What it means
F01512 (BICO: No scaling available) is raised when an attempt is made to determine a conversion factor for a scaling that does not exist. It concerns the BICO signal interconnection: once a BICO output is connected to a BICO input, the drive converts between the two signals using the reference values. If the interconnection runs between different drive objects (DO) and the signals are normalized differently — different normalized units on output and input, or the same units but different reference values — the drive must calculate a conversion factor; when no scaling exists for that conversion, this fault follows. The manuals for all listed converter families give this same cause; the G120XA documentation additionally works out the two constellations reproduced below.
Why it appears
An attempt was made to determine a conversion factor for a scaling that does not exist.
The requested BICO interconnection itself was established, but the conversion between BICO output and BICO input is made using the reference values — and no scaling is available for it.- Output and input lie in different drive objects and are normalized to different units, for example a BICO output with a voltage normalized unit feeding a BICO input with a current normalized unit. The drive then forms the factor p2002/p2001 between output and input, where p2002 contains the reference value for current and p2001 the reference value for voltage.
- Output and input carry the same normalized unit but sit in different drive objects whose reference values differ, for example a voltage-normalized output in DO1 and a voltage-normalized input in DO2 whose voltage reference values (p2001) have different values. The drive then forms the factor p2001(DO1)/p2001(DO2).
What to check
- Apply a scaling, or check the transfer value of the affected BICO interconnection — this is the remedy the manual gives for the code.
- Use the fault value to locate the point of trouble: it names the unit (for example the unit corresponding to SPEED) for which the factor was sought, and in the G120XA decoding it contains the parameter number of the BICO input (signal sink).
- Examine the connected BICO output and input for the constellations described above: different drive objects with different normalized units, or the same unit with different reference values (p2001, p2002) in the two objects.
Reading the message value
- The fault value is held in r0949 and is to be interpreted as a decimal number.
- Value: the unit (for example the unit corresponding to SPEED) for which an attempt was made to determine a factor.
- The G120XA documentation gives a second decoding: the parameter number of the BICO input (signal sink).
Parameters the manual names
- r0949 — fault value: read it here as a decimal number to identify the unit (e.g. SPEED) — or, in the G120XA decoding, the BICO input parameter number — to which the failed scaling attempt refers.
- p2001 — reference voltage: reference value from which the drive calculates the conversion factor, e.g. as p2001(DO1)/p2001(DO2) when two drive objects have different voltage references.
- p2002 — reference current: reference value that, together with p2001, forms the factor p2002/p2001 when a voltage-normalized BICO output is connected to a current-normalized BICO input.
Acknowledging and restarting
The drive coasts down while this fault is active and must be acknowledged before it will start. The acknowledgment is a POWER ON: switch the converter power supply off and then on again — a reset from the operator panel alone does not clear this fault. Correct the BICO interconnection first (apply the scaling or check the transfer value), then power the converter down and up and restart the drive.
What differs between the drive families
Straight from the manuals' own fields — F01512 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120XA | OFF2 NONE | POWER ON IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1112 |
| S120, S150 | Infeed: OFF2 (OFF1) Servo: OFF2 Vector: OFF2 Hla: OFF2 | POWER ON | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2616 |
| G130, G150 | Vector: OFF2 Infeed: OFF2 (OFF1) | POWER ON | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1425 |
| G120 | OFF2 | POWER ON | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 835 |
| G115D | — | — | — | — | SINAMICS G115D distributed drive · p. 392 |
| G120C | — | — | — | — | SINAMICS G120C Converters · p. 382 |
The drives this code lives on
F01512 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS fault F01512 mean?
The drive attempted to determine a conversion factor for a scaling that does not exist — typically on a BICO interconnection between two drive objects whose signals are normalized to different units or to different reference values.
How do I fix SINAMICS fault F01512?
Apply a scaling or check the transfer value of the affected BICO interconnection. Then acknowledge the fault with a POWER ON — switch the converter power supply off and on again.
What is stored in r0949 when F01512 appears?
The fault value, interpreted as a decimal number, gives the unit (for example the unit corresponding to SPEED) for which the factor was sought; the G120XA decoding alternatively gives the parameter number of the BICO input (signal sink).
Why do p2001 and p2002 matter for F01512?
They are the reference values from which the drive forms the conversion factor: p2002/p2001 between a voltage-normalized output and a current-normalized input, or p2001(DO1)/p2001(DO2) when two drive objects have different voltage references.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.