SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

YVAA Only Planned Maintenance Warnings Software Version V18

Document typeService Information Letter
Document numberSI0476
EquipmentYVAA Variable Speed Drive Screw Chiller
BrandYORK
File size0.7 MB

Fault codes in this document

Faults and Warnings

Code / displayMeaningCauseActionPage
UNIT WARNING
QUARTERLY SERVICE REQUIRED - CONTACT JCI
Quarterly Service Required Warning (Warning Code: 1) Manual Reset Warning; shutdown type: None. Enabled always. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 2
UNIT WARNING
YEARLY SERVICE REQUIRED - CONTACT JCI
Yearly Service Required Warning (Warning Code: 2) Set when all of the following are true: Days Since Last Yearly Service >= 365 Days; Operating Hours Since Last Yearly Service > 2,890 Hours (33% of a year’s run hours = 24*365*0.33) Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: None; trip time: Instantaneous. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 2
UNIT WARNING
3 YEAR SERVICE REQUIRED - CONTACT JCI
3 Year Service Required Warning (Warning Code: 3) Set when Days Since Last 3 Year Service >= 1095 Days Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: None; trip time: Instantaneous. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 2
UNIT WARNING
5 YEAR SERVICE REQUIRED - CONTACT JCI
5 Year Service Required Warning (Warning Code: 4) Set when Days Since Last 5 Year Service >= 1825 Days Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: None; trip time: Instantaneous. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter) to set the counter back to zero days. 3
SYS X WARNING - REPLACE OIL FILTER System Replace Oil Filter Warning (Warning Code: 5) Set when Differential Oil to Discharge Pressure > 50 PSID Manual Reset Warning; shutdown type: None. Allowed states: All; bypass time: 15 Minutes of Run Time; trip time: 10 Minutes. Release after set; warnings are not logged to the History buffer. Acknowledge in Maintenance Mode (press the Service Key, enter password 0726, press Enter). 3

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.

Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.