What it means
F07433 is raised when a changeover to closed-loop control with encoder is to be carried out but the connected encoder has not been unparked — it is still parked. While the encoder remains parked, the drive cannot use it for closed-loop control and rejects the changeover. The fault signals this rejected changeover rather than a drive trip, so no automatic stop is executed.
Why it appears
- The changeover to closed-loop control with encoder was commanded while the encoder had not yet been unparked.
- For long-stator motors (p3870.0 = 1): the encoder had not completed the unparking procedure (r3875.0 = 1) before the changeover was attempted.
What to check
- Check whether the encoder firmware supports the "parking" function: r0481.6 must read 1.
- If the encoder firmware does not support the parking function, upgrade the firmware.
- For long-stator motors (p3870.0 = 1), make sure the encoder has completed the unparking procedure before changing over — r3875.0 must read 1.
The encoder is unparked using binector input p3876 = 0/1 signal and remains until a 0 signal in this state.
Parameters the manual names
- r0481 (CO: Encoder status word Gn_ZSW / Enc Gn_ZSW) — for this fault bit 6 is checked: r0481.6 = 1 means the encoder firmware supports the parking function.
- p3870 (Long stator configuration / Long stator config) — p3870.0 = 1 identifies the application as a long-stator motor, the case for which the unparking condition applies before the changeover.
- p3876 (BI: Unpark long stator signal source 1 encoder / s_s 1 enc unpark) — the binector input whose 0/1 signal unparks the encoder; the encoder remains unparked until a 0 signal is applied.
Acknowledging and restarting
No special reset is described for this fault. Once the encoder is unparked — for long-stator motors, once r3875.0 reads 1 — and, where the parking function was not supported, the firmware has been upgraded, acknowledge the fault in the way shown for your drive object and repeat the changeover to closed-loop control with encoder.
The same on every family
Every manual that describes F07433 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE (OFF1, OFF2, OFF3) | — | Actual position/speed value incorrect or not available (11) | Sensor Module Encoder 1 | SINAMICS S120, S150 List Manual · p. 2813 |
The drives this code lives on
F07433 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07433 mean in SINAMICS?
The drive wanted to change over to closed-loop control with encoder, but the connected encoder has not been unparked. The changeover is rejected while the encoder is still parked.
How do I fix F07433?
Check r0481.6: if the encoder firmware does not support the parking function, upgrade the firmware. For long-stator motors (p3870.0 = 1), unpark the encoder via p3876 and wait until r3875.0 = 1 before repeating the changeover.
How is a long-stator encoder unparked?
With a 0/1 signal at binector input p3876; the encoder remains unparked until a 0 signal is applied. r3875.0 = 1 shows that the unparking procedure has completed.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.