What it means
F35400 comes from the temperature evaluation of the Terminal Module 150 (TM150), channel 4. The drive raises it when either the channel's alarm threshold has been exceeded for longer than the set timer allows, or the fault threshold itself has been passed. Depending on the drive's configuration, the same condition can also be delivered as an alarm or with no reaction at all. The manual points out that the message only shuts the drive down when at least one BICO interconnection exists between the drive and the Terminal Module. The remaining temperature channels of the Terminal Module carry their own codes.
Why it appears
- The alarm threshold of channel 4 has been exceeded for longer than the time set in the timer (p4102[8], p4103[4]).
- The fault threshold of channel 4 has been exceeded (p4102[9]).
What to check
- Allow the temperature sensor to cool down to below p4102[9] minus the hysteresis set in p4118[4].
- Follow the channel 4 temperature actual value at connector output r4105[4]; the value can be interconnected and so watched while cooling.
- If the sensor type is "PTC thermistor" or "Bimetallic NC contact" (p4100[4] = 1, 4), read the resistance in r4101[4]: above 1650 ohms the drive shows r4105[4] = 250 °C, at 1650 ohms or below it shows r4105[4] = -50 °C.
- If required, set the fault response to NONE (p2100, p2101).
Reading the message value
- r0949, interpreted decimal, holds the temperature actual value of channel 4 at the moment the fault was initiated, in 0.1 °C.
Parameters the manual names
- p4102 — index [8] holds the alarm threshold and index [9] the fault threshold of channel 4; these are the comparison values behind this message.
- p4103 — index [4] sets the timer: how long the alarm threshold may be exceeded before the fault is initiated.
- p4100 — index [4] selects the sensor type of channel 4; the fixed display values of the note apply for the settings 1 (PTC thermistor) and 4 (bimetallic NC contact).
- r4101 — reports the resistance of the channel 4 sensor; the 1650 ohms limit from the note refers to this value.
- r4105 — connector output (CO) with the channel 4 temperature actual value; the drive writes 250 °C or -50 °C here depending on the sensor state, and the value can be interconnected.
- p4118 — hysteresis of the fault/alarm threshold for channel 4; the sensor must cool below the fault threshold minus this hysteresis.
- p2100 / p2101 — together they re-map the response of this fault number; the remedy names the setting NONE.
Acknowledging and restarting
As a fault, the message is acknowledged immediately; switching the power supply off and on (POWER ON) also removes it. Where the drive delivers the same condition as an alarm or with no reaction, no acknowledgement is required. Before restarting, make sure the sensor has cooled below p4102[9] minus the hysteresis (p4118[4]) so the condition is really gone.
What differs between the drive families
Straight from the manuals' own fields — F35400 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (NONE, OFF1, OFF3) Vector: OFF2 (NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3223 |
| G130, G150 | Vector: OFF2 (NONE, OFF1, OFF3) Infeed: OFF2 (NONE, OFF1) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1887 |
The drives this code lives on
F35400 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does F35400 mean in a SINAMICS drive?
The Terminal Module 150 reports on its temperature channel 4 that either the alarm threshold stayed exceeded longer than the timer (p4102[8], p4103[4]) allows, or the fault threshold (p4102[9]) was passed. The fault value in r0949 shows the temperature at the moment of tripping.
How do I clear fault F35400?
Let the sensor cool down to below p4102[9] minus the hysteresis in p4118[4], then acknowledge the message immediately; a POWER ON also removes it. As an alarm or with no reaction it needs no acknowledgement.
Why does the temperature display show 250 °C or -50 °C?
With the sensor types PTC thermistor or bimetallic NC contact (p4100[4] = 1, 4) the drive maps the resistance directly: r4101[4] above 1650 ohms gives 250 °C in r4105[4], 1650 ohms or less gives -50 °C.
Does F35400 always stop the drive?
No. The manual notes the fault only causes a shutdown when at least one BICO interconnection exists between the drive and the Terminal Module, and the configuration decides whether it appears as a fault, an alarm, or with no reaction.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F35xxx group · SINAMICS manuals · Siemens manuals