Alarm · SINAMICS G130, G150, S120, S150

A07918Three-phase setpoint generator operation selected/active

What it means

A07918 is an alarm (and can, depending on the drive configuration, also be output without any reaction, N) that reports the following operating state: the drive is set for a separately excited synchronous motor (p0300 = 5) and the active open-loop/closed-loop control mode is I/f control (open-loop) with a fixed current (p1300 = 18). In this mode the speed comes from the setpoint channel, while the current setpoint is fixed at the stator minimum current p1620. The message draws attention to the fact that the control dynamic performance in this mode is very limited, so longer ramp-up times for the speed setpoint are expected than in normal operation.

Why it appears

  • Only for separately excited synchronous motors (p0300 = 5): the selected open-loop/closed-loop control mode is I/f control (open-loop) with a fixed current (p1300 = 18); the speed is entered via the setpoint channel and the current setpoint is given by the stator minimum current p1620.
  • The drive raises the message because in this mode the control dynamic performance is very limited — longer ramp-up times should be set for the setpoint speed than for normal operation.

What to check

  1. Check p0300: the message is only issued when the motor is configured as a separately excited synchronous motor (p0300 = 5).
  2. If the limited control dynamic performance of this mode does not suit the application, select another open-loop/closed-loop control mode in p1300 — this is the remedy the manual gives.
  3. If the drive stays in I/f control with fixed current (p1300 = 18), set longer ramp-up times for the setpoint speed than for normal operation.

Parameters the manual names

  • p0300 (Motor type selection) — must read 5 (separately excited synchronous motor) for this alarm to appear; check it first.
  • p1300 (Open-loop/closed-loop control operating mode) — value 18 (I/f control, open-loop, fixed current) is what triggers A07918; selecting another mode here is the remedy.
  • p1620 (Stator current minimum) — in this mode it supplies the fixed current setpoint the drive runs with.

Acknowledging and restarting

No acknowledgment is needed and the drive does not trip: the condition is signalled while the mode is selected, and the alarm is gone once another open-loop/closed-loop control mode has been chosen in p1300. As long as p1300 = 18 remains set, the message stays present.

The same on every family

Every manual that describes A07918 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2882
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1610

The drives this code lives on

A07918 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07918 on a SINAMICS drive mean?

It reports that I/f control (open-loop) with a fixed current (p1300 = 18) is selected and active while the motor is configured as a separately excited synchronous motor (p0300 = 5). The speed comes from the setpoint channel and the current setpoint from p1620.

Does A07918 stop the drive or have to be acknowledged?

No. The drive keeps operating and no acknowledgment is required; the message is present while the mode is selected and disappears when another control mode is chosen in p1300.

How do I clear A07918?

Select another open-loop/closed-loop control mode in p1300. If the application must stay in I/f control with fixed current, set longer ramp-up times for the speed setpoint, because the control dynamic performance is very limited in this mode.

Which motors does A07918 relate to?

Only separately excited synchronous motors, i.e. drives set to p0300 = 5; for other motor settings the message is not issued.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.