  • r0949, interpreted as a decimal number: the temperature actual value of channel 9 at the time the fault was initiated, given in 0.1 °C.

Parameters the manual names

  • p4102 — holds the temperature thresholds that channel 9 is monitored against: index [18] is the alarm threshold, index [19] the fault threshold.
  • p4103 — the delay time in [9]: how long the alarm threshold may be exceeded before this fault is initiated.
  • p4100 — sensor type of channel 9; the special resistance interpretation for this fault applies when it is set to 1 or 4 (PTC thermistor, Bimetallic NC contact).
  • r4101 — resistance measured at the channel 9 sensor; for a PTC thermistor or bimetallic NC contact, compare it with 1650 ohms to interpret the displayed temperature.
  • r4105 — connector output (CO) with the evaluated temperature actual value of channel 9; the drive displays the temperature here and it can be interconnected.
  • p4118 — hysteresis of channel 9; the sensor must cool below the fault threshold minus this value before the fault can be remedied.
  • p2100 — fault number for changing the fault response; the number of this fault is entered here.
  • p2101 — response for the fault number entered in p2100; set it to NONE if the temperature monitoring should not shut the drive down.
  • r0949 — fault value memory; for this fault it carries the temperature at the moment of initiation in 0.1 °C.

Acknowledging and restarting

Once the sensor has cooled below the fault threshold p4102[19] minus the hysteresis p4118[9], acknowledge the fault; acknowledgement is possible immediately, and a POWER ON also clears it, after which the drive can be restarted. If the drive is configured to output this condition only as an alarm or with no reaction, neither a reaction nor an acknowledgement is required.

What differs between the drive families

Straight from the manuals' own fields — F35405 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (NONE, OFF1, OFF3) Vector: OFF2 (NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3)IMMEDIATELY (POWER ON)External measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3226
G130, G150Vector: OFF2 (NONE, OFF1, OFF3) Infeed: OFF2 (NONE, OFF1)IMMEDIATELY (POWER ON)External measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1890

The drives this code lives on

F35405 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F35405 mean on a SINAMICS drive?

It reports that the temperature evaluation of channel 9 on a Terminal Module 150 (TM150) has left the permissible range: either the alarm threshold p4102[18] stayed exceeded longer than the time in p4103[9], or the fault threshold p4102[19] was exceeded. Depending on the configuration, the same condition can also appear as an alarm or with no reaction.

How do I clear fault F35405?

Let the temperature sensor cool down below the fault threshold p4102[19] minus the hysteresis p4118[9], then acknowledge the fault immediately; a POWER ON also acknowledges it. If the condition is only output as an alarm or without reaction, no acknowledgement is needed.

Why does the drive not shut down when F35405 appears?

The fault only causes a shutdown if there is at least one BICO interconnection between the drive and the Terminal Module. In addition, the fault response can be changed to NONE via p2100 and p2101, and the condition may be configured as an alarm or with no reaction.

What is stored in r0949 for F35405?

The fault value holds the temperature actual value of channel 9 at the time the fault was initiated, interpreted as a decimal number in steps of 0.1 °C. The evaluated temperature is also visible at connector output r4105[9].

Codes next to this one