What it means
A32422 is an alarm from Encoder 2: the pulses per revolution of the connected square-wave encoder are outside the tolerance bandwidth. In concrete terms, the zero mark distance the drive measures does not correspond to the zero mark distance that is parameterized. The monitoring only takes effect when square-wave encoder PPR correction is active and fault 31131 has been re-parameterized; the alarm is then raised as soon as the accumulator contains larger values than the thresholds p4683 or p4684. For a rotary encoder, the zero mark distance used for zero mark monitoring is set in p0425. Depending on the drive configuration, the same condition can also be output as a fault or as a message with no reaction.
Why it appears
- The measured zero mark distance does not correspond to the parameterized zero mark distance.
- The alarm only becomes active with square-wave encoder PPR correction and re-parameterized fault 31131, when the accumulator contains larger values than p4683 or p4684.
What to check
- Check that the encoder cables are routed in compliance with EMC.
- Check the plug connections.
- Check the encoder type — the encoder must have equidistant zero marks.
- Adapt the parameter for the distance between zero marks (p0424, p0425).
- Replace the encoder or the encoder cable.
Reading the message value
The drive writes the accumulated differential pulses in encoder pulses into the alarm value; it is stored in r2124 and is to be interpreted as a decimal number.
- r2124 (interpret decimal): accumulated differential pulses in encoder pulses
Parameters the manual names
- p0424 — encoder linear zero mark distance: the parameter for the distance between zero marks that the remedy names for adaptation on a linear encoder.
- p0425 — encoder rotary zero mark distance: sets the zero mark distance for zero mark monitoring of a rotary encoder; adapt it when the measured distance deviates.
- p4683 — zero mark monitoring tolerance window alarm threshold positive: the alarm is raised when the accumulated differential pulses are larger than this positive threshold.
- p4684 — zero mark monitoring tolerance window alarm threshold negative: the corresponding negative threshold of the tolerance window.
- r2124 — alarm value: shows the accumulated differential pulses in encoder pulses for this alarm, to be read as a decimal number.
Acknowledging and restarting
As an alarm, A32422 requires no acknowledgment and does not switch the drive off by itself. If the drive is configured so that the same condition appears as a fault instead, the fault must be acknowledged IMMEDIATELY before the drive can be restarted. The condition ends once the measured zero mark distance again corresponds to the parameterized one.
The same on every family
Every manual that describes A32422 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 2 | SINAMICS S120, S150 List Manual · p. 3108 |
| G130, G150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 2 | SINAMICS G130, G150 List Manual · p. 1785 |
The drives this code lives on
A32422 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A32422 on a SINAMICS drive mean?
Encoder 2 reports that the pulses per revolution of the square-wave encoder are outside the tolerance bandwidth: the zero mark distance measured by the drive does not match the parameterized one.
How do I fix A32422?
Check that the encoder cables are routed in compliance with EMC, check the plug connections and verify that the encoder has equidistant zero marks. Then adapt the zero mark distance in p0424/p0425 or replace the encoder or encoder cable.
What is stored in the alarm value of A32422?
The value in r2124, interpreted as a decimal number, contains the accumulated differential pulses in encoder pulses.
Does A32422 stop the drive?
No. As an alarm there is no automatic shutdown and no acknowledgment is required; only if the condition is configured as a fault must it be acknowledged IMMEDIATELY before a restart.