What it means
A30031 reports that the hardware current limiting of the power unit has responded in phase U. The response is brief by design: pulsing in that phase is inhibited for one pulse period, and the drive takes no further action on its own. The manuals add a note that helps read the message correctly: the hardware current limiting is monitored separately for each output phase, and this alarm is always output when the limiting responds in phase U of a Power Module — the other phases have alarms of their own.
Why it appears
- The closed-loop control parameters do not match the motor as parameterized and connected.
- The motor or its power cables are faulty.
- The power cables exceed the maximum permissible length.
- The load on the motor is too high.
- The power unit is defective.
What to check
- Check the motor data against the motor actually connected; if they do not match, recalculate the control parameters (p0340 = 3). Running a motor data identification (p1910 = 1, p1960 = 1) is the alternative the manual offers.
- Check the motor circuit configuration (star/delta).
- Check the motor load.
- Check the power cable connections.
- Examine the power cables for a short-circuit or ground fault.
- Check that the length of the power cables stays within the maximum permissible length.
Parameters the manual names
- p0340 — set to 3 to have the control parameters recalculated automatically from the motor data when they do not fit the connected motor.
- p1910 — set to 1 to run a motor data identification, the manual's alternative to recalculating with p0340.
- p1960 — selects the moving measurement performed during that identification and is set to 1 together with p1910.
Acknowledging and restarting
No acknowledgement is needed: the alarm clears itself as soon as the hardware current limiting no longer responds in the phase. If it keeps returning, work through the checks above — a repeated response points to the motor data and parameters, the motor and its power cables, the load, or a defective power unit.
What differs between the drive families
Straight from the manuals' own fields — A30031 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Power electronics faulted (5) | Power Module | SINAMICS S120, S150 List Manual · p. 2949 |
| G130, G150 | NONE | NONE | Power electronics faulted (5) | Power Module | SINAMICS G130, G150 List Manual · p. 1659 |
| G120 | NONE | NONE | Power electronics faulted (5) | — | SINAMICS G120 · p. 912 |
| G120XA | NONE | NONE | — | — | SINAMICS G120XA PN converter · p. 1158 |
The drives this code lives on
A30031 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A30031 mean on a SINAMICS drive?
The hardware current limit of the power unit has responded in phase U. Pulsing in that phase is inhibited for one pulse period, and the drive otherwise takes no action.
Does A30031 have to be acknowledged?
No. The alarm needs no acknowledgement and disappears by itself once the hardware current limiting no longer responds.
Can a motor cable that is too long trigger A30031?
Yes. Power cables exceeding the maximum permissible length are one of the listed causes, so the cable length should be checked along with the connections and a possible short-circuit or ground fault.
How do I correct wrong control parameters after A30031?
Check the motor data and recalculate the control parameters with p0340 = 3, or alternatively run a motor data identification with p1910 = 1 and p1960 = 1.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.