Alarm · SINAMICS G130, G150, S120, S150

A32419Encoder 2: Track A or B outside tolerance

What it means

A32419 reports that a correction which the drive applies to the signals of Encoder 2 has reached its limit: the drive continuously corrects the amplitude, phase and offset of tracks A and B, and one of these corrections is now at the edge of its range. The alarm value stored in r2124 identifies which correction on which track is affected. Depending on the drive's configuration, the same condition can also be issued as a fault or with no reaction (N) instead of as this alarm.

Why it appears

  • One of the corrections the drive applies to the track A or track B signal of Encoder 2 — amplitude, phase or offset — has reached its limit.
  • The drive treats the correction as being at the limit when the amplitude error correction sits at Amplitude B / Amplitude A = 0.78 ... 1.27, when the phase falls below 84 degrees or rises above 96 degrees, or when the offset correction reaches +/-140 mV with an SMC20 or +/-650 mV with an SMC10.

What to check

  1. For encoders without their own bearings, for example toothed-wheel encoders, check the mechanical mounting tolerances.
  2. Check the plug connections, also with regard to transition resistance.
  3. Check the encoder signals.
  4. Replace the encoder or the encoder cable.

Reading the message value

  • The drive stores an alarm value in r2124 which shows which correction has reached which limit; interpret the value hexadecimal:
  • xxxx1: Minimum of the offset correction, track B
  • xxxx2: Maximum of the offset correction, track B
  • xxx1x: Minimum of the offset correction, track A
  • xxx2x: Maximum of the offset correction, track A
  • xx1xx: Minimum of the amplitude correction, track B/A
  • xx2xx: Maximum of the amplitude correction, track B/A
  • x1xxx: Minimum of the phase error correction
  • x2xxx: Maximum of the phase error correction
  • 1xxxx: Minimum of the cubic correction
  • 2xxxx: Maximum of the cubic correction

Parameters the manual names

  • r2124 — alarm value of this message; read it in hexadecimal to determine which correction (offset, amplitude, phase error or cubic) on track A or B has reached its minimum or maximum.

Acknowledging and restarting

As an alarm, A32419 requires no acknowledgement, and the drive performs no automatic stop for this condition. If the drive configuration outputs the same condition as a fault instead, the drive likewise performs no automatic stop and the fault can be acknowledged immediately. The no-reaction variant needs no acknowledgement either.

The same on every family

Every manual that describes A32419 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Encoder 2SINAMICS S120, S150 List Manual · p. 3107
G130, G150NONENONEActual position/speed value incorrect or not available (11)Encoder 2SINAMICS G130, G150 List Manual · p. 1784

The drives this code lives on

A32419 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A32419 mean?

It means that one of the corrections the drive applies to the track A or track B signal of Encoder 2 — amplitude, phase or offset — has reached its limit. The alarm value in r2124 shows which correction and which track are affected.

How do I clear alarm A32419?

Check the mechanical mounting tolerances for encoders without their own bearings such as toothed-wheel encoders, check the plug connections including the transition resistance, check the encoder signals, and replace the encoder or the encoder cable.

Does A32419 stop the drive?

No. The drive raises it as an alarm without an automatic stop and without acknowledgement. If it is configured to appear as a fault instead, the fault can be acknowledged immediately.

How do I interpret the r2124 alarm value for A32419?

Read the value hexadecimal: each digit position identifies the correction concerned — for example xxxx1 is the minimum of the offset correction on track B, x1xxx the minimum of the phase error correction, and 1xxxx the minimum of the cubic correction.