What it means
F01055 is an internal error of the CU: the SYNO clock cycle of a port and the SYNO clock cycle of an application are not identical. All applications that operate with slaves at one port must be derived from the same SYNO clock cycle. The first application whose registration (log-on) connects a slave to a port defines the SYNO clock cycle that is used as the basis for this port; the fault is raised when an application at the port does not match that clock cycle. The entries that describe this message carry the same cause and add: Only for internal Siemens troubleshooting.
Why it appears
- All applications that operate with slaves at one port must be derived from the same SYNO clock cycle — the CU has detected an application at a port whose SYNO clock cycle differs from the one the port is based on.
- The SYNO clock cycle of a port is fixed by the first application whose registration (log-on) connects a slave to that port; an application that comes onto the port afterwards must match this clock cycle.
What to check
- Read the fault value in r0949 and note the Method ID it contains (the manual specifies to interpret the value hexadecimal).
- Contact Technical Support and quote the Method ID; the manual names no remedy that can be carried out on the converter itself.
Reading the message value
- The message value (%1) is the Method ID. The drive stores it in r0949, and the manual specifies to interpret this value hexadecimal. No bit-level decoding is printed for this fault value.
Parameters the manual names
- r0949 — fault value: holds the Method ID for this fault; read and note it (interpret hexadecimal) before contacting Technical Support.
Acknowledging and restarting
The drive does not trip on this fault. Acknowledging clears the message but not the underlying condition: the only remedy the manual names is to contact Technical Support, and the fault is explicitly marked Only for internal Siemens troubleshooting
. No parameter change or on-site procedure is described for eliminating the clock-cycle mismatch.
The same on every family
Every manual that describes F01055 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | IMMEDIATELY | Hardware/software error (1) | Control Unit (CU) | SINAMICS S120, S150 List Manual · p. 2571 |
| G130, G150 | NONE | IMMEDIATELY | Hardware/software error (1) | Control Unit (CU) | SINAMICS G130, G150 List Manual · p. 1384 |
The drives this code lives on
F01055 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01055 mean on a SINAMICS drive?
It is an internal error of the CU: the SYNO clock cycle of a port and the SYNO clock cycle of an application are not identical. All applications that operate with slaves at one port must be derived from the same SYNO clock cycle, which the first application that connects a slave to the port defines.
How do I fix F01055?
There is no on-site fix. The manuals mark the fault as only for internal Siemens troubleshooting and give contacting Technical Support as the sole remedy; note the fault value in r0949 first so you can quote it.
What is stored in the fault value of F01055?
The Method ID. The drive writes it to r0949 and the manual says to interpret the value hexadecimal; no bit-level decoding is printed.
Does F01055 trip the drive?
No. No automatic reaction is assigned to this fault, so the converter keeps running; the message appears in the diagnostics and must be acknowledged.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals