On the display
The panel reads SYS X YYYYYYYY LOW DIFF OIL PRESSURE, printed in short form as SYS X LOW DIFF OIL PRESSURE. X is the system number, so the message tells you which system of the chiller tripped. YYYYYYYY is the status word that follows the message on the display: it reads FAULT or LOCKOUT, and which one is shown decides how the system comes back (see Reset). The manual groups this message with the system safeties (faults).
What it means
This is the Low Differential Oil Pressure Cutout. It protects the compressor from low oil flow and insufficient lubrication, and it ensures the compressor is pumping sufficiently to push oil through the oil cooling circuit and the internal compressor lubrication system. The value it watches is the differential between the oil pressure and the suction pressure. When that differential falls below the cutout, the system does not drop out hard: it shuts down with a controlled ramped shutdown.
Why it appears
- The differential between the oil and suction pressure falls below the cutout that is active at that moment. This cutout is not one fixed number — it is ignored during the first part of run time and then ramped upward as the run continues, with the ramp duration set by ambient temperature (values under Settings).
- Nuisance-trip window: the manual introduces the case of another compressor being brought on while the running compressor is ramped down to 5 Hz, and it employs a 30 second safety bypass below 50 Hz during rampdown specifically to prevent nuisance low oil differential trips in that situation.
Setpoints and thresholds
- Ignored for the first 60 seconds of run time.
- Ramped cutout: after the first 60 seconds the cutout is ramped linearly from 0 barg to 2.09 barg (0 psid to 30 psid) over 5 to 10 minutes, based on ambient temperature: above 10 °C — 5 minutes; above 7.2 °C — 6 minutes; above 4.4 °C — 7 minutes; above 1.6 °C — 8 minutes; above 1.1 °C — 9 minutes; 1.1 °C or below — 10 minutes.
- Low-speed bypass: below 50 Hz during rampdown a 30 second safety bypass applies — this is what covers the moment another compressor is brought on and the running compressor is ramped down to 5 Hz.
Reset and restart
On the trip itself the system shuts down with a controlled ramped shutdown. What happens then depends on the status word on the display. FAULT: the system restarts automatically once the 120 second anti-recycle timer times out; the auto-reset is not unlimited, because on the third fault within 90 minutes the system locks out — the manual's instruction is to cycle the respective system switch OFF and ON to clear
. LOCKOUT: the system will not restart until the operator clears the fault using the keypad.
Questions engineers ask
What does SYS X LOW DIFF OIL PRESSURE mean on a YORK YVAA?
It is the low differential oil pressure cutout: the difference between the oil pressure and the suction pressure fell below the active cutout, so the system protects the compressor from low oil flow and insufficient lubrication and shuts it down with a controlled ramped shutdown.
How do I reset a LOW DIFF OIL PRESSURE fault or lockout?
If the display reads FAULT, the system restarts by itself once the 120 second anti-recycle timer times out; on the third fault within 90 minutes it locks out, and the manual says to cycle the respective system switch OFF and ON to clear. If the display reads LOCKOUT, the system will not restart until the operator clears the fault using the keypad.
Why does my YVAA show LOW DIFF OIL PRESSURE when the second compressor starts?
That is the known nuisance-trip window: another compressor is being brought on and the running compressor is ramped down to 5 Hz. The control therefore applies a 30 second safety bypass below 50 Hz during rampdown to prevent these nuisance low oil differential trips.
At what oil differential pressure does the cutout trip?
The safety is ignored for the first 60 seconds of run time; after that the cutout ramps linearly from 0 barg to 2.09 barg (0 to 30 psid) over 5 to 10 minutes, with the duration set by ambient temperature — 5 minutes above 10 °C up to 10 minutes at 1.1 °C or below.
Messages next to this one
The same message on other models
Source
Written from the manufacturer's manuals for the YORK YVAA; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: