SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A07927DC braking active

What it means

The drive reports that DC braking is active: the motor is currently being braked by DC current fed into it. A07927 is an informational alarm rather than a fault — the manual states that no remedy is necessary and that the alarm disappears by itself once DC braking has been executed.

Why it appears

  • A message with response DCBRK is active: the motor is braked with the braking current set in p1232 for the duration set in p1233. If the standstill threshold p1226 is undershot, braking is canceled prematurely.
  • DC braking has been activated at binector input p1230 with the DC braking set (p1230 = 4): the braking current p1232 is injected until this binector input becomes inactive.

What to check

  1. No action is necessary — the alarm only reports that DC braking is running.
  2. The alarm automatically disappears once DC braking has been executed; nothing has to be acknowledged.
  3. If the DC braking was not expected, identify which of the two activation paths listed under causes applies — a message with response DCBRK, or the binector input p1230 = 4.

Parameters the manual names

  • p1232 (DC braking braking current / DCBRK I_brake) — sets the DC current injected into the motor while DC braking is running.
  • p1233 (DC braking time / DCBRK time) — sets how long the braking current flows when DC braking is started by a message with response DCBRK.
  • p1226 (threshold for zero speed detection / n_standst n_thresh) — if the speed undershoots this threshold, DC braking is canceled prematurely.
  • p1230 (BI: Armature short-circuit / DC braking activation / ASC/DCBRK act) — binector input used to switch DC braking on directly; with p1230 = 4 the braking current p1232 is injected until the input becomes inactive.

Acknowledging and restarting

No acknowledgment is required. The alarm is withdrawn automatically as soon as DC braking has been executed — after the braking time p1233 has elapsed when it was started by a DCBRK response, or when the binector input p1230 becomes inactive again.

What differs between the drive families

Straight from the manuals' own fields — A07927 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEApplication/technological function faulted (17)MotorSINAMICS G130, G150 List Manual · p. 1612
S120, S150NONENONEApplication/technological function faulted (17)MotorSINAMICS S120, S150 List Manual · p. 2884
G120NONENONEApplication/technological function faulted (17)SINAMICS G120 · p. 889
G120XANONENONESINAMICS G120XA PN converter · p. 1140
G115DSINAMICS G115D distributed drive · p. 394
G120CSINAMICS G120C Converters · p. 385

The drives this code lives on

A07927 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07927 DC braking active mean on a SINAMICS drive?

The motor is currently being braked by DC current injected by the drive. It is an informational alarm, not a fault, and needs no action.

How do I clear A07927?

You do not have to — the alarm is withdrawn automatically once DC braking has been executed, and no acknowledgment is needed.

Why does A07927 appear?

Either a message with response DCBRK is braking the motor with the current in p1232 for the time in p1233, or DC braking was switched on at binector input p1230 (p1230 = 4), in which case the braking current flows until the input goes inactive.

Which parameters belong to DC braking?

p1232 sets the braking current, p1233 the braking time, p1226 the standstill threshold that can cancel braking early, and p1230 the binector input that activates DC braking.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A07xxx group · SINAMICS manuals · Siemens manuals