Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F01511BICO: Interconnection with different scalings

What it means

F01511 is raised when a requested BICO interconnection is established between a signal source (BICO output) and a signal sink (BICO input) whose normalized units differ. The drive still makes the interconnection and converts the signal between the two scalings using the reference values. The message appears only for interconnections made within one drive object.

The manual's example: the BICO output carries voltage and the BICO input carries current, so the drive calculates the factor p2002/p2001 between output and input — p2002 holds the reference value for current, p2001 the reference value for voltage.

Depending on the drive's configuration, the same condition can also be signalled as an alarm (A).

Why it appears

  • A requested BICO interconnection was established, and the drive converts between the BICO output and the BICO input using the reference values.
  • The BICO output has different normalized units than the BICO input.
  • The message is only issued for interconnections within a drive object.

What to check

  1. The manuals state that no remedy is necessary: the interconnection remains established and the signal keeps being converted between the two scalings with the reference values.
  2. If you want to trace the interconnection concerned, read the fault value in r0949 as a decimal number — it contains the parameter number of the BICO input (signal sink).

Reading the message value

  • The fault value is held in r0949 and is interpreted as a decimal number: it contains the parameter number of the BICO input, i.e. the signal sink of the interconnection.
  • The message value shows this as Parameter: %1, where %1 stands for that parameter number.

Parameters the manual names

  • p2002 — reference current (I_ref); in the manual's example it is the numerator of the conversion factor p2002/p2001 that the drive calculates between BICO output and BICO input.
  • p2001 — reference voltage; in the example it is the denominator of the factor p2002/p2001.
  • r0949 — fault value; interpreted as a decimal number it gives the parameter number of the BICO input (signal sink) for this message.

Acknowledging and restarting

The drive takes no automatic action: the interconnection stays established and the signal keeps being converted using the reference values, so no remedy is necessary. The message is acknowledged immediately. When the drive signals the same condition as an alarm (A), no reaction follows and no acknowledgement is required.

What differs between the drive families

Straight from the manuals' own fields — F01511 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1425
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2615
G120NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 834
G120XAIMMEDIATELYSINAMICS G120XA PN converter · p. 1111

The drives this code lives on

F01511 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01511 mean on a SINAMICS drive?

A BICO interconnection was established between a signal source and a signal sink that use different normalized units. The drive keeps the interconnection and converts the signal between the two scalings using the reference values.

Does F01511 have to be fixed?

No — the manuals state that no remedy is necessary. The message only tells you that a conversion between different scalings is being made within one drive object.

How do I find the parameter behind F01511?

Read the fault value in r0949 as a decimal number; it contains the parameter number of the BICO input (signal sink). The message value also shows this parameter number.

Can F01511 also appear as an alarm?

Yes, depending on the drive's configuration the same condition can be signalled as an alarm. As an alarm it triggers no reaction and needs no acknowledgement.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.