What it means
A07893 (Drive: Load monitoring pump leakage) is issued when the drive's load monitoring is configured for a pump (p2193 = 4) and detects a leak in the pump circuit. With a leak, the pump requires a lower torque than in normal operation to pump the reduced quantity — that drop in torque is what the monitoring function evaluates. The code appears as an alarm; the drive does not intervene by itself, the monitoring function only reports the condition, and the remedy lies in the pump circuit or in the threshold settings.
Why it appears
- The load monitoring is configured for a pump (p2193 = 4).
- The monitoring function has detected a leak in the pump circuit.
- Because of the leak, the pump requires a torque that is lower than in normal operation to pump the reduced quantity.
What to check
- Remove the leak in the pump circuit.
- If the alarm is a nuisance trip, reduce the torque thresholds of the leakage characteristic (p2186, p2188, p2190).
Parameters the manual names
- p2193 (load monitoring configuration): the value 4 sets the load monitoring to pump mode — the configuration in which this leakage alarm is generated.
- p2186 (load monitoring torque threshold 1 lower): reduce this threshold of the leakage characteristic if the alarm trips as a nuisance.
- p2188 (load monitoring torque threshold 2 lower): second threshold of the leakage characteristic, reduced on a nuisance trip.
- p2190 (load monitoring torque threshold 3 lower): third threshold of the leakage characteristic, reduced together with p2186 and p2188 on a nuisance trip.
What differs between the drive families
Straight from the manuals' own fields — A07893 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120 | NONE | NONE | Application/technological function faulted (17) | — | SINAMICS G120 · p. 884 |
| G120XA | NONE | NONE | — | — | SINAMICS G120XA PN converter · p. 1136 |
The drives this code lives on
A07893 is described for G120, G120XA. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A07893 mean on a SINAMICS drive?
The load monitoring, configured for a pump (p2193 = 4), has detected a leak in the pump circuit: the pump needs less torque than in normal operation to pump the reduced quantity.
How do I fix A07893?
Remove the leak in the pump circuit. If the alarm is a nuisance trip, reduce the torque thresholds of the leakage characteristic in p2186, p2188 and p2190.
Why does A07893 appear although there is no real leak?
That points to a nuisance trip; the remedy the manuals give is to reduce the torque thresholds of the leakage characteristic (p2186, p2188, p2190).
Which parameter configures the pump leakage monitoring?
p2193, the load monitoring configuration — the value 4 sets it to pump mode, in which this alarm is generated.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.