SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A07903Drive: Motor speed deviation

What it means

A07903 reports that the motor speed is not following its setpoint closely enough: the absolute difference between the speed setpoint and the smoothed speed actual value (r2169) has exceeded the tolerance threshold p2163 for longer than the monitoring tolerates (p2164, p2166). The alarm is only enabled when p2149.0 = 1. Depending on the drive, one setpoint (p2151) or two setpoints (p2151 and p2154) are monitored against the actual value.

Why it appears

  • The load torque is greater than the torque setpoint.
  • When accelerating, the torque, current or power limit is reached — and if the limits are not sufficient, the drive may have been dimensioned too small.
  • In closed-loop torque control, the speed setpoint does not track the speed actual value (not every manual lists this cause).
  • The Vdc controller is active.
  • With U/f control, the overload condition is detected because the I_max controller is active.

What to check

  1. Increase p2163 and/or p2166 so that brief speed deviations no longer trip the alarm.
  2. Increase the torque, current and power limits; if they are genuinely insufficient for the load, the drive has probably been dimensioned too small.
  3. For closed-loop torque control, make sure the speed setpoint tracks the speed actual value.
  4. If the monitoring is not wanted for the application, deactivate the alarm by setting p2149.0 = 0.

Parameters the manual names

  • p2149 — monitoring configuration: bit 0 must be 1 for this alarm to be active, and p2149.0 = 0 is the manual's way to switch A07903 off.
  • p2151 — speed setpoint (CI) that the deviation monitoring compares with the actual speed.
  • p2154 — second speed setpoint (CI); on drives that monitor two setpoints it is evaluated together with p2151.
  • r2169 — smoothed speed actual value (CO) against which the setpoints are checked.
  • p2163 — the velocity threshold the speed difference must stay below to avoid the alarm.
  • p2164 — hysteresis belonging to that speed threshold.
  • p2166 — off-delay time that defines how long the deviation is tolerated before A07903 comes.

Acknowledging and restarting

No acknowledgement is needed for this code: it is an alarm without a fault reaction, and it clears itself once the speed difference falls back within the p2163 tolerance for the tolerated time. If it keeps returning, work through the checks above instead of merely raising the thresholds.

What differs between the drive families

Straight from the manuals' own fields — A07903 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Application/technological function faulted (17)MotorSINAMICS S120, S150 List Manual · p. 2876
G130, G150NONENONEApplication/technological function faulted (17)MotorSINAMICS G130, G150 List Manual · p. 1606
G120NONENONEApplication/technological function faulted (17)SINAMICS G120 · p. 886
G120XANONENONESINAMICS G120XA PN converter · p. 1138
G115DSINAMICS G115D distributed drive · p. 394
G120CSINAMICS G120C Converters · p. 385

The drives this code lives on

A07903 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07903 mean on a SINAMICS drive?

It means the motor speed deviates from the speed setpoint by more than the p2163 tolerance for longer than p2164/p2166 allow. The monitoring is only enabled when p2149.0 = 1.

How do I reset A07903?

No acknowledgement is required — the alarm clears itself once the speed difference returns within tolerance. If the monitoring is not wanted, setting p2149.0 = 0 deactivates it.

Why does A07903 appear during acceleration?

Because the torque, current or power limit is reached while accelerating. If those limits are not sufficient, the drive may have been dimensioned too small.

Which setpoints does A07903 monitor?

The manual compares the smoothed actual speed r2169 with p2151, and on some drives additionally with the second setpoint p2154. In closed-loop torque control the alarm indicates that the setpoint does not track the actual value.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A07xxx group · SINAMICS manuals · Siemens manuals