What it means
The drive routes the active current setpoint for master/slave operation through a 4-channel multiplexer. Connector input p3572 selects which of the four channels is used; only the values 0, 1, 2 and 3 are valid. The drive has identified a value outside this set at this input. Operation is not interrupted: the multiplexer control remains effective with the previous value until a valid value is present again.
Why it appears
- Connector input p3572, which selects the channel of the 4-channel multiplexer for the master/slave active current setpoint, was given a value other than 0, 1, 2 or 3.
- The invalid value originates from the signal source of the BICO interconnection to p3572.
What to check
- Check the interconnection used to control the multiplexer (CI: p3572).
- Check the signal value that the signal source of this BICO interconnection delivers.
Reading the message value
- The message value corresponds to the fault value in r0949 and is to be interpreted as a decimal number.
- It contains the invalid value with which the multiplexer was to be controlled; the values 0, 1, 2 and 3 would have been valid.
Parameters the manual names
- p3572 — CI: Master/slave active current setpoint multiplexer selection: the connector input whose interconnection selects the multiplexer channel and must be checked for this fault.
- r0949 — Fault value: read here, interpreted as a decimal number, which invalid value was present at the multiplexer selection.
Acknowledging and restarting
The fault can be acknowledged immediately — no waiting time applies. Because the drive does not trip, no restart of the converter is required; once the interconnection to p3572 again supplies one of the valid values 0, 1, 2 or 3, acknowledging clears the message.
The same on every family
Every manual that describes F06320 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | IMMEDIATELY | Infeed faulted (13) | Power Module | SINAMICS S120, S150 List Manual · p. 2765 |
The drives this code lives on
F06320 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS fault F06320 mean?
The drive has detected an invalid value at connector input p3572, which controls the 4-channel multiplexer for the master/slave active current setpoint. Only the values 0, 1, 2 and 3 are valid selections.
How do I fix fault F06320?
Check the interconnection to control the multiplexer (CI: p3572) and the signal value delivered by the signal source of that BICO interconnection. Once a valid value is present again, the fault can be acknowledged immediately.
Does F06320 stop the drive?
No. The fault is signalled but the drive does not trip — the multiplexer control remains effective with the previous value.
Where can I see which value triggered F06320?
In the fault value r0949, interpreted as a decimal number. It contains the invalid value that was applied to the multiplexer control.