What it means
F06311 is raised by the infeed when the line supply voltage does not match the nominal line voltage stored in p0210. Once precharging has completed, the drive calculates the actual line supply voltage (Vrms) from the measured DC link voltage. The fault is triggered when this calculated value does not lie within the extended tolerance range of the supply voltage set in p0210 — the manual defines that range as 75 % * p0210 < Vrms < 120 % * p0210. The message also covers the case where the nominal value entered in p0210 itself lies outside the nominal voltage range of the power unit. While the fault is active, the drive coasts down and must be acknowledged before it will start again.
Why it appears
- The nominal line voltage stored in p0210 lies outside the nominal voltage range of the power unit.
- After precharging was completed, the infeed calculated the actual line supply voltage Vrms from the measured DC link voltage, and this value does not lie within the extended tolerance range of the supply voltage set in p0210 (75 % * p0210 < Vrms < 120 % * p0210).
What to check
- Check the parameterized supply voltage in p0210 and, if required, change it so that it matches the supply actually connected to the infeed.
- Check the line supply voltage itself: the calculated Vrms has left the window around p0210, so establish whether the incoming supply is below 75 % or above 120 % of the setting, or whether p0210 was parameterized incorrectly in the first place.
Reading the message value
- Message value:
Line supply voltage: %1
— the drive inserts the line supply voltage Vrms it calculated from the measured DC link voltage. - Alarm value: r2124 (floating point) — the drive stores the line supply voltage Vrms present when the message was raised.
Parameters the manual names
- p0210 — Drive unit line supply voltage (U_connect): the nominal line voltage setting this fault is judged against; for F06311, compare it with the actual supply and correct it if it was set wrongly.
- r2124 — Alarm value: read out the line supply voltage Vrms the drive captured, stored as a floating-point value.
Acknowledging and restarting
Remove the cause first — correct p0210 if it was set incorrectly, or restore the line supply voltage so that it lies within the tolerance window around p0210. The fault is then acknowledged; the manual specifies IMMEDIATELY, with POWER ON as the second acknowledgment option for this message. Once the fault has been acknowledged, the drive can be restarted.
The same on every family
Every manual that describes F06311 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 (OFF1) | IMMEDIATELY (POWER ON) | Network fault (2) | None | SINAMICS S120, S150 List Manual · p. 2765 |
| G130, G150 | OFF2 (OFF1) | IMMEDIATELY (POWER ON) | Network fault (2) | None | SINAMICS G130, G150 List Manual · p. 1529 |
The drives this code lives on
F06311 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F06311 mean on a SINAMICS infeed?
It means the actual line supply voltage, calculated from the measured DC link voltage after precharging, lies outside the range 75 % to 120 % of the nominal voltage set in p0210 — or that the p0210 value itself is outside the power unit's nominal voltage range.
How do I fix fault F06311?
Check the supply voltage parameterized in p0210 and correct it if required, and check the line supply voltage actually present. The fault can only stay cleared when the calculated voltage and the p0210 setting agree.
Which parameter is behind F06311?
p0210, the drive unit line supply voltage. The drive compares the calculated Vrms against this setting; the captured voltage value can be read from r2124.
How is F06311 acknowledged?
After the cause has been removed, the fault is acknowledged immediately; POWER ON is printed as the second acknowledgment option. The drive can be restarted once the message has been acknowledged.