Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F01054CU: System limit exceeded

What it means

The Control Unit (CU) raises F01054 when at least one system overload has been identified. The fault value in r0949, read as a decimal number, tells which system limit was exceeded: 1 means the computing time load is too high (r9976[1]), 5 means the peak load is too high (r9976[5]). The manuals describe the code identically for every listed converter family, so there are no family-specific causes.

Why it appears

  • At least one system overload has been identified by the Control Unit.
  • Computing time load too high — signalled with fault value 1 (r9976[1]).
  • Peak load too high — signalled with fault value 5 (r9976[5]).

What to check

  1. Read the fault value in r0949 (decimal) to see whether the computing time load (1) or the peak load (5) is too high.
  2. Reduce the computing time load of the drive unit (r9976[1] and r9976[5]) to under 100 %.
  3. Check the sampling times and adjust them if necessary (p0115, p0799, p4099).
  4. Deactivate function modules.
  5. Deactivate drive objects.
  6. Remove drive objects from the target topology.
  7. Note the DRIVE-CLiQ topology rules and, if required, change the DRIVE-CLiQ topology.
  8. When the Drive Control Chart (DCC) or free function blocks (FBLOCKS) are used, read out the computing time load of the individual runtime groups on a drive object in r21005 (DCC) or r20005 (FBLOCKS).
  9. If necessary, change the assignment of the runtime group (p21000, p20000) in order to increase the sampling time (r21001, r20001).
  10. If necessary, reduce the number of cyclically calculated blocks (DCC) and/or function blocks (FBLOCKS).

Reading the message value

  • The drive outputs the fault value as the message value; it is held in r0949 and must be interpreted as a decimal number.
  • 1: Computing time load too high (r9976[1]).
  • 5: Peak load too high (r9976[5]).

Parameters the manual names

  • r0949 (fault value) — read it as a decimal number to see whether fault value 1 or 5 tripped F01054.
  • r9976 (system utilization) — index 1 shows the computing time load, index 5 the peak load; bring both under 100 %.
  • p0971 (save drive object parameters) — saving is not possible as long as F01054 is present.
  • p0977 (save all parameters) — named alongside p0971 in the note of some manuals; likewise blocked while the fault is present.
  • p0115 (sampling time for supplementary functions) — check and adjust if necessary.
  • p0799 (CU inputs/outputs sampling time) — check and adjust if necessary.
  • p4099 (inputs/outputs sampling time) — check and adjust if necessary.
  • r20001 (run-time group sampling time) — can be increased via the runtime group assignment to lower the DCC/FBLOCKS computing load.

Acknowledging and restarting

The drive coasts down (OFF2). Remedy the overload first: as long as the fault is present, it is not possible to save the parameters (p0971; some manuals also name p0977 here). Then acknowledge the fault immediately — after that the drive can be restarted.

What differs between the drive families

Straight from the manuals' own fields — F01054 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2571
G130, G150OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)Control Unit (CU)SINAMICS G130, G150 List Manual · p. 1384
G120OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 828
G120XAOFF2IMMEDIATELYSINAMICS G120XA PN converter · p. 1106

The drives this code lives on

F01054 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F01054 mean?

The Control Unit has identified at least one system overload. The fault value in r0949 (decimal) shows which limit was hit: 1 = computing time load too high (r9976[1]), 5 = peak load too high (r9976[5]).

How do I clear fault F01054?

Reduce the computing time load of the drive unit (r9976[1] and r9976[5]) to under 100 %: check the sampling times (p0115, p0799, p4099), deactivate function modules and drive objects, and review the DRIVE-CLiQ topology. With DCC or FBLOCKS, reduce the number of cyclically calculated blocks or function blocks.

Why can I not save parameters when F01054 is active?

The manual notes that as long as this fault is present it is not possible to save the parameters (p0971, and on some families also p0977). Save only after the overload has been remedied and the fault acknowledged.

What is the fault value of F01054?

It is shown in r0949 and must be read as a decimal number: 1 means the computing time load is too high, 5 means the peak load is too high.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.