On the display
The panel prints the message as SYS X CONTROL VOLTAGE for the affected system. In the manual's fault tables the same entry appears as SYS X YYYYYYYY CONTROL VOLTAGE: X is the number of the system involved, and YYYYYYYY reads FAULT or LOCKOUT. The manuals list this message under the system safeties (faults).
What it means
This safety alerts the operator that the 115 V AC control voltage to one of the systems is missing; the manual calls it the System Control Voltage Cutout. The affected system faults and shuts down immediately when the 115 V AC supply is lost. The safety is deliberately scoped to a single system: it will not shut down a system if the UNIT switch is OFF, because that switch electrically removes the 115 V AC to all systems. It is only used to indicate a situation where a single system is missing the 115 V AC.
Why it appears
- The 115 V AC supply has been lost to a single system.
- The loss may be due to a system fuse that has been removed or is blown.
What to check
- Read the system number X in the message — it identifies the system that is missing its 115 V AC control voltage.
- Check the 115 V AC supply to that one system.
- Check the system fuse serving that system; the manual names a fuse that has been removed or blown as the possible reason the supply is gone.
- Confirm the loss affects a single system rather than the whole unit: with the UNIT switch OFF the 115 V AC is electrically removed from all systems, and this safety does not shut a system down in that case.
Reset and restart
This safety does not cause a LOCKOUT. The manual's stated action is: Will not cause a lockout; the system fault resets when power is returned.
Restoring the 115 V AC supply to the affected system returns power to it, the system fault resets, and the message clears. No other reset procedure is described for this safety.
Questions engineers ask
What does SYS X CONTROL VOLTAGE mean on a York YVAA?
It alerts the operator that the 115 V AC control voltage to one of the systems is missing. The affected system faults and shuts down immediately when the 115 V AC supply is lost.
What causes the SYS X CONTROL VOLTAGE fault on a York YVAA?
The 115 V AC supply has been lost to a single system, which may be due to a system fuse that has been removed or is blown. The safety does not respond to the UNIT switch being OFF, since that removes the 115 V AC from all systems.
Does SYS X CONTROL VOLTAGE lock out a York YVAA chiller?
No. The safety will not cause a lockout; the system fault resets when power is returned to the affected system.
How do I clear SYS X CONTROL VOLTAGE on a York YVAA?
Restore the missing 115 V AC supply to the affected system — the manual names a removed or blown system fuse as the typical reason it was lost. The system fault resets when power is returned.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YVAA; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YVAA messages: fault codes · YORK YVAA documentation · YORK manuals