Fault · SINAMICS G130, G150, S120, S150

F07551Drive encoder: No commutation angle information

What it means

F07551 is raised when the drive encoder (component Encoder 1) is not supplying any commutation angle information. Without this angle the drive cannot control a synchronous motor in closed loop, so it trips the drive. The manual names two distinct situations behind the fault, and the fault value in r0949 tells you which one applies and which drive data set is affected.

Why it appears

The manual names two situations that leave the drive without a commutation angle:

  • Fault cause 1 — the motor encoder used does not supply an absolute commutation angle.
  • Fault cause 2 — the selected ratio of the measuring gear does not match the motor pole pair number.

What to check

  1. Read the fault cause and the affected drive data set from r0949 (decimal yyyyxxxx) so you know whether you are dealing with cause 1 or cause 2.
  2. Fault cause 1: check the encoder parameterization (p0404).
  3. Fault cause 1: use an encoder with track C/D, an EnDat interface or Hall sensors.
  4. Fault cause 1: with a sinusoidal A/B track encoder, the motor pole pair number (r0313) multiplied by the gear ratio (p0432/p0433) must be less than the encoder pulse number (p0408) — or an integer multiple of it.
  5. Fault cause 1: for motor encoders without absolute position information, activate the pole position identification routine (p1982 = 1).
  6. For the VECTOR drive objects, the manual additionally states that after the pole position identification the angular commutation offset should be determined using the encoder adjustment (p1990).
  7. Fault cause 2: make sure the quotient of the pole pair number divided by the ratio of the measuring gear is an integer number: (p0314 * p0433) / p0432.
  8. Note for operation with track C/D: this quotient must be less than 8.

Reading the message value

The message text carries two placeholders: %1 is the fault cause, %2 the drive data set. The drive writes the value into r0949 — interpret it as a decimal number yyyyxxxx:

  • yyyy = fault cause: 1 dec — the motor encoder used does not supply an absolute commutation angle; 2 dec — the selected ratio of the measuring gear does not match the motor pole pair number.
  • xxxx = the affected drive data set.

Parameters the manual names

  • r0949 — fault value: holds this fault's fault cause (yyyy) and affected drive data set (xxxx) as the decimal number yyyyxxxx.
  • p0404 — effective encoder configuration: the first thing to check for fault cause 1.
  • r0313 — actual (or calculated) motor pole pair number: enters the sinusoidal A/B track condition (r0313 multiplied by the gear ratio versus p0408).
  • p0432 / p0433 — gearbox factors for encoder revolutions and motor/load revolutions: together they form the gear ratio used in the sinusoidal A/B condition and in the integer quotient.
  • p0408 — rotary encoder pulse number: the sinusoidal A/B condition compares against this pulse number.
  • p1982 — pole position identification selection: set it to 1 to activate the routine for motor encoders without absolute position information.
  • p1990 — encoder adjustment to determine the angular commutation offset: per the manual for the VECTOR drive objects, use it after p1982 = 1.
  • p0314 — enters the quotient (p0314 * p0433) / p0432 that must be an integer for fault cause 2.

Acknowledging and restarting

F07551 trips the drive and the motor coasts down. The fault is acknowledged immediately, but only after POWER ON: switch the drive supply off and on again before the drive can be restarted.

What differs between the drive families

Straight from the manuals' own fields — F07551 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (IASC/DCBRK)IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)Encoder 1SINAMICS S120, S150 List Manual · p. 2842
G130, G150OFF2 (IASC/DCBRK)IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)Encoder 1SINAMICS G130, G150 List Manual · p. 1576
S120, S150Servo: OFF2 (IASC/DCBRK) Hla: OFF2IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)Encoder 1SINAMICS S120, S150 List Manual · p. 2841

The drives this code lives on

F07551 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F07551 in a SINAMICS drive mean?

The drive encoder is not delivering any commutation angle information. Without this angle the drive cannot control a synchronous motor in closed loop, so it trips with F07551.

How do I fix F07551 fault cause 1?

Check the encoder parameterization (p0404) and use an encoder that supplies an absolute commutation angle — track C/D, an EnDat interface or Hall sensors. For motor encoders without absolute position information, activate the pole position identification routine with p1982 = 1; on the VECTOR drive objects the manual then calls for determining the angular commutation offset with the encoder adjustment (p1990).

What does the fault value of F07551 mean?

Read r0949 as a decimal number yyyyxxxx: yyyy is the fault cause (1 = the motor encoder does not supply an absolute commutation angle, 2 = the measuring gear ratio does not match the motor pole pair number) and xxxx is the affected drive data set.

Why can F07551 not be cleared from the panel?

This fault is acknowledged immediately, but only after POWER ON — the drive supply must be switched off and on again before the fault can be cleared and the drive restarted.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.