Safety shutdown · YORK YVAA · Air-cooled variable speed drive screw chiller

YORK YVAAEDUCTOR CLOG FAULT

On the display

The status fault shows EDUCTOR CLOG FAULT; the control documentation also prints it as Eductor clog fault. It is one of the system safeties and appears when the eductor clog detection safety trips.

What it means

This safety senses a loss of oil return to the compressor. To do that, it monitors the temperature of the line between the eductor and the suction line. The control algorithm looks at the eductor line temperature once a second and compares it with the saturated suction temperature plus 5.5°C (10°F). A temperature that stays above that threshold means oil is no longer returning to the compressor through the eductor; when it remains above the threshold for 600 seconds, the clog timer counts to 0 and the system shuts down and locks out.

Why it appears

  • The eductor line temperature stays greater than the saturated suction temperature plus 5.5°C (10°F): the clog timer is decremented one second for each second above the threshold, and if the temperature remains above it for 600 seconds the timer counts to 0. The timer resets to 600 seconds whenever the temperature is below the threshold, which prevents nuisance faults.
  • The eductor valve was not opened: for units with optional eductor and suction valves, the manual warns that failure to open the eductor valve results in eductor clog faults.

What to check

  1. Change the eductor filter — the manual states: Whenever this fault occurs, the eductor filter should be changed.
  2. If optional eductor and suction valves are installed on the unit, confirm that the eductor valve is open, since leaving it closed results in eductor clog faults.

Setpoints and thresholds

  • Threshold: saturated suction temperature plus 5.5°C (10°F).
  • Clog timer: set at 600 seconds at start; one second is decremented for each second the eductor line temperature is above the threshold.
  • Timer reset: back to 600 seconds whenever the eductor line temperature is below the threshold.
  • Sampling: the eductor line temperature is checked once a second.
  • Eductor differential and eductor safety time are programmable under the PROGRAM key.

Reset and restart

The system shuts down and locks out. As a lockout, the unit will not restart until the operator clears the fault using the keypad. Before restarting, change the eductor filter, which the manual requires after every occurrence of this fault.

Questions engineers ask

Why does my YORK YVAA show EDUCTOR CLOG FAULT?

The control saw the eductor line temperature stay above the saturated suction temperature plus 5.5°C (10°F) for 600 seconds, which it reads as a loss of oil return to the compressor. On a unit fitted with the optional valves, a closed eductor valve also produces this fault.

What must be replaced after an eductor clog fault?

The eductor filter. The manual directs that it should be changed whenever this fault occurs.

How do I clear the EDUCTOR CLOG FAULT lockout?

The unit shuts down and locks out and will not restart until the operator clears the fault using the keypad. Change the eductor filter before restarting.

Can the eductor clog timer be changed?

The eductor differential and eductor safety time are programmable under the PROGRAM key. At start the clog timer is set at 600 seconds and resets to 600 seconds whenever the eductor line temperature is below the threshold.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YVAA; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: