What it means
F07437 means that the actual value of the free technology controller 1 has reached the limit set for it. Which of the two limits was reached — the upper or the lower one — is shown by the fault value in r0949. The signal that serves the controller as its actual value is selected via connector input p11164. Depending on the drive configuration, the same condition can also be output as an alarm (A). As a fault it trips the drive — OFF1 is the set response (IASC/DCBRK, OFF2, OFF3 or NONE can be selected instead) — and the message must be acknowledged immediately.
Why it appears
- The actual value of the free technology controller 1 has reached its limit: with fault value 1 the upper limit, with fault value 2 the lower limit.
What to check
- Adapt the limit settings to the actual value signal — upper limit in p11167, lower limit in p11168.
- Check the scaling of the actual value signal.
- Check the signal source setting for the actual value in p11164.
Reading the message value
- Read the fault value in r0949 and interpret it as a decimal number.
- 1 — the actual value has reached the upper limit.
- 2 — the actual value has reached the lower limit.
Parameters the manual names
- p11164 (CI: Free tec_ctrl 1 actual value signal source) — sets the signal source from which free technology controller 1 takes its actual value; check this setting when the actual value runs into a limit.
- p11167 (Ftec1 act v up lim) — upper limit of the free technology controller 1 actual value; adapt it to the actual value signal.
- p11168 (Ftec1 act v lo lim) — lower limit of the free technology controller 1 actual value; adapt it to the actual value signal.
- r0949 (fault value) — read here, interpreted as a decimal number, to see whether the upper limit (1) or the lower limit (2) was reached.
Acknowledging and restarting
Remove the cause first, then acknowledge the fault immediately. The drive can only be restarted once the fault message has been cleared.
The same on every family
Every manual that describes F07437 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120XA | OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) | IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1131 |
Questions technicians ask
What does fault F07437 mean on a SINAMICS G120XA?
It means the actual value of the free technology controller 1 has reached the limit set for it. Fault value 1 in r0949 indicates the upper limit, fault value 2 the lower limit.
How do I fix F07437?
Adapt the limit values p11167 and p11168 to the actual value signal, check the scaling of that signal, and verify the signal source set in p11164. Then acknowledge the fault immediately.
Can F07437 also appear as an alarm?
Yes. Depending on the drive configuration, the same condition can also be output as an alarm (A) instead of a fault.
Which parameter sets the actual value signal source for free technology controller 1?
p11164 (CI: Free tec_ctrl 1 actual value signal source) defines the signal source of the actual value.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals