What it means
The drive raises F07435 when the ramp-function generator is operated in a way that sensorless vector control does not permit: during operation with sensorless vector control (r1407.1) the ramp-function generator was stopped (p1141) or bypassed (p1122), and an internal setting command of the ramp-function generator output froze the setpoint speed — or the command was not able to be realized. Depending on the drive's configuration, the same condition can also be issued with no reaction (N).
Why it appears
- During operation with sensorless vector control (r1407.1) the ramp-function generator was stopped (p1141): an internal setting command of the ramp-function generator output caused the setpoint speed to be frozen (the S120/S150 and G130/G150 descriptions add: or the command was not able to be realized).
- In the S120/S150 and G130/G150 descriptions the cause list is broader: the ramp-function generator was bypassed (p1122) during sensorless vector operation.
- Also for these drive objects: the drive is switched on with flying restart activated (p1200) and the ramp-function generator is bypassed (p1122) at the same time.
What to check
- Deactivate the holding command for the ramp-function generator (p1141) so it is no longer stopped during sensorless vector operation.
- Do not bypass the ramp-function generator (p1122) — this step comes from the S120/S150 and G130/G150 remedy.
- If the ramp-function generator is held using jogging while the speed setpoint is simultaneously inhibited (r0898.6), suppress the fault via p2101 and p2119 — the manual calls this necessary in exactly that case.
- Check the setpoint routing: for sensorless vector control
it is not practical to read in the main setpoint of the speed control via p1155 or p1160
(p0922). Inject the main setpoint before the ramp-function generator (p1070) instead, because the RFG output is set automatically when transitioning from closed-loop speed controlled into open-loop speed controlled operation.
Reading the message value
- Message value “Parameter: %1” — the value identifies the parameter concerned. The manual prints no bit-by-bit decoding for it.
Parameters the manual names
- p1141 (BI, continue/freeze ramp-function generator): the holding command that stops the RFG; deactivating it is the first remedy step.
- p1122 (BI, bypass ramp-function generator): must not be active here; bypassing the RFG — including at switch-on with flying restart — is named as a cause for the affected drive objects.
- p1200: named in the cause — the fault also occurs when the drive is switched on with flying restart activated while the RFG is bypassed.
- p2101 (change fault response): together with p2119, the pair the remedy names for suppressing this fault.
- p2119 (change message type): the second parameter for suppressing the fault.
- p1155 (CI, speed controller speed setpoint 1): not a practical path for the main setpoint with sensorless vector control.
- p1160 (CI, speed controller speed setpoint 2): same — avoid reading the main setpoint in here for sensorless vector control.
- p0922 (IF1 PROFIdrive PZD telegram selection): cited in the note together with the p1155/p1160 setpoint path it advises against.
- p1070 (CI, main setpoint): where the main setpoint should be injected — before the ramp-function generator — for sensorless vector control.
Acknowledging and restarting
The fault response trips the drive to OFF2, so the motor coasts down. Once the cause has been removed, acknowledge the fault immediately — only then will the drive restart. Where the drive's configuration outputs the condition as N, there is neither a reaction nor an acknowledgement.
What differs between the drive families
Straight from the manuals' own fields — F07435 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY | Application/technological function faulted (17) | None | SINAMICS S120, S150 List Manual · p. 2814 |
| G130, G150 | OFF2 (IASC/DCBRK, NONE, OFF1, OFF3) | IMMEDIATELY | Application/technological function faulted (17) | None | SINAMICS G130, G150 List Manual · p. 1552 |
| G120 | OFF2 (IASC/DCBRK, NONE, OFF1, OFF3) | IMMEDIATELY | Application/technological function faulted (17) | — | SINAMICS G120 · p. 879 |
| G120XA | OFF2 (IASC/DCBRK, NONE, OFF1, OFF3) | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1130 |
The drives this code lives on
F07435 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07435 mean on a SINAMICS drive?
It means that during operation with sensorless vector control (r1407.1) the ramp-function generator was stopped (p1141) or, on some drive objects, bypassed (p1122). An internal setting command of the ramp-function generator output then froze the setpoint speed or could not be realized.
How do I clear F07435?
Deactivate the ramp-function generator holding command (p1141), do not bypass the ramp-function generator (p1122), and acknowledge the fault immediately. If the RFG is held using jogging while the speed setpoint is simultaneously inhibited (r0898.6), suppress the fault via p2101 and p2119.
Can fault F07435 be suppressed?
Yes — the remedy names p2101 and p2119 for this. Suppression is necessary when the ramp-function generator is held using jogging and the speed setpoint is simultaneously inhibited (r0898.6).
Why should the speed setpoint not be fed via p1155 or p1160 with sensorless vector control?
Because the ramp-function generator output is automatically set when transitioning from closed-loop speed controlled into open-loop speed controlled operation. The manual therefore recommends injecting the main setpoint before the ramp-function generator (p1070).
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals