YORK YVAAfault codes

Fault, warning and safety-shutdown messages documented by Johnson Controls for the YORK YVAA. Each row cites the page of the manual it was taken from — nothing here is summarised or reworded.

From YVAA Style A with VSD, Frame size 015-027 2-Compressor, Frame size 054-098, 2-Compressor 50 Hz (525-950 KW) R-134a or R-513A Installation, Operation and Maintenance 201.28-NM1.1.EN.GB

Original: docs.johnsoncontrols.com

Commissioning

Code / displayMeaningCauseActionPage
Sys2 - single phase input VoltsFault reported by the unit; the unit does not start.Power-on sequence reversed on YVAA0373/0375/0413/0443/0483/0490/0500/0523 units (independent circuit breaker/disconnect switches in each conduit of Sys1 and Sys2): Sys1 powered before Sys2.Ensure that the Sys2 power is on first and then Sys1 by closing the corresponding circuit breaker or disconnect switch.89

Unit Warnings

Code / displayMeaningCauseActionPage
UNIT WARNING: !! LOW BATTERY !!
CHECK SETPOINTS/PROGRAM/OPTIONS/TIME
Low RTC battery condition detected at micropanel power-up; warning displayed indefinitely. Warnings are not logged to the history buffer; message is displayed when the STATUS key is pressed.RTC battery voltage determined to be low when checked at unit power-up.All programmed setpoints, program values, time, schedule, and history buffers will have been lost and reset to default values. Unit is prevented from running until the MANUAL OVERRIDE key is pressed (anti-recycle timers then set to the programmed default anti-recycle time to allow the operator time to check setpoints, program values, etc.). Replace the battery as soon as possible; if a low battery is detected and not replaced, the programmed values will all be lost and the unit will be prevented from running on the next power interruption.102
UNIT WARNING:
INVALID NUMBER OF COMPRESSORS SELECTED
Warning displayed indefinitely after the VSD has been initialized.No jumpers installed or more than 1 jumper installed ("Number of Compressors Select" message displayed).To clear this warning, both the control panel and VSD control voltage must be turned OFF and the jumpers correctly installed in the VSD wiring harness. Jumpers are factory installed in the wire harness plug and should not require changes.111
UNIT WARNING: INVALID SERIAL NUMBER
ENTER UNIT SERIAL NUMBER
The appearance of this message may mean the chiller has lost important factory programmed information; the serial number and other important data may need to be reprogrammed.Immediately contact Johnson Controls Product Technical Support. The serial number can be entered using the SERVICE key (date and time must be set on the chiller before programming; factory-provided password required). This status message can be bypassed to view additional messages under the STATUS key by pressing the STATUS key repeatedly.111

Unit safeties

Code / displayMeaningCauseActionPage
UNIT YYYYYYYY
HIGH AMBIENT TEMP
Unit safety shutdown on high ambient temperature (auto-reset unit fault; YYYYYYYY indicates FAULT condition).Ambient temperature rises above 55°C (131°F).Controlled ramped shutdown. Restart will automatically occur, if demand allows, when temperature falls 1.1°C (2°F) below the cutout (53.9°C [129°F]). This fault cannot cause a lockout. Message present only while ambient temperature is causing the fault condition. Unit also inhibited from starting any time the temperature is above 53.9°C (129°F).112
UNIT YYYYYYYY
LOW AMBIENT TEMP
Unit safety shutdown on low ambient temperature (auto-reset unit fault; YYYYYYYY indicates FAULT condition).Ambient temperature falls below the programmable Low Ambient Temp Cutout. This fault only occurs if the Low Ambient Cutout is "ENABLED" under the OPTIONS key.Controlled ramped shutdown. Restart can occur, if demand allows, when temperature rises 1.1°C (2°F) above the cutout. This fault cannot cause a lockout. Unit also inhibited from starting any time the temperature is below the cutout plus 1.1°C (2°F).112
UNIT YYYYYYYY
LOW LEAVING CHILLED LIQUID TEMP
Protects the chiller from an evaporator freeze-up should the chilled liquid temp drop below the freeze point (auto-reset unit fault; YYYYYYYY indicates FAULT condition).Leaving chilled liquid temperature (water or brine) drops below the programmable cutout point. Situation could occur under low flow conditions or if the Micro Panel setpoint values are incorrectly programmed.Fault and controlled ramped shutdown. Restart can occur, if demand allows, when chilled liquid temperature rises 2.2°C (4°F) above the cutout. This fault cannot cause a lockout. Unit inhibited from starting any time the chilled liquid temperature is below the cutout plus 2.2°C (4°F).112
UNIT YYYYYYYY
VSD COMMUNICATIONS FAILURE
Prevents the unit from trying to run if the Chiller Control Board never initializes communications with the VSD Logic Board; shuts the unit down if communications are lost while the chiller is operating.On power-up, no reply from the VSD Logic Board within 8 seconds; during normal operation, no valid response to messages received for 8 seconds.All compressors shut down on a Comms fault with a controlled ramped shutdown. Unit inhibited from starting until communications is established. Fault automatically resets when the Chiller Control Board receives a valid response from the VSD for a data request. Note: if any 3 VSD unit faults occur within 90 minutes, the unit will be locked out on the last fault; a VSD lockout requires a manual reset using the system switches — both system switches must be cycled OFF and ON to clear.113

System safeties (faults)

Code / displayMeaningCauseActionPage
SYS X YYYYYYYY HIGH DISCHARGE PRESSURESoftware high discharge pressure cutout. X indicates the system; YYYYYYYY indicates the system is in a FAULT condition (restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).Discharge pressure rises above 22.4 barg (325 psig) for 0.5 seconds.Controlled ramped shutdown. System allowed to restart when the discharge pressure falls to 20.3 barg (295 psig); system also inhibited from starting if the pressure is above 20.3 barg (295 psig). Lockout occurs on the third fault in 90 minutes; lockout cleared by cycling the respective system switch OFF and ON.113
SYS X YYYYYYYY HPCO FAULTMechanical (hardware) High Pressure Cutout protecting the system from dangerously high discharge pressure. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.Mechanical high pressure cutout contacts open — cutout opens at 23.2 barg ± 0.55 barg (337 psig ± 8 psig) and closes at 17.4 barg ± 0.69 barg (252 psig ± 10 psig). Wired in series with the VSD Run Signal and only checked when the system is running; fault occurs immediately and does not wait the 3 seconds typical of most system faults.Immediate shutdown. Restart when the 120 second anti-recycle timer times out, or LOCKOUT until the operator clears the fault using the keypad.114
SYS X YYYYYYYY LOW SUCTION PRESSUREProgrammable Low Suction Pressure Cutout — protects the chiller from an evaporator freeze-up if the system attempts to run with a low refrigerant charge. X indicates the system number.Suction pressure falls below the programmable Suction Pressure Cutout. Cutout is ignored at system start for the programmed Suction Pressure Startup Bypass Time, then linearly ramped from 10% to 100% of the programmed Suction Pressure Cutout; shutdown occurs if the suction pressure falls below the ramped cutout during the ramp or below the programmed cutout after the ramp.System shuts down. Causes a lockout on the third fault in 90 minutes; lockout cleared by cycling the respective system switch OFF and ON.114
SYS X YYYYYYYY LOW SUCT PRES SMART FREEZELow suction pressure smart freeze safety (R-134a and R-513A refrigeration systems). X indicates the system number.Suction Pressure is below the programmable Suction Pressure Override Threshold (Suction Pressure Cutout in psig + 1.7 psig) longer than the programmable Smart Freeze Timer.Safety fault is released when the Suction Pressure >= Suction Pressure Override Threshold. Causes a lockout on the third fault in 90 minutes.114
SYS X YYYYYYYY LOW MOTOR CURRENTMotor Current Cutout — shuts the system down when the microprocessor detects the absence of motor current, usually indicating that a compressor is not running. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.Motor current less than 10% FLA; safety is ignored for the first 10 seconds of operation.Controlled ramped shutdown. Restart when the 120 second anti-recycle timer times out, or LOCKOUT until the operator clears the fault using the keypad.114
SYS X YYYYYYYY HIGH DIFF OIL PRESSUREProtects the compressor from low oil flow and insufficient lubrication, possibly from a dirty oil filter. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.Discharge to Oil Differential Pressure rises above the cutout of 4.48 barg (65 psid) — measures the pressure differential between discharge and oil pressure (pressure drop across the oil filter); safety ignored for the first 90 seconds of run time.Controlled ramped shutdown. Restart when the 120 second anti-recycle timer times out, or LOCKOUT until the operator clears the fault using the keypad.114
SYS X YYYYYYYY LOW DIFF OIL PRESSUREProtects the compressor from low oil flow and insufficient lubrication; ensures the compressor is pumping sufficiently to push oil through the oil cooling circuit and internal compressor lubrication system. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.Differential between oil and suction pressure falls below the cutout. Safety ignored for the first 60 seconds of run time; thereafter the cutout is linearly ramped from 0 barg to 2.09 barg (0 psid to 30 psid) in 5 to 10 minutes based on ambient temperature (Table 15). A 30 second safety bypass below 50 Hz is employed during rampdown (needed when another compressor is being brought on and the running compressor is ramped down to 5 Hz) to prevent nuisance low oil differential trips.Controlled ramped shutdown. Restart when the 120 second anti-recycle timer times out, or LOCKOUT until the operator clears the fault using the keypad.115
SYS X YYYYYYYY HIGH DISCHARGE TEMPProtects the motor and compressor from overheating. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.Discharge Temperature rises above 121°C (250°F); system also inhibited from starting if the discharge temperature is above 93°C (200°F).Controlled ramped shutdown. Restart when the 120 second anti-recycle timer times out, or LOCKOUT until the operator clears the fault using the keypad.115
Low discharge superheat cutout fault
(display wording not printed in manual)
Helps protect the compressor from liquid floodback through the economizer line due to a high flashtank level, and from excessive oil in circulation due to excess oil charge in the system (entrained liquid refrigerant drops out once it enters the compressor).Discharge superheat falls below 2.8°C (5.0°F) for 5 minutes. Safety is ignored for the first 10 minutes of operation if the system economizer feed valve is closed (0%) and for 5 minutes of operation if the economizer feed valve is open greater than 0%.System shuts down. Restart when the 120 second anti-recycle timer times out, or LOCKOUT until the operator clears the fault using the keypad.115
SYS X YYYYYYYY SENSOR FAILURE:
ZZZZZZZZZZZZ
Prevents the system from running when a critical sensor (transducer, level sensor, or motor winding temp sensor) is not functioning correctly and reading out of range. X indicates the specific system; YYYYYYYY indicates FAULT (restarts when the fault clears) or LOCKOUT after 3 faults; ZZZZZZZZZZZ indicates the failed sensor.Sensor failed or reading out of range (high or low); checked at startup and also during operation. Failed sensor indicated as SUCT PRESS, OIL PRESS, DSCH PRESS, or MOTOR TEMP X. Start inhibit sensor thresholds (Table 18): Suction Transducer 0.3 VDC to 4.7 VDC; Oil Transducer 0.3 VDC to 4.7 VDC; Discharge Transducer 0.3 VDC to 4.7 VDC; Motor Temp. Sensor 0°C (0ºF) to 116°C (240ºF).Prevents the system from running at startup; faults and shuts down a system while in operation if a safety threshold is exceeded or a sensor reads out of range. Restarts when the fault clears, or LOCKOUT after 3 faults until the operator clears the fault using the keypad. The Unit Setup Mode allows a specific motor temperature sensor to be ignored if it fails.116
SYS X YYYYYYYY HIGH MOTOR TEMPPrevents a compressor from running when its motor temperature is too high. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.Any compressor motor temperature sensor rises above 121°C (250°F); system inhibited from starting if its motor temperature sensors indicate temperatures above 116°C (240°F). If any single temperature sensor is being ignored under the Unit Set-up Mode, that sensor is not utilized when evaluating motor temperature.Fault and shutdown. Restart when the fault clears, or LOCKOUT until the operator clears the fault using the keypad.117
SYS X YYYYYYYY CONTROL VOLTAGEAlerts the operator that the 115 V AC Control voltage to one of the systems is missing. X indicates the system; YYYYYYYY indicates FAULT or LOCKOUT.System fuse removed or blown. Safety will not shut down a system if the UNIT switch is OFF (which electrically removes the 115 V AC to all systems); only used to indicate a situation where a single system is missing the 115 V AC.Affected system faults and shuts down immediately when the 115 V AC supply is lost. Will not cause a lockout; the system fault resets when power is returned.117
EDUCTOR CLOG FAULTSenses a loss of oil return to the compressor — the eductor clog detection safety monitors the temperature of the line between the eductor and the suction line.Eductor line temperature greater than the saturated suction temperature plus 5.5°C (10°F): the clog timer (set at 600 seconds at start) is decremented one second for each second above the threshold and, if the temperature remains above the threshold for 600 seconds, counts to "0". Timer resets to 600 seconds whenever the eductor line temperature is below the threshold, preventing nuisance faults.System shuts down and locks out. Whenever this fault occurs, the eductor filter should be changed.117

Real time error numbers for BAS, SC-EQ or E-Link communications card

Code / displayMeaningCauseActionPage
0ALL OK108
1DATUM TYPE OK TEST FAILED108
2ENGLISH TEXT TOO LONG108
3FLOATING POINT EXCEPTION108
4GET PACKET FAILED108
5GET TYPE FAILED108
6INVALID UNIT CONVERSION108
7INVALID HARDWARE SELECTION108
8REAL TIME FAULT108
9SPANISH TEXT TOO LONG108
10THREAD EXITED108
11THREAD FAILED108
12THREAD STALLED108
13IO BOARD RESET108
14RTC/BRAM INVALID108
15BACNET SETUP FAILED108

Flash card update error

Code / displayMeaningCauseActionPage
0Okay110
10Flash card not found.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110
11SOFTWARE.ELF file not foundNever reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110
14SOFTWARE.ELF file larger than expected.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110
15RAM to IPU Flash transfer of DATABASE.ELF failed.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110
16RAM to IPU Flash transfer of SOFTWARE.ELF failed.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110
17Could not allocate sufficient memory to read or write file.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110
99Internal software error.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.110

Troubleshooting guide

Code / displayMeaningCauseActionPage
NO DISPLAY ON CONTROL PANEL UNIT WILL NOT RUN.Supply to the Panel is missing.
High Voltage to the Chiller is missing.
Line Fuse is blown.
Chiller Control Board is defective.
Display Board defective.
Check 1FU, 2FU, 4FU, 5FU 17FU, or 19FU.
Check 2T or 10T Transformer.
Check Fuses.
Replace Chiller Control Board.
Replace Display Board.
170
LINE FUSE BLOWS.SCR Diode Module is defective.
IBGT Module is defective.
VSD Logic Board is defective.
SCR Trigger Board is defective.
Check SCR/Diode Module.
Check IBGT Module.
Replace VSD Logic Board.
Replace SCR Trigger Board.
170
CHILLER FAULT: LOW AMBIENT TEMPERATUREAmbient temperature is lower than the programmed operating limit.
Ambient Sensor is defective.
Check the programmed cutout and determine if it is programmed correctly.
Check the panel against the thermometer reading of ambient temperature.
170
CHILLER FAULT: HIGH AMBIENT TEMPERATUREAmbient Temperature is above the maximum operating limit.
Ambient Sensor is defective.
Check outside air temperature.
Check the Panel Display against Thermometer reading of Ambient Temperature at the sensor.
170
CHILLER FAULT: LOW LEAVING CHILLED LIQUIDLeaving chilled liquid temperature drops faster than the unit can unload.
Water loop is too small.
Flow is below minimum for chiller.
Chilled Water Sensor is defective.
Check for restricted flow.
Check for rapid flow changes.
Check Sensor against Temp. Gauge in water line.
Check Sensor for intermittent operation.
Check Wiring for shorts or opens.
170
SYSTEM FAULT: CONTROL VOLTAGESystem Fuse is blown.Check respective system Fuse 20FU or 21FU.
NOTE: Always remove power to the chiller and ensure the DC Bus voltage has bled off.
170
SYSTEM FAULT: HIGH DISCHARGE PRESSURECoils dirty.
Coils are damaged.
Fans NOT operating.
System is overcharged.
Check and clean coils.
Comb out fins.
Check fan fuses.
Check fan rotation.
Check fan motor/blade.
Remove charge and check subcooling.
171
SYSTEM FAULT: HIGH DISCHARGE TEMPERATUREDischarge Temperature Sensor is defective.
Condenser Fans NOT operating or are running backwards.
Coils dirty.
High Superheat.
Check Sensor.
Check Fans.
Check and clean Coils.
Measure Superheat with gauges and thermocouple. Determine cause.
171
SYSTEM FAULT: HIGH MOTOR TEMPERATUREHigh Motor temperature input from one of the sensors.
Refrigerant charge low.
Excess charge in system, High discharge pressure.
High Superheat.
Motor Sensor reading incorrectly.
Economizer Solenoid energized at low speeds.
Check subcooling.
Check subcooling.
Drain/Feed Valves NOT controlling. Isolate cause.
Program panel to ignore a single sensor.
Valve is leaking through.
171
SYSTEM FAULT: LOW SUCTION PRESSURELow charge.
Transducer reads incorrectly.
Suction Temp. Sensor reads incorrectly.
Low flow.
Condenser Drain (Flash Tank Feed) Valve NOT operating.
Condenser or Drain (Flash Tank Feed) Valve defective.
Check subcooling.
Check transducer against a gauge.
Check sensor against a thermocouple.
Check flow.
Check Feed and Drain Valve operation.
Check superheat.
Check Feed and Drain Valve operation.
Check superheat.
171
VSD FAULT: HIGH BASEPLATE TEMPERATURECoolant level low.
Glycol Pump is defective.
VSD Board is defective
IBGT Module is defective.
Add coolant.
Replace Glycol Pump.
Replace VSD Logic Board.
Check defective IGBT Module.
172
VSD FAULT: LOW DC BUS VOLTAGESCR / Diode Module is defective.
SCR Trigger Board is defective.
Check SCR / Diode Module.
Check SCR Trigger Board.
NOTE: Always remove power to the chiller and ensure the DC Bus voltage has bled off.
172

From Model YVAA Style B Air-Cooled Screw Liquid Chillers with Variable Speed Drive Frame Sizes 016 to 026 201.47-ICOM1.EN.CE

Original: docs.johnsoncontrols.com

Safety update error messages

Code / displayMeaningCauseActionPage
MORE THAN ONE FILE FOUND
PRESS THE ENTER KEY TO CONTINUE  X
Software update aborted; panel waits for operator acknowledgement.More than one *.bin file found on the selected SD card or USB device.Press the ENTER key to return to the previous screen (software download).190
FILE NOT FOUND
PRESS THE ENTER KEY TO CONTINUE  X
Software update aborted; panel waits for operator acknowledgement.No *.bin file on the selected device.Press the ENTER key.190
FILE NOT ABLE TO BE LOADED
PRESS THE ENTER KEY TO CONTINUE  X
Software update aborted; panel waits for operator acknowledgement.The *.bin file is not able to be loaded to SPI flash, for example if the embedded checksum verification fails.Press the ENTER key.190
SELECTED DEVICE NOT FOUND
PRESS THE ENTER KEY TO CONTINUE  X
Software update aborted; panel waits for operator acknowledgement.User tried to update the software without inserting an SD or USB device.Press the ENTER key.190
FLASH ERROR XX
PRESS THE ENTER KEY TO CONTINUE  X
Other internal errors during the update; XX corresponds to the flash card update error codes of Table 24.Other internal errors.Press the ENTER key.190
10Flash card update error code: Flash card not found.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.189
11Flash card update error code: SOFTWARE.ELF file not found.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.189
14Flash card update error code: SOFTWARE.ELF file larger than expected.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.188
15Flash card update error code: RAM to IPU Flash transfer of DATABASE.BIN failed.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.188
16Flash card update error code: RAM to IPU Flash transfer of SOFTWARE.ELF failed.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.188
17Flash card update error code: Could not allocate sufficient memory to read or write file.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.188
99Flash card update error code: Internal software error.Never reset or power down the chiller until the update is finished. Interrupting the flash update procedure can corrupt the program file and render the control board inoperative.190

Unit warning

Code / displayMeaningCauseActionPage
UNIT WARNING:  !!  LOW BATTERY  !!
CHECK  SETPOINTS/PROGRAM/OPTIONS/TIME
RTC battery low detected at power-up. All programmed setpoints, program values, time, schedule, and history buffers are lost and reset to default values, which may not be the appropriate operating values. Unit is prevented from running. Warning displays indefinitely; warnings are not logged to the history buffer.RTC battery voltage low / bad battery, checked when powering up the micropanel.Replace the battery as soon as possible; the unit cannot run on the next power interruption until values are restored. After detecting a bad battery the unit is prevented from running until the MANUAL OVERRIDE key is pressed; anti-recycle timers are then set to the programmed default anti-recycle time so the operator has time to check setpoints, program values and other parameters.191
UNIT  WARNING:
INVALID NUMBER OF COMPRESSORS SELECTED
Warning displayed indefinitely; invalid number-of-compressors-selected configuration.Occurs after initializing the VSD if no number-of-compressors-select jumpers are installed, or if more than 1 jumper is installed.To clear the warning, turn off both the control panel and VSD control voltage and ensure the jumpers are correctly installed in the VSD wiring harness. Jumpers are factory installed in the wire harness plug and do not require changes.191
UNIT  WARNING:  INVALID  SERIAL  NUMBER
ENTER UNIT  SERIAL  NUMBER
May mean the chiller has lost important factory-programmed information; the serial number and other important data may need to be reprogrammed.Invalid / lost serial number data.Immediately contact Johnson Controls Product Technical Support. Enter the serial number using the service key (date and time must be set on the chiller before programming; factory-provided password required). This status message can be bypassed to view additional messages under the STATUS key by pressing the STATUS key repeatedly.191
UNIT  WARNING
QUARTERLY SERVICE REQUIRED – CONTACT JCI
Quarterly service reminder. Warnings are not logged in the history buffer.Days since the last service exceed 90 days.When quarterly service is complete, set the days to zero after clearing the warning.191
Unit  WARNING
YEARLY SERVICE REQUIRED – CONTACT JCI
Yearly service reminder. Warnings are not logged in the history buffer.Days since the last service exceed 365 days and the operating hours since the last service exceed 2,890 hours.When the yearly service is complete, set the days to zero after clearing the warning.192
UNIT  WARNING
3 YEAR SERVICE REQUIRED – CONTACT JCI
3 year service reminder. Warnings are not logged in the history buffer.Days since the last service exceed 1,095 days.When the 3 year service is complete, set the days to zero after clearing the warning.192
UNIT  WARNING
5 YEAR SERVICE REQUIRED – CONTACT JCI
5 year service reminder. Warnings are not logged in the history buffer.Days since the last service exceed 1,825 days.When the 5 year service is complete, set the days to zero after clearing the warning.192

Unit safeties

Code / displayMeaningCauseActionPage
UNIT YYYYYYYY
HIGH AMBIENT TEMP
Ambient temperature above allowable range; chiller shuts down with a controlled ramped shutdown. Fault message present only while the ambient temperature is causing the fault condition.Ambient temperature rises above 55°C.Auto-reset: restart occurs automatically, if demand allows, when temperature falls 1.1°C below the cutout of 53.9°C. Cannot cause a lockout. Unit is inhibited from starting any time the temperature is above 53.9°C.192
UNIT YYYYYYYY
LOW AMBIENT TEMP
Ambient temperature below the programmable Low Ambient Temp Cutout; chiller shuts down with a controlled ramped shutdown. Fault message present only while the ambient temperature is causing the fault condition.Ambient temperature falls below the programmable Low Ambient Temp Cutout. Fault only occurs if the Low Ambient Cutout is ENABLED under the OPTIONS key.Auto-reset: restart can occur, if demand allows, when temperature rises 1.1°C above the cutout. Cannot cause a lockout. Unit is inhibited from starting any time the temperature is below the cutout plus 1.1°C.192
UNIT  YYYYYYYY
LOW  LEAVING  CHILLED  LIQUID  TEMP
Leaving chilled liquid temperature below the programmable cutout; helps protect the chiller from an evaporator freeze-up; chiller faults and shuts down with a controlled ramped shutdown.Leaving chilled liquid temperature (water or brine) drops below the programmable cutout point — situation could occur under low flow conditions or if the Micro Panel setpoint values are improperly programmed.Auto-reset: restart can occur, if demand allows, when chilled liquid temperature rises 2.2°C above the cutout. Cannot cause a lockout. Unit is inhibited from starting any time the chilled liquid temperature is below the cutout plus 2.2°C.193
UNIT  YYYYYYYY
VSD  COMMUNICATIONS  FAILURE
Prevents the unit from trying to run if the Chiller Control Board never initializes communications with the VSD Logic Board; shuts down all compressors with a controlled ramped shutdown if communications are lost while operating.On power-up, no reply from the VSD Logic Board within 8 s; or during normal operation, no valid response to messages for 8 s.Unit is inhibited from starting until communications is established. Auto-reset: fault automatically resets when the Chiller Control Board receives a valid response from the VSD for a data request. VSD-related unit fault: if any 3 VSD unit faults occur within 90 min the unit locks out on the last fault; a VSD lockout requires a manual reset — both system switches must be cycled OFF and ON.193

System safeties, faults

Code / displayMeaningCauseActionPage
SYS X YYYYYYYY HIGH DISCHARGE PRESSUREHigh Discharge Pressure Cutout (software fault); system faults and shuts down with a controlled ramped shutdown.Discharge pressure rises above the programmed discharge pressure cutout for 0.5 seconds.System allowed to restart when discharge pressure falls below the programmed cutout − 2.07 bar; inhibited from starting above cutout − 2.07 bar. Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.194
SYS X YYYYYYYY HPCO FAULTMechanical high pressure cutout (hardware) protecting the system from dangerously high discharge pressure; system faults and shuts down immediately.Mechanical HPCO contacts open (opens at 23.2 barg ± 0.55 barg; closes at 17.4 barg ± 0.69 barg). Wired in series with the VSD Run Signal; only checked when the system is running. Fault occurs immediately, does not wait 3 s.Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.194
SYS X YYYYYYYY LOW SUCTION PRESSUREProgrammable Low Suction Pressure Cutout; protects the chiller from an evaporator freeze-up if the system attempts to run with a low refrigerant charge.Suction pressure falls below the ramped Suction Pressure Cutout during the startup ramp, or below the programmed Suction Pressure Cutout after the ramp. Cutout is ignored at system start for the programmable Suction Pressure Startup Bypass Time, then linearly ramped from 10% to 100% of the programmed Suction Pressure Cutout.Causes a lockout on the 3rd fault in 90 min — cycle the respective system switch OFF and ON to clear.194
SYS X YYYYYYYY LOW SUCT PRES SMART FREEZESmart freeze safety fault.Suction Pressure below the Suction Pressure Override Threshold longer than the programmable Smart Freeze Timer. Override Threshold = Suction Pressure Cutout + 11.72 kPa (R-134a), + 12.41 kPa (R-513A), + 8.96 kPa (R-1234ze).Safety released when Suction Pressure ≥ Suction Pressure Override Threshold. Causes a lockout on the 3rd fault in 90 min — cycle the respective system switch OFF and ON to clear.194
SYS X YYYYYYYY LOW MOTOR CURRENTMotor Current Cutout; shuts the system down with a controlled ramped shutdown.Microprocessor detects absence of motor current (less than 10% FLA), usually indicating that a compressor is not running. Safety ignored for the first 10 s of operation.Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.195
SYS X YYYYYYYY HIGH DIFF OIL PRESSUREHigh Differential Oil Pressure Cutout; protects the compressor from low oil flow and insufficient lubrication; shuts down with a controlled ramped shutdown.Discharge-to-Oil differential pressure rises above the cutout of 4.48 barg (measures the pressure drop across the oil filter — possibly a dirty oil filter). Safety ignored for the first 90 s of run time.Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.195
SYS X YYYYYYYY LOW DIFF OIL PRESSURELow Differential Oil Pressure Cutout; protects the compressor from low oil flow and insufficient lubrication; ensures the compressor is pumping sufficiently to push oil through the oil cooling circuit and internal lubrication system; shuts down with a controlled ramped shutdown.Differential between oil and suction pressure falls below the cutout. Ignored for the first 60 s of run time; then linearly ramped from 0 barg to 2.09 barg in 5–10 min based on ambient temperature (>10°C: 5 min; >7.2°C: 6 min; >4.4°C: 7 min; >1.6°C: 8 min; >1.1°C: 9 min; ≤1.1°C: 10 min). A 30 s safety bypass below 50 Hz is employed during rampdown.Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.195
SYS X YYYYYYYY HIGH DISCHARGE TEMPHigh Discharge Temperature Cutout; protects the motor and compressor from overheating; shuts down with a controlled ramped shutdown.Discharge Temperature rises above 121°C.System also inhibited from starting if the discharge temperature is above 93°C. Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.195
SYS X YYYYYYYYYY
LOW ECONOMIZER SUPERHEAT
Protects against excessive liquid refrigerant carryover from the economizer (possible EEV, sensor or other problems) and protects the system compressor from liquid refrigerant flood back from the economizer feed line if the economizer valve fails to close.Superheat falls below 2.8°C for 5 min under either condition. Safety ignored for the first 10 min of operation if the system economizer feed valve is closed at 0%, and for 5 min of operation if the economizer feed valve is open greater than 0%.Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.198
SYS X YYYYYYYY SENSOR FAILURE:
ZZZZZZZZZZZZ
Sensor Failure Cutout; prevents the system from running when a critical sensor, transducer, level sensor, or motor winding temperature sensor is not functioning properly and reading out of range. Checked at startup (prevents running) and faults/shuts down a system during operation if a safety threshold is exceeded or a sensor reads out of range high or low.Failed sensor indicated by ZZZZZZZZZZZZ: SUCT PRESS, OIL PRESS, DSCH PRESS, ECONOMIZER PRESS, or MOTOR TEMP X. Start inhibit thresholds: suction, oil and discharge transducers 0.3–4.7 VDC; motor temperature sensor 0–116°C.A specific motor temperature sensor can be ignored using the unit setup mode if it fails; report any failure to Johnson Controls service for investigation. Auto-reset after the 120 s anti-recycle timer; LOCKOUT after 3 faults — cycle the respective system switch OFF and ON to clear.197
SYS X YYYYYYYY HIGH MOTOR TEMPHigh Motor Temperature Cutout; prevents a compressor from running when its motor temperature is too high; system faults and shuts down.Any compressor motor temperature sensor rises above 121°C.System inhibited from starting if its motor temperature sensors indicate temperatures above 116°C. A sensor being ignored under the Unit Set-up Mode is not used when evaluating motor temperature. Auto-reset after the 120 s anti-recycle timer; locks out on the 3rd fault within 90 min — cycle the respective system switch OFF and ON to clear.197
SYS X YYYYYYYY CONTROL VOLTAGESystem Control Voltage Cutout; alerts the operator that the 115 V AC control voltage to one of the systems is missing; affected system faults and shuts down immediately when the 115 V AC supply is lost.115 V AC supply lost to a single system — may be due to a system fuse that has been removed or is blown. Does not shut down a system if the UNIT switch is OFF (which electrically removes 115 V AC to all systems).Will not cause a lockout; the system fault resets when power is returned.198
Eductor clog faultSafety sensing a loss of oil return to the compressor by monitoring the temperature of the line between the eductor and the suction line. No display message is documented for this safety.Eductor line temperature is not less than the saturated suction temperature plus 5.5°C. Control looks at the eductor line temperature once a second; at start a clog timer is set at 600 s and is reset to 600 s each time the temperature is below the threshold. Eductor differential and eductor safety time are programmable under the PROGRAM key.198
SYS X YYYYYYYYYY
ISO VALVE FAILED TO CLOSE
Isolation valve open warning; message displayed and fault code communicated. Shall not prevent the system from starting.System isolation valve digital input J5-1 or J5-2 indicates the isolation valve did not close within 60 s of the evaporator heater outputs being turned on.Warning clears when the unit begins precharge or the condition clears.198
SYS X YYYYYYYYYY
ISO VALVE FAILED TO OPEN
Isolation valve closed fault; system fault before compressor start.Before starting the compressor, after the VSD has completely precharged, the system isolation valve digital input J5-1 or J5-2 indicates the system isolation valve did not open.Causes a lockout on the first fault — manual reset required (cycle the respective system switch OFF and ON).198
SYS X YYYYYYYYYY
HIGH DSCH PRESSURE RATE
High Discharge Pressure Rate Cutout; immediate fault with no 3 s delay.When enabled, during system run the discharge pressure of each running system is monitored once per second; system shuts down when its discharge pressure rate of change exceeds the programmed Discharge Pressure Rate Threshold (Unit Setup Mode).Locks out on the first fault — manual reset required (cycle the respective system switch OFF and ON).198
SYS X WARNING
CONDENSER FAN VSD FAULT
System Condenser Fan VSD Fault Warning; auto reset warning monitoring the status of the fault input.Fault input is low.Auto reset — resets when the input is high.198
SYS X WARNING
REPLACE OIL FILTER
System Replace Oil Filter Warning; manual reset warning monitoring the status of the oil filter maintenance cycle. Can be enabled/disabled under Unit Setup Mode.Differential Oil to Discharge Pressure is greater than 3.447 bar.Manual reset warning.198

General status messages

Code / displayMeaningCauseActionPage
UNIT  STATUS
FLOW  SWITCH  SHUTDOWN
Flow switch is not allowing the chiller to run. Loss-of-flow protection against evaporator freeze-up; the manual lists flow switch operation among the unit auto-reset safeties.Flow switch open (no chilled liquid flow). There is a 1 s delay on this safety to ensure the flow switch did not momentarily open.Auto-reset: unit can run once the flow switch closes (chilled liquid flow re-established).200
UNIT  STATUS
VSD  COOLING  SHUTDOWN
Chiller is shut down while all condenser fans, the VSD glycol pump, and the VSD fan run to bring the internal VSD ambient temperature down to an acceptable level before allowing the chiller to start.Internal VSD ambient temperature above the acceptable level.Chiller is allowed to start once the internal VSD ambient temperature is brought down to an acceptable level.200

Troubleshooting guide

Code / displayMeaningCauseActionPage
No display on control panel unit will not runControl panel dead; unit will not run.Supply to the panel is missing; line fuse is blown; chiller control board is defective; display board defective.Verify that power is being applied to the unit from the customer supply; check 1FU, 2FU, 4FU, 5FU, 17FU, or 19FU; check 2T or 10T transformer; check fuses; replace chiller control board; replace display board.260
Line fuse blowsLine fuse repeatedly blowing.SCR diode module is defective; IBGT module is defective; VSD logic board is defective; SCR trigger board is defective.Check SCR/Diode module; check IBGT module; replace VSD logic board; replace SCR trigger board. Always remove power to the chiller and ensure the DC Bus voltage has bled off.260
Chiller fault: Low ambient temperatureChiller shutdown on low ambient temperature.Ambient temperature is lower than the programmed operating limit; ambient sensor is defective.Check the programmed cutout and determine if it is programmed correctly; check the panel against the thermometer reading of ambient temperature.260
Chiller fault: High ambient temperatureChiller shutdown on high ambient temperature.Ambient temperature is above the maximum operating limit; ambient sensor is defective.Check outside air temperature; check the panel display against thermometer reading of ambient temperature at the sensor.260
Chiller fault: Low leaving chilled liquidChiller shutdown on low leaving chilled liquid temperature.Leaving chilled liquid temperature drops faster than the unit can unload (restricted flow; rapid flow changes; water loop too small; flow below minimum for chiller); chilled water sensor is defective.Check for restricted flow; check for rapid flow changes; check water loop size; check flow against chiller minimum; check sensor against temp. gauge in water line; check sensor for intermittent operation; check wiring for shorts or opens.260
System fault: Control voltage115 V AC control voltage missing to a system.System fuse is blown.Check respective system fuse 20FU or 21FU. Always remove power to the chiller and ensure the DC Bus voltage has bled off.260
System fault: high discharge pressureSystem shutdown on high discharge pressure.Coils dirty; coils are damaged; fans not operating; system is overcharged.Check and clean coils; comb out fins; check fan fuses, fan rotation, fan motor/blade; remove charge and check subcooling.261
System fault: high discharge temperatureSystem shutdown on high discharge temperature.Discharge Temperature Sensor is defective; condenser fans not operating or are running backwards; coils dirty; high superheat.Check sensor; check fans; check and clean coils; measure superheat with gauges and thermocouple and determine cause.261
System fault: high motor temperatureSystem shutdown on high motor temperature.High motor temperature input from one of the sensors: refrigerant charge low; excess charge in system with high discharge pressure; high superheat (drain or feed valves not controlling); motor sensor reading incorrectly; economizer solenoid energized at low speeds with valve leaking through.Check subcooling (charge low); check subcooling (excess charge); isolate cause (high superheat); program panel to ignore a single sensor; check economizer solenoid/valve leakage.261
System fault: low suction pressureSystem shutdown on low suction pressure.Low charge; transducer reads incorrectly; suction temp. sensor reads incorrectly; low flow; condenser drain valve not operating; condenser or drain valve defective.Check subcooling; check transducer against a gauge; check sensor against a thermocouple; check flow; check drain valve operation and check superheat.261
System fault: low economizer superheatSystem shutdown on low economizer superheat.Economizer line temperature sensor is defective; economizer transducer is defective; economizer feed valve malfunction; economizer line solenoid purge valve malfunction.Check temperature sensor; check transducer against a gauge; check economizer feed valve operation; check economizer line solenoid purge valve operation.261
VSD fault: High baseplate temperatureVSD shutdown on high baseplate temperature.Coolant level low; glycol pump is defective; VSD board is defective; IBGT module is defective; VSD cooling coil not clean.Add coolant; replace glycol pump; replace VSD logic board; check defective IGBT module; clean VSD cooling coil. Always remove power to the chiller and ensure the DC Bus voltage has bled off.262
VSD fault: Low DC Bus voltageVSD shutdown on low DC Bus voltage.SCR/Diode module is defective; SCR trigger board is defective.Check SCR/diode module; check SCR trigger board. Always remove power to the chiller and ensure the DC Bus voltage has bled off.262

From YVAA Style A with VSD, Frame size 015-027 2-Compressor 60 Hz (150-350 tons), Frame size 054-098, 2-Compressor 50 Hz (525-950 KW) R-134a or R-513A 201.28-NM1.1

Original: docs.johnsoncontrols.com

Unit warning

Code / displayMeaningCauseActionPage
UNIT WARNING: !! LOW BATTERY !!
CHECK SETPOINTS/PROGRAM/OPTIONS/TIME
Low Real Time Clock (RTC) battery voltage detected at micropanel power-up.On micropanel power-up the RTC battery is checked to see if it is still operational; if the battery voltage is determined to be low, this warning message is displayed indefinitely.All programmed setpoints, program values, time, schedule, and history buffers have been lost and are reset to their default values, which may not be the correct operating values. After a bad battery is detected, the unit is prevented from running until the manual override key is pressed; after pressing the manual override key, the anti-recycle timers are set to the programmed default anti-recycle time to allow the operator sufficient time to check setpoints, program values, and other relevant values. Replace the battery as soon as possible — the programmed values will all be lost and the unit will be prevented from running on the next power interruption.139
UNIT WARNING:
INVALID NUMBER OF COMPRESSORS SELECTED
Invalid Number of Compressors Select jumper configuration.Occurs after the VSD has been initialized, if no jumpers are installed or if more than 1 jumper is installed.To clear this warning, both the control panel and VSD control voltage must be turned OFF and the jumpers properly installed in the VSD wiring harness.139
UNIT WARNING: INVALID SERIAL NUMBER
ENTER UNIT SERIAL NUMBER
Chiller serial number invalid or lost.The appearance of this message may mean the chiller has lost important factory programmed information.Immediately contact Johnson Controls Product Technical Support. The serial number can be entered using the SERVICE key. This status message can be bypassed to view additional messages under the STATUS key by pressing the STATUS key repeatedly to scroll through as many as three STATUS messages that could possibly be displayed at any time.139

Unit safeties

Code / displayMeaningCauseActionPage
UNIT YYYYYYYY
HIGH AMBIENT TEMP
Ambient air temperature above the maximum allowable value.Ambient temperature rises above 55°C (131°F).Chiller shuts down with a controlled ramped shutdown. Restart will automatically occur, if demand allows, when temperature falls 1.1°C (2°F) below the cutout (53.9°C [129°F]). This fault cannot cause a lockout. The fault display message is present only during the time when the ambient temperature is causing a fault condition. The unit is also inhibited from starting any time the temperature is above 53.9°C (129°F).140
UNIT YYYYYYYY
LOW AMBIENT TEMP
Ambient air temperature below the programmed cutout.Ambient temperature falls below the programmable Low Ambient Temp Cutout. This fault only occurs if the Low Ambient Cutout is ENABLED under the OPTIONS key.Chiller shuts down with a controlled ramped shutdown. Restart can occur, if demand allows, when temperature rises 1.1°C (2°F) above the cutout. This fault cannot cause a lockout. The fault display message is present only during the time when the ambient temperature is causing a fault condition. The unit is also inhibited from starting any time the temperature is below the cutout plus 1.1°C (2°F).140
UNIT YYYYYYYY
LOW LEAVING CHILLED LIQUID TEMP
Leaving chilled liquid temperature below the freeze-protection cutout.The leaving chilled liquid temperature (water or brine) drops below the programmable cutout point. Helps protect the chiller from an evaporator freeze-up; this situation could occur under low flow conditions or if the Micro Panel setpoint values are improperly programmed.Chiller faults and shuts down with a controlled ramped shutdown. Restart can occur, if demand allows, when chilled liquid temperature rises 2.2°C (4°F) above the cutout. This fault cannot cause a lockout. The unit is inhibited from starting any time the chilled liquid temperature is below the cutout plus 2.2°C (4°F).140
UNIT YYYYYYYY
VSD COMMUNICATIONS FAILURE
Loss of communications between the Chiller Control Board and the VSD Logic Board.On power-up, the Chiller Control Board fails to initialize communications with the VSD Logic Board (no reply from the VSD Logic Board within 8 seconds), or during normal operation the Chiller Control Board receives no valid response to messages for 8 seconds.Prevents the unit from trying to run; while operating, the unit shuts down all compressors with a controlled ramped shutdown. The Chiller Control Board continues to send messages to the VSD while faulted. The unit is inhibited from starting until communications is established. The fault automatically resets when the Chiller Control Board receives a valid response from the VSD for a data request.140

System safeties, faults

Code / displayMeaningCauseActionPage
SYS X YYYYYYYY HIGH DISCHARGE PRESSURESoftware high discharge pressure cutout.Discharge pressure rises above 22.4 barg (325 psig) for 0.5 seconds.System faults and shuts down with a controlled ramped shutdown. The system is allowed to restart when the discharge pressure falls to 20.3 barg (295 psig). The system is also inhibited from starting if the pressure is above 20.3 barg (295 psig). YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (does not restart until the operator clears the fault using the keypad).141
SYS X YYYYYYYY HPCO FAULTMechanical (hardware) high pressure cutout trip.The mechanical high pressure cutout contacts open, protecting the system from dangerously high discharge pressure. The cutout opens at 23.2 barg ± 0.55 barg (337 psig ± 8 psig) and closes at 17.4 barg ± 0.69 barg (252 psig ± 10 psig). The HPCO is wired in series with the VSD Run Signal and is only checked by the Chiller Control Board when the system is running. The fault occurs immediately and does not wait 3 seconds.System faults and shuts down immediately. YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).141
SYS X YYYYYYYY LOW SUCTION PRESSURESuction pressure below the programmable cutout.If the system attempts to run with a low refrigerant charge, the programmable LOW SUCTION PRESSURE CUTOUT protects the chiller from an evaporator freeze-up. The cutout is ignored at the system start to allow the initial programmable SUCTION PRESSURE STARTUP BYPASS TIME; immediately after the bypass time expires, the cutout is linearly ramped from 10% to 100% of the programmed Suction Pressure Cutout.The system shuts down if at any time during the ramp the suction pressure falls below the ramped Suction Pressure Cutout, or if at any time after the ramp the suction pressure falls below the programmable Suction Pressure Cutout. This causes a lockout on the 3rd fault in 90 minutes.142
SYS X YYYYYYYY LOW SUCT PRES SMART FREEZESuction pressure held below the override threshold longer than permitted (R-134a and R-513A refrigeration systems).Set when the Suction Pressure is lower than the programmable Suction Pressure Override Threshold (Suction Pressure Cutout in psig + 1.7 psig) for longer than the programmable Smart Freeze Timer. The safety fault is released when the Suction Pressure >= Suction Pressure Override Threshold.This fault causes a lockout on the 3rd fault in 90 minutes.142
SYS X YYYYYYYY LOW MOTOR CURRENTAbsence of motor current detected.The microprocessor detects the absence of motor current (less than 10% FLA), usually indicating that a compressor is not running. This safety is ignored for the first 10 seconds of operation.Shuts the system down with a controlled ramped shutdown. YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).142
SYS X YYYYYYYY HIGH DIFF OIL PRESSUREExcessive discharge-to-oil differential pressure (pressure drop across the oil filter).The Discharge to Oil Differential Pressure rises above the cutout of 4.48 barg (65 psid). Protects the compressor from low oil flow and insufficient lubrication, possibly from a dirty oil filter. This safety is ignored for the first 90 seconds of run time.System faults and shuts down with a controlled ramped shutdown. YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).142
SYS X YYYYYYYY LOW DIFF OIL PRESSUREOil-to-suction differential pressure below the cutout (protection against low oil flow and insufficient lubrication).The differential between oil and suction pressure falls below the cutout. The safety ensures the compressor is pumping sufficiently to push oil through the oil cooling circuit and the internal compressor lubrication system. The safety is ignored for the first 60 seconds of run time; after that the cutout is linearly ramped from 0 barg to 2.09 barg (0 psid to 30 psid) in 5 to 10 minutes based on ambient temperature (see Table 17). A 30 second safety bypass below 50 Hz is employed during rampdown (needed when another compressor is being brought on and the running compressor is ramped down to 5 Hz).System faults and shuts down with a controlled ramped shutdown. YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).143
SYS X YYYYYYYY HIGH DISCHARGE TEMPDischarge temperature above the cutout (motor and compressor overheat protection).Discharge Temperature rises above 121°C (250°F).System faults and shuts down with a controlled ramped shutdown. The system is also inhibited from starting if the discharge temperature is above 93°C (200°F). YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).143
Low discharge superheat cutout faultProtection against liquid floodback through the economizer line due to a high flashtank level, and against excessive oil in circulation due to excess oil charge in the system.Discharge superheat falls below 2.8°C (5.0°F) for 5 minutes. The safety is ignored for the first 10 minutes of operation if the system economizer feed valve is closed (0%), and for 5 minutes of operation if the economizer feed valve is open greater than 0%. Excessive oil in circulation brings back liquid refrigerant entrained in the oil; the liquid drops out once it enters the compressor.System shuts down. YYYYYYYY = FAULT (system restarts when the 120 second anti-recycle timer times out) or LOCKOUT (will not restart until the operator clears the fault using the keypad).143
SYS X YYYYYYYY SENSOR FAILURE:
ZZZZZZZZZZZZ
A critical sensor is failed or reading out of range. ZZZZZZZZZZZZ indicates the failed sensor: SUCT PRESS, OIL PRESS, DSCH PRESS, or MOTOR TEMP X * (* a specific motor temperature sensor can be ignored under the Unit Setup Mode).A critical sensor (transducer, level sensor, or motor winding temp sensor) is not functioning properly and reading out of range. The safety is checked at startup and will also fault and shut down a system while in operation if a safety threshold is exceeded or a sensor reads out of range (high or low). Start inhibit sensor thresholds (Table 20): Suction Transducer 0.3–4.7 VDC; Oil Transducer 0.3–4.7 VDC; Discharge Transducer 0.3–4.7 VDC; Motor Temp. Sensor 0°C (0°F) to 116°C (240°F).At startup, prevents the system from running if one of the sensors has failed. During operation, the system faults and shuts down. YYYYYYYY = FAULT (system restarts when the fault clears) or LOCKOUT after 3 faults (will not restart until the operator clears the fault using the keypad).145
SYS X YYYYYYYY HIGH MOTOR TEMPCompressor motor temperature too high.Any compressor motor temperature sensor rises above 121°C (250°F). The system is inhibited from starting if its motor temperature sensors indicate temperatures above 116°C (240°F). If any single temperature sensor is being ignored under the Unit Set-up Mode, that sensor is not utilized when evaluating motor temperature.System faults and shuts down. YYYYYYYY = FAULT (system restarts when the fault clears) or LOCKOUT (will not restart until the operator clears the fault using the keypad).145
SYS X YYYYYYYY CONTROL VOLTAGE115 V AC control voltage missing from one system.The 115 V AC Control voltage to one of the systems is missing; this could be due to a system fuse that has been removed or is blown. The affected system faults and shuts down immediately when the 115 V AC supply is lost. The safety will not shut down a system if the UNIT switch is OFF (which electrically removes the 115 V AC to all systems); it is only used to indicate a situation where a single system is missing the 115 V AC.This safety will not cause a lockout; the system fault resets when power is returned.145
EDUCTOR CLOG FAULTLoss of oil return to the compressor through the eductor.The safety monitors the temperature of the line between the eductor and the suction line once a second. At start, a clog timer is set at 600 seconds; the timer resets to 600 seconds whenever the eductor line temperature is less than the saturated suction temperature plus 5.5°C (10°F). If the eductor line temperature is greater than the saturated suction temperature plus 5.5°C (10°F) for 600 seconds, the clog timer counts to 0.The system shuts down and locks out. Whenever this fault occurs, the eductor filter should be changed.146

General status messages

Code / displayMeaningCauseActionPage
UNIT STATUS
FLOW SWITCH SHUTDOWN
Chilled liquid flow switch open — flow switch is not allowing the chiller to run.The flow switch is not allowing the chiller to run. There is a 1 second delay on this safety to ensure the flow switch did not momentarily open.Chiller is kept shut down while the flow switch is open.148
UNIT STATUS
VSD COOLING SHUTDOWN
Chiller shut down while the VSD internal ambient temperature is brought down to an acceptable level.The chiller is shutdown, but running all the condenser fans, VSD glycol pump, and VSD fan in an effort to bring the internal VSD ambient temperature down to an acceptable level before allowing the chiller to start.Chiller remains shut down (with condenser fans, VSD glycol pump and VSD fan running) until the internal VSD ambient temperature is at an acceptable level, before the chiller is allowed to start.148

Flash card update error

Code / displayMeaningCauseActionPage
0Okay130
10Flash card not found.130
11SOFTWARE.ELF file not found130
14SOFTWARE.ELF file larger than expected.130
15RAM to IPU Flash transfer of DATABASE.ELF failed.130
16RAM to IPU Flash transfer of SOFTWARE.ELF failed.130
17Could not allocate sufficient memory to read or write file.130
99Internal software error.130

Software update errors

Code / displayMeaningCauseActionPage
MORE THAN ONE FILE FOUNDmore than on *.bin file on selected device132
FILE NOT FOUND*.bin file not on selected device132
FILE NOT ABLE TO BE LOADED*.bin file not able to be loaded to flash132
SELECTED DEVICE NOT FOUNDupdate attempted without SD or USB132

Flash errors

Code / displayMeaningCauseActionPage
FILE_BUFFER_APP_HEADER_READError code 90132
CANNOT_CALCULATE_BUFFER_DATA_CRCError code 91132
BAD_FILE_BUFFER_DATA_CRCError code 92132
SFLASH_DEVICE_WRITEError code 93132
BAD_SFLASH_CRCError code 94132
APP_CODE_TOO_BIGError code 95132
SPI_FLASH_APP_NOT_PRESENTError code 96132
SPI_FLASH_READ_ERRORError code 97132
CANNOT_READ_DEVICE_CONFIGURATIONError code 98132

Troubleshooting guide

Code / displayMeaningCauseActionPage
No display on control panel unit will not run.Supply to the Panel is missing.
High Voltage to the Chiller is missing.
Line Fuse is blown.
Chiller Control Board is defective.
Display Board defective.
Check 1FU, 2FU, 4FU, 5FU 17FU, or 19FU.
Check 2T or 10T Transformer.
Check Fuses.
Replace Chiller Control Board.
Replace Display Board.
198
Line fuse blows.SCR Diode Module is defective.
IBGT Module is defective.
VSD Logic Board is defective.
SCR Trigger Board is defective.
Check SCR/Diode Module.
Check IBGT Module.
Replace VSD Logic Board.
Replace SCR Trigger Board.
198
Chiller fault: Low ambient temperatureAmbient temperature is lower than the programmed operating limit.
Ambient Sensor is defective.
Check the programmed cutout and determine if it is programmed correctly.
Check the panel against the thermometer reading of ambient temperature.
198
Chiller fault: High ambient temperatureAmbient Temperature is above the maximum operating limit.
Ambient Sensor is defective.
Check outside air temperature.
Check the Panel Display against Thermometer reading of Ambient Temperature at the sensor.
198
Chiller fault: Low leaving chilled liquidLeaving chilled liquid temperature drops faster than the unit can unload.
Water loop is too small.
Flow is below minimum for chiller.
Chilled Water Sensor is defective.
Check for restricted flow.
Check for rapid flow changes.
Check Sensor against Temp. Gauge in water line.
Check Sensor for intermittent operation.
Check Wiring for shorts or opens.
198
System fault: Control voltageSystem Fuse is blown.Check respective system Fuse 20FU or 21FU.198
System fault: High discharge pressureCoils dirty.
Coils are damaged.
Fans NOT operating.
System is overcharged.
Check and clean coils.
Comb out fins.
Check fan fuses.
Check fan rotation.
Check fan motor/blade.
Remove charge and check subcooling.
199
System fault: High discharge temperatureDischarge Temperature Sensor is defective.
Condenser Fans NOT operating or are running backwards.
Coils dirty.
High Superheat.
Check Sensor.
Check Fans.
Check and clean Coils.
Measure Superheat with gauges and thermocouple. Determine cause.
199
System fault: High motor temperatureHigh Motor temperature input from one of the sensors.
Refrigerant charge low.
Excess charge in system, High discharge pressure.
High Superheat.
Motor Sensor reading incorrectly.
Economizer Solenoid energized at low speeds.
Check subcooling.
Check subcooling.
Drain/Feed Valves NOT controlling. Isolate cause.
Program panel to ignore a single sensor.
Valve is leaking through.
199
System fault: Low suction pressureLow charge.
Transducer reads incorrectly.
Suction Temp. Sensor reads incorrectly.
Low flow.
Condenser Drain (Flash Tank Feed) Valve NOT operating.
Condenser or Drain (Flash Tank Feed) Valve defective.
Check subcooling.
Check transducer against a gauge.
Check sensor against a thermocouple.
Check flow.
Check Feed and Drain Valve operation. Check superheat.
Check Feed and Drain Valve operation. Check superheat.
199
System fault: Discharge pressure limitingDischarge Transducer is defective.
Ambient Temp. very high.
Fans not operating.
Remote or local discharge pressure load limiting is programmed.
Check transducer against a gauge.
Normal operation.
Check fan operation.
Normal operation.
199
VSD fault: High baseplate temperatureCoolant level low.
Glycol pump is defective.
VSD Board is defective.
IBGT Module is defective.
Add coolant.
Replace Glycol Pump.
Replace VSD Logic Board.
Check defective IGBT Module.
200
VSD fault: Low DC Bus voltageSCR/Diode Module is defective.
SCR Trigger Board is defective.
Check SCR/Diode Module.
Check SCR Trigger Board.
200

From Improved clamped voltage design for digital suction pressure transducers SI0602

Original: docs.johnsoncontrols.com

Improved clamped voltage design for digital suction pressure transducers

Code / displayMeaningCauseActionPage
sensor failure fault Suction pressure transducer output voltage value below 0.3 V and above 4.7 V results in a sensor failure fault on the impacted system on the chiller, which inhibits the operation of that system. Observed on chillers in high ambient climate locations when the chiller was in standby mode; this prevented the system(s) from startup. The voltage output of the impacted suction pressure transducers (P/N: 025-29583-002, digital type, identified by the 2D matrix barcode stamped on the side of the transducer) was unregulated and could reach up to 4.9 V. These transducers were released to production in January 2021; transducers prior to this date are not impacted by this issue. Verify the manufacturing date for the digital pressure transducer (identified by 2D barcode) to determine if it has unclamped output voltage and needs to be replaced. The last 3 digits of the serial number depict the code for week and year of manufacturing. If the transducer was manufactured between January 2021 and week 10 of 2022 (date code: 102), replace the transducer with a new part — an improved version of the suction pressure transducer that clamps the maximum output voltage at 4.7 V, thereby preventing the sensor failure fault from occurring during these high ambient conditions. 1

From SOO Do's and Don'ts Workbook / Troubleshooting Guide SI0630

Original: docs.johnsoncontrols.com

Errors (IPU3 Software Update)

Code / displayMeaningCauseActionPage
MORE THAN ONE FILE FOUND
PRESS TO CONTINUE (x)
Error message displayed during IPU3 program update.More than one *.bin file is on the selected device.Displayed until the user presses the Enter key and returns to the software download display.5
FILE NOT FOUND
PRESS TO CONTINUE (x)
Error message displayed during IPU3 program update.No *.bin file is on the selected device.Displayed until the user presses the Enter key and returns to the software download display.5
FILE NOT ABLE TO BE LOADED
PRESS TO CONTINUE (x)
Error message displayed during IPU3 program update.The *.bin file cannot be loaded to SPI flash, for example if the embedded checksum verification fails.Displayed until the user presses the Enter key and returns to the software download display.5
SELECTED DEVICE NOT FOUND
PRESS TO CONTINUE (x)
Error message displayed during IPU3 program update.The software update was attempted without a SD or USB device inserted.Displayed until the user presses the Enter key and returns to the software download display.5
FLASH ERROR XX
PRESS TO CONTINUE (x)
Displayed if other internal errors occur during the software update. The Error Code displayed in the XX field is one of:
90 — FILE_BUFFER_APP_HEADER_READ
91 — CANNOT_CALCULATE_BUFFER_DATA_CRC
92 — BAD_FILE_BUFFER_DATA_CRC
93 — SFLASH_DEVICE_WRITE
94 — BAD_SFLASH_CRC
95 — APP_CODE_TOO_BIG
96 — SPI_FLASH_APP_NOT_PRESENT
97 — SPI_FLASH_READ_ERROR
98 — CANNOT_READ_DEVICE_CONFIGURATION
Other internal errors occurred during the software update.Displayed until the user presses the Enter key.5

Unit Faults

Code / displayMeaningCauseActionPage
1
Low Ambient Temperature
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
2
High Ambient Temperature
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
3
Low Chilled Liquid Temperature
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
4
VSD Initialization Failure
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
5
Low RTC Battery Voltage
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
6
Invalid Number of Compressors Selected
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
7
VSD Communications Failure
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
8
Pre-charge Low DC Bus Voltage
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
9
Pre-charge DC Bus Voltage Imbalance
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
10
High DC Bus Voltage
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
11
Low DC Bus Voltage
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
12
DC Bus Voltage Imbalance
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
13
High VSD Ambient Temperature
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
14
Single Phase Input
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
15
VSD Power Supply Fault
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
16
VSD Logic Board Fault
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
17
Motor Current Overload (Hardware)
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
18
CT Plug Fault
Unit fault — VSD sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared. If any 3 (or more) VSD-related unit faults occur within 90 minutes, the unit triggers a lockout on the last fault in the range. A lockout requires manual reset, done via the System Switches button on the keypad or HMI.16
19
High Harmonic Filter Temperature
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
20
Evap Anti-Freeze Pump Fault
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
21
SPARE
Unit fault — Panel source16
22
Replace RTC Battery
Unit fault — Panel sourceIf unit faults exceed a set threshold for 3 seconds, all running compressors are shut down. Unit faults are logged in the history buffer. Most unit faults are auto-reset; the unit can restart automatically after the fault condition is cleared.16
23
SPARE
Unit fault — source not listed16
24
SPARE
Unit fault — source not listed16
25
SPARE
Unit fault — source not listed16
26
SPARE
Unit fault — source not listed16

System Faults

Code / displayMeaningCauseActionPage
27
High Discharge Pressure (Software)
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.16
28
High Differential Oil Pressure
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.16
29
Low Differential Oil Pressure
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.16
30
Low Suction Pressure
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.16
31
High Discharge Temperature
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.16
32
SPARE
System fault — Panel source17
33
Eductor Clog Fault
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
34
Sensor Failure
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
35
Low Motor Current
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
36
High Motor Temperature
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
37
Pre-charge Low DC Bus Voltage
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
38
Pre-charge DC Bus Voltage Imbalance
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
39
High DC Bus Voltage
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
40
Low DC Bus Voltage
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
41
DC Bus Voltage Imbalance
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
42
High Motor Current
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
43
Motor Current Overload (Software)
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
44
IGBT Gate Driver Fault
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
45
High Baseplate Temperature
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
46
Single Phase Input
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
47
VSD Run Signal Fault
System fault — VSD sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
48
High Discharge Press (Hardware – HPCO)
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
49
Spare
System fault — Panel source17
50
Control Voltage Fault
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
51
Low Discharge Superheat
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
52
Low Suction Pressure Smart Freeze
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
53
Isolation Valve Failed to Close Warning
System fault — Panel source17
54
Isolation Valve Failed to Open Fault
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
55
High Discharge Pressure Rate
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
56
Condenser Fan VSD Warning
System fault — Panel source17
57
Low Economizer Superheat
System fault — Panel sourceIf a system fault threshold is exceeded for 3 seconds, only the affected system is shut down (not the whole unit/all systems). System faults are auto-reset; the system restarts automatically after the fault condition clears. If 3 faults on the same system occur within 90 minutes, that system is locked out after the third fault. Lockout requires manual reset: the operator must cycle the system switch off then on to clear the lockout.17
58
SPARE
System fault — source not listed17
59
SPARE
System fault — source not listed17
60
SPARE
System fault — source not listed17
61
SPARE
System fault — source not listed17
62
SPARE
System fault — source not listed17

From YVAA Only Planned Maintenance Warnings Software Version V18 SI0476

Original: docs.johnsoncontrols.com

Faults and Warnings

Code / displayMeaningCauseActionPage
UNIT WARNING
QUARTERLY SERVICE REQUIRED - CONTACT JCI
Quarterly Service Required Warning (Warning Code: 1) Manual Reset Warning; shutdown type: None. Enabled always. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 2
UNIT WARNING
YEARLY SERVICE REQUIRED - CONTACT JCI
Yearly Service Required Warning (Warning Code: 2) Set when all of the following are true: Days Since Last Yearly Service >= 365 Days; Operating Hours Since Last Yearly Service > 2,890 Hours (33% of a year’s run hours = 24*365*0.33) Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: None; trip time: Instantaneous. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 2
UNIT WARNING
3 YEAR SERVICE REQUIRED - CONTACT JCI
3 Year Service Required Warning (Warning Code: 3) Set when Days Since Last 3 Year Service >= 1095 Days Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: None; trip time: Instantaneous. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 2
UNIT WARNING
5 YEAR SERVICE REQUIRED - CONTACT JCI
5 Year Service Required Warning (Warning Code: 4) Set when Days Since Last 5 Year Service >= 1825 Days Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: None; trip time: Instantaneous. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 3
SYS X WARNING - REPLACE OIL FILTER System Replace Oil Filter Warning (Warning Code: 5) Set when Differential Oil to Discharge Pressure > 50 PSID Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: 15 Minutes of Run Time; trip time: 10 Minutes. Release after set; warnings are not logged to the History buffer. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter). 3

From ZIEHL-ABEGG Variable Speed Fan Troubleshooting Guide SI0640

Original: docs.johnsoncontrols.com

ZIEHL-ABEGG Variable Speed Fan — Motor Fault Codes (LED Status/Fault Light)

Code / displayMeaningCauseActionPage
LED OFFNo voltage supply. Unit is switched off and will automatically turn on when the voltage has been restored.Check voltage supply.3
1
No enable = OFF
No enable = OFFTerminal “D1” – “24V” (Digital In 1) not bridgedCheck jumpers/wiring connections.3
2
Temperature management active
The device has integrated active temperature management to protect the device from damage caused by excessively high internal temperatures.Internal temperature increases above the predetermined limits.The speed is linearly reduced. When the temperature drops, the speed rises again linearly. Check installation of the device and cooling of the motor.3
3
Error rotor position
Determination of the rotor position has failed.After 8 starting tests, the error message is displayed. Check whether the motor can rotate freely (without line voltage).3
4
Line failure (only for 3 ~ types)
The device is provided with a built-in phase-monitoring function for the mains supply.Mains interruption (failure of a fuse or mains phase).The unit switches off after a delay (approx. 200 ms). Following a shutoff, a startup attempt is made after approximately 15 seconds, if the voltage supply is present. This will continue to occur until all 3 supply phases are present. Check power supply.3
5
Motor blocked
If after 8 seconds of attempting to rotate no speed is measured, the fault “Motor blocked” is released.Device switches off, attempt to restart after about 2.5 sec. After the fourth starting test fails, the device locks out. After lockout, it is necessary to reset by disconnecting the line voltage. Check whether the motor can rotate freely (without line voltage).3
6
Failure power module
Failure power moduleShort circuit to earth or short circuit of the motor winding.EC-Controller switches off, attempt to restart after about 60 sec. If (following a second starting test) a second fault detection is detected within a period of 60 seconds, the device locks out. After lockout, it is necessary to reset by disconnecting the line voltage.3
7
Intermediate undervoltage
If the DC-link voltage drops below a specified limit, the device will switch off.If the DC-link voltage rises above the limit within 75 seconds, then the controller will attempt to start. Should the DC-link voltage stay, for more than 75 seconds, below the limit, the device will switch off with a fault message.3
8
Intermediate circuit overvoltage
If the DC-link voltage increases above a specified limit, the motor will switch off.If the DC-link voltage drops below the limit within 75 seconds, then the controller will attempt to start. Should the DC-link voltage stay above the limit for more than 75 seconds, the device will switch off with a fault message.3
9
Cooling down period power module
Cooling down period power module for approx. 60 sec.Final shutoff after 2 cooling-off intervals.3
10
Communication fault
If the communication watchdog is active, it signals that MODBUS communication is interrupted.Response dependent on set watchdog mode. Check MODBUS communication.4
11
Error motor start
If a starting command is given (enable available and Setpoint > 0) and the motor does not start to turn in the correct direction within 5 minutes, then an error message will appear.If it is possible to start the motor in the correct direction of rotation after the error message, the error message will disappear. Should a voltage interruption occur during the 5 minute duration of the fault, the timer will reset. Check whether the motor can rotate freely (without line voltage). Check if the fan is spinning in reverse direction by air stream.4
12
Line voltage too low
If the DC-link voltage drops below a specified limit the device will switch off.If the line voltage rises above a specified limit within 75 seconds, then the controller will attempt to start. Should the line voltage stay below the specified limit for more than 75 seconds, the device will switch off with an error message.4
13
Line voltage too high
If the line voltage increases above a specified limit, the motor will switch off.Cause of high input voltageIf the line voltage drops below the specified limit within 75 seconds, then the controller will attempt to start. Should the line voltage stay above the specified limit for more than 75 seconds, the device will switch off with an error message.4
14
Error peak current
If the motor current increases above the specified limit (even in a short timeframe) the device will switch-off.After a switch off, the controller waits for 5 seconds then the controller attempts to restart. If there are 5 faults within 60 seconds of the first fault, the device locks out. If there are no additional faults, after 60 seconds the counter will be reset.4
17
Temperature alarm
Excess of the max. permissible internal temperature.Controller switches off motor. Automatic restarting after cooling down. Check installation of the device and cooling of the controller.4
18
System error
Device has detected a system error. Only limited operation or no operation is possible.The error is displayed immediately. The motor is switched off depending on the system error. Reset fault by disconnecting the voltage supply. If the error message persists, replace assembly.4
20 a)
Vibration values
If the vibration velocity rises above the specified limits, an error message is issued.The error is displayed after the set time. The device will continue to operate. Check the impeller for damage, contamination, or ice formation.4
20 b)
Lifetime
If the remaining service life falls below the defined limit, an error message is issued.The error is displayed immediately. The device will continue to operate. If the error message persists, replace assembly.4
Continuous short flash
Internal communication error
Internal communication failure. Fault indication.If the error message persists, replace assembly.5
1 Long, 2 Short
MODBUS Recovery function
A failure in the MODBUS communication has been detected, e.g. incorrect communication parameters (baud rate, parity), wiring error.Incorrect communication parameters (baud rate, parity), wiring error.The motor can be accessed in recovery mode using the following parameters: Address 254, 19200Baud / 8E1. Check the bus wiring and communication parameters.5

Other documentation for this model: commissioning and checklists · installation · parts lists · service bulletins · specifications