Alarm · SINAMICS G130, G150, S120, S150

A32429Encoder 2: Position difference hall sensor/track C/D and A/B too large

What it means

The message appears as Encoder 2: Position difference hall sensor/track C/D and A/B too large. It is raised when the monitoring of Encoder 2 measures an error for track C/D greater than +/-15 ° mechanical or +/-60 ° electrical, or an error for the Hall signals greater than +/-60 ° electrical. One period of track C/D corresponds to 360 ° mechanical and one period of the Hall signal to 360 ° electrical — these are the reference scales behind the tolerances. As an alarm, the drive carries out no automatic response of its own; depending on the drive configuration, the same condition can also be signalled as a fault or without a reaction.

Why it appears

  • The error for track C/D exceeds +/-15 ° mechanical or +/-60 ° electrical, or the error for the Hall signals exceeds +/-60 ° electrical.
  • Hall sensors are connected as an equivalent for track C/D with the incorrect rotational sense — a situation the manual names explicitly as a trigger for this monitoring.
  • The supply values are not accurate enough.

What to check

  1. Establish whether track C or D is not connected.
  2. Correct the direction of rotation of a hall sensor that is possibly connected as an equivalent for track C/D.
  3. Check that the encoder cables are routed in compliance with EMC.
  4. Check the adjustment of the hall sensor.

Reading the message value

The drive writes the measured deviation into the alarm value r2124, which is to be interpreted as a decimal number and is held in 16 bits with sign:

  • For track C/D: the measured deviation as a mechanical angle, where 182 dec corresponds to 1 °.
  • For the Hall signals: the measured deviation as an electrical angle, where 182 dec corresponds to 1 °.

Parameters the manual names

  • r2124 — holds the alarm value of this message; read it as a decimal to see the measured deviation, given in 16 bits with sign where 182 dec corresponds to 1 ° (mechanical angle for track C/D, electrical angle for the Hall signals).

Acknowledging and restarting

As an alarm, the message requires no acknowledgement and clears itself once the difference is back within tolerance; the drive also carries out no automatic response of its own, so removing the cause is all that is needed. If the drive configuration raises the same condition as a fault instead, the fault must be acknowledged immediately before the drive will run again.

The same on every family

Every manual that describes A32429 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Encoder 2SINAMICS S120, S150 List Manual · p. 3108
G130, G150NONENONEActual position/speed value incorrect or not available (11)Encoder 2SINAMICS G130, G150 List Manual · p. 1786

The drives this code lives on

A32429 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A32429 mean on a SINAMICS G130, G150, S120 or S150?

The monitoring of Encoder 2 has detected a position difference between the hall sensor or track C/D and tracks A/B that is too large — more than +/-15 ° mechanical or +/-60 ° electrical on track C/D, or more than +/-60 ° electrical on the Hall signals.

How do I fix alarm A32429?

Check that track C or D is not simply unconnected, correct the rotational sense of a hall sensor used as an equivalent for track C/D, verify EMC-compliant routing of the encoder cables and the adjustment of the hall sensor. The alarm itself needs no acknowledgement.

What does the r2124 value for A32429 tell me?

Read r2124 as a decimal: it holds a signed 16-bit figure in which 182 dec corresponds to 1 °, giving the deviation as a mechanical angle for track C/D or as an electrical angle for the Hall signals.

Can A32429 also appear as a fault?

Yes. Depending on the drive configuration, the same condition can also be signalled as a fault — which must then be acknowledged immediately — or as a message without a reaction.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A32xxx group · SINAMICS manuals · Siemens manuals