Fault · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

F07320Drive: Automatic restart interrupted

What it means

F07320 is the message the drive issues when its automatic restart does not complete: the restart is interrupted before the unit manages to switch itself on again. The function works with a limited number of start attempts (p1211) and a monitoring time (p1213) inside which the faults have to be acknowledged — and every new start attempt consumes one attempt from the counter. When one of these limits is missed, or the drive stays off after commissioning and related routines, this fault is the result.

Why it appears

  • The configured number of restart attempts in p1211 is exhausted because the faults could not be acknowledged within the monitoring time in p1213; each new start attempt decrements the counter.
  • The monitoring time of the power unit (p0857) has expired.
  • The drive unit is not switched on again automatically when commissioning is exited, when the motor identification routine ends, or when the speed controller optimization finishes.

What to check

  1. Raise the number of restart attempts in p1211; r1214 shows the actual number of start attempts.
  2. Make the delay time stored in p1212 longer and/or extend the monitoring time kept in p1213.
  3. Set a longer monitoring time for the power unit in p0857, or disable this monitoring.
  4. Shorten the delay at which the start counter is reset via p1213[1]; fewer faults are then registered inside the time interval.
  5. The manuals for the G115D and the G120C, which describe the code only as a short table, add one more step: apply an ON command at p0840.

Reading the message value

  • The fault value is held in r0949 and must be read hexadecimal.
  • The manual publishes no decoding for this code: the value is reserved for internal Siemens troubleshooting, and the message value appears only as the placeholder %1.

Parameters the manual names

  • p1211 — AR start attempts: the stock of automatic restart attempts; raise it here, noting that each new start attempt decrements it.
  • p1212 — AR t_wait start: the automatic restart delay time, to be increased alone or together with p1213.
  • p1213 — AR t_mon: the monitoring time inside which the faults must be acknowledged; increase it, and shorten the p1213[1] delay that resets the start counter.
  • p0857 — PU t_mon: the power unit monitoring time; lengthen it or disable it so it does not expire during the restart sequence.
  • r0949 — fault value of this message, read hexadecimal, reserved for internal Siemens troubleshooting.

Acknowledging and restarting

The drive coasts down on this fault and must be acknowledged before it will start again. Once acknowledged, a new automatic restart sequence can begin — and every new start attempt decrements the counter in p1211 again.

What differs between the drive families

Straight from the manuals' own fields — F07320 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2792
G130, G150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1542
G120OFF2IMMEDIATELYApplication/technological function faulted (17)SINAMICS G120 · p. 875
G120XAOFF2IMMEDIATELYSINAMICS G120XA PN converter · p. 1125
S120, S150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2792
G130, G150OFF2IMMEDIATELYApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1542
G115DSINAMICS G115D distributed drive · p. 393
G120CSINAMICS G120C Converters · p. 384

The drives this code lives on

F07320 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does F07320 mean on a SINAMICS drive?

That the automatic restart was interrupted. Either the start attempts in p1211 were used up without the faults being acknowledged inside the monitoring time p1213, the power unit monitoring time p0857 expired, or the unit was not switched on again automatically after commissioning, motor identification or speed controller optimization.

How do I clear F07320?

Acknowledge the fault; the drive coasts down and must be acknowledged before it will start again. If the fault keeps coming back, raise the number of restart attempts in p1211 or lengthen the times in p1212 and p1213.

Why does my drive not restart automatically after motor identification or commissioning?

The manual lists this directly as one of the causes: when commissioning is exited, when the motor identification routine ends, or when the speed controller optimization finishes, the drive unit is not switched on again automatically — and F07320 results.

What is stored in r0949 for F07320?

The fault value, which is to be read hexadecimal. The manual states it serves only for internal Siemens troubleshooting, so no decoding is published for this code.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.