What it means
The drive raises F07563 when it identifies an incorrect configuration for the “Absolute position for incremental encoder” function of the connected drive encoder. The encoder data set is then configured for this function although the Sensor Module does not provide the property it requires (r0459.13 = 0). The message value tells you which fault cause applies and which encoder data set is affected. Depending on the drive's configuration, the same condition can also be issued as an alarm (A).
Why it appears
- An incorrect configuration was identified for the “Absolute position for incremental encoder” function of the drive encoder.
- Fault cause 1: the “Absolute value for incremental encoder” function is not supported — r0459.13 = 0, i.e. the connected Sensor Module lacks the property the configured function needs (the remedy points to a Sensor Module firmware upgrade).
- The mode set in p4652 (1 or 3) is configured although r0459.13 = 0, so the configured mode exceeds what the Sensor Module supports.
What to check
- Read the fault value in r0949, interpreted as a decimal number: yy gives the fault cause, xx the encoder data set whose configuration was rejected.
- For fault cause 1: upgrade the Sensor Module firmware version.
- Check the mode set in p4652: p4652 = 1 or 3 requires the property r0459.13 = 1; if r0459.13 reads 0, the configured mode is not supported by the connected Sensor Module.
Reading the message value
- The drive stores the value in r0949 for the fault and in r2124 when the condition appears as an alarm; interpret it as a decimal number coded as yyxx: yy = fault cause, xx = encoder data set.
- Fault cause 1 (= 01 hex): the “Absolute value for incremental encoder” function is not supported (r0459.13 = 0).
Parameters the manual names
- r0949 — fault value: read the coded value here (decimal) to identify the fault cause (yy) and the affected encoder data set (xx).
- r2124 — alarm value: holds the same coded value when the condition is output as an alarm instead of the fault.
- r0459 — Sensor Module properties extended: check bit 13; it must read 1 for the configured “Absolute value for incremental encoder” function.
- p4652 — XIST1_ERW reset mode: check the set mode; 1 and 3 require r0459.13 = 1.
Acknowledging and restarting
Once the configuration has been corrected, acknowledge the fault immediately; switching the drive power supply off and on (POWER ON) also clears it, after which the drive can be restarted. If the drive is configured to output the condition only as an alarm, no reaction follows and no acknowledgment is required.
What differs between the drive families
Straight from the manuals' own fields — F07563 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Hla: OFF2 (NONE, OFF1, OFF3, STOP2) | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2847 |
| G130, G150 | Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Infeed: OFF2 (NONE, OFF1) | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1581 |
The drives this code lives on
F07563 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07563 mean on my SINAMICS drive?
It reports an incorrect configuration for the “Absolute position for incremental encoder” function of the drive encoder — typically the configured function is not supported by the Sensor Module (r0459.13 = 0).
How do I fix fault F07563?
Upgrade the Sensor Module firmware and check the mode in p4652 — settings 1 and 3 require r0459.13 = 1. Then acknowledge the fault immediately; POWER ON also clears it.
What does the F07563 fault value tell me?
Interpret r0949 as a decimal number yyxx: yy is the fault cause (1 = the function is not supported) and xx is the encoder data set concerned.
Can F07563 also appear as an alarm?
Yes — depending on the drive's configuration the same condition can be issued as an alarm; then it triggers no automatic reaction and needs no acknowledgment.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals