What it means
A02051 is an alarm from the trace function: a recording cannot be carried out because at least one of the signals involved — a recorded signal or the trigger signal — is under know-how protection. The cause lies on the configuration and commissioning side, not in a hardware fault. The same alarm text is used on the G120, G130, G150, S120 and S150.
Why it appears
- A trace function is configured on the drive, and at least one signal that it uses — one of the recorded signals or the trigger signal — is under know-how protection, so the trace recording is not possible.
- The protected signal can be one of the trace record signals (p4730 to p4737) or the trace trigger signal (p4711).
What to check
- Read the alarm value in r2124 to identify the recorder concerned: on the G120, G130 and G150 the value is interpreted as a decimal number — 1: Recorder 0, 2: Recorder 1, 3: Recorders 0 and 1. On the S120 and S150 it is interpreted as hexadecimal bbbbaaaa, where aaaa identifies the recorder and bbbb is the parameter number (hexadecimal) that was not able to be written to.
- Use the trace configuration to find the signal under know-how protection: the trace control (p4700), the trace trigger signal (p4711) and the trace record signals 0 to 7 (p4730 to p4737) show which signals the recorder uses.
- Then apply one of the remedies: temporarily activate or deactivate know-how protection (p7766), include the signal in the OEM exception list (p7763 sets the number of indices for p7764, p7764 is the exception list itself), or — where relevant — do not record the signal.
Reading the message value
- The drive stores the alarm value in r2124.
- G120, G130, G150 — interpret r2124 as a decimal number: 1: Recorder 0, 2: Recorder 1, 3: Recorders 0 and 1.
- S120, S150 — interpret r2124 as hexadecimal bbbbaaaa: aaaa = 1: recorder 0; aaaa = 2: recorder 1; aaaa = 3: recorders 0 and 1; bbbb = parameter number (hexadecimal) that was not able to be written to.
- Message value:
initiating recorder: %1, parameter %2
(S120, S150);involves %1
(G130, G150).
Parameters the manual names
- r2124 — alarm value: shows which recorder is affected and, on the S120/S150, the number of the parameter that could not be written to.
- p4700 — trace control: the configuration of the trace function whose recording is blocked.
- p4711 — trace trigger signal: the trigger of the trace; its source can be the signal under know-how protection.
- p4730 to p4737 — trace record signals 0 to 7: the signals the trace records; check here which one is protected.
- p7766 — KHP password input: used to temporarily activate or deactivate know-how protection.
- p7763 — KHP OEM exception list, number of indices for p7764: sets how many entries the OEM exception list has.
- p7764 — KHP OEM exception list: the list into which the affected signal is included.
Acknowledging and restarting
This alarm requires no acknowledgement, and the drive takes no automatic action in response to it. Nothing has to be reset: the condition is removed by the configuration changes themselves — temporarily activating or deactivating know-how protection (p7766), including the signal in the OEM exception list (p7763, p7764) or no longer recording the signal.
What differs between the drive families
Straight from the manuals' own fields — A02051 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2730 |
| G130, G150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1504 |
| G120 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 862 |
The drives this code lives on
A02051 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A02051 mean on a SINAMICS drive?
A trace recording cannot be carried out because at least one signal or trigger signal used by the trace is under know-how protection.
How do I clear alarm A02051?
Either temporarily activate or deactivate know-how protection with p7766, include the signal in the OEM exception list (p7763, p7764), or stop recording the signal. No acknowledgement is needed.
How can I see which recorder caused A02051?
Read the alarm value in r2124: the values 1, 2 and 3 stand for recorder 0, recorder 1 or both recorders. On the S120 and S150 the value also contains the parameter number that could not be written to, read as hexadecimal bbbbaaaa.
Does A02051 stop the drive?
No. The drive takes no automatic action in response to this alarm; only the trace recording is blocked.