A07929Drive: No motor detected

What it means

A07929 ("Drive: No motor detected") is raised when the absolute current value is so small after enabling the inverter pulses that no motor is detected — the current does not reach the output load identification current limit (p2179). Depending on how the drive is configured, the same condition can also be output as a fault rather than as this alarm.

The inverter takes no automatic action on this alarm, and no acknowledgement is required. In the case of vector control and an induction motor, this alarm is followed by fault F07902. On the G120XA with a PM330 power module, correction currents are calculated and displayed in the optimized pulse pattern range.

Why it appears

  • The absolute current value is so small after enabling the inverter pulses that no motor is detected — the measured current stays below the threshold in p2179. Both the G120 and the G120XA manual give this as the single cause; no other causes are listed.

What to check

  1. Check the motor feeder cables.
  2. Reduce the threshold value in p2179 — the manual names this measure explicitly for synchronous motors.
  3. Increase the threshold value (PM330) — this step is described for the G120XA with a PM330 power module.
  4. Check the voltage boost of the U/f control (p1310).
  5. Carry out a standstill measurement to set the stator resistance (p0350).

Parameters the manual names

  • p2179 — Output load identification current limit: the threshold evaluated after the pulses are enabled; reduce it when the alarm appears, e.g. for synchronous motors.
  • p1310 — Starting current (voltage boost) permanent: check this voltage boost of the U/f control as one of the remedies for this alarm.
  • p0350 — Motor stator resistance cold: set it by carrying out a standstill measurement, as the manual prescribes for this alarm.

Acknowledging and restarting

The alarm requires no acknowledgement, and the inverter takes no automatic action when it is raised. Remove the underlying cause first: check the motor feeder cables, adjust the thresholds (p2179, or the PM330 threshold on the G120XA), check the U/f voltage boost (p1310) and, if required, set the stator resistance (p0350) via a standstill measurement. Once the current after enabling the pulses is large enough for a motor to be detected, the alarm no longer appears.

What differs between the drive families

Straight from the manuals' own fields — A07929 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G120XANONENONESINAMICS G120XA PN converter · p. 1140
G120NONENONEApplication/technological function faulted (17)SINAMICS G120 · p. 889

The drives this code lives on

A07929 is described for G120, G120XA. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A07929 mean?

The absolute current was so small after the inverter pulses were enabled that no motor was detected. The alarm takes no automatic action and needs no acknowledgement; with vector control and an induction motor it is followed by fault F07902.

How do I fix A07929 on a G120 or G120XA?

Check the motor feeder cables, reduce the threshold in p2179 (the manual names this especially for synchronous motors) and check the U/f voltage boost in p1310. If the alarm persists, carry out a standstill measurement to set the stator resistance in p0350; on the G120XA the threshold for the PM330 power module can also be increased.

Which threshold belongs to A07929?

p2179, the output load identification current limit. The drive detects no motor when the current after pulse enablement stays below it, and reducing this threshold is one of the manual's remedies, e.g. for synchronous motors.

Does A07929 have to be acknowledged?

No — the manuals for the G120 and the G120XA specify no acknowledgement for this alarm, and the inverter takes no automatic action when it is raised.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.