Fault · SINAMICS G130, G150, S120, S150

F35209TM: Temperature fault/alarm threshold channel 2 exceeded

What it means

This fault comes from the temperature evaluation of a Terminal Module (TM) and concerns sensor channel 2. It is raised when, on this channel, either the alarm threshold has been exceeded for longer than the delay time set in the timer, or the fault threshold has been exceeded outright. The temperature itself is acquired by the Terminal Module, and the manual points out explicitly: This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal Module. Depending on how the message is configured, the same condition can also be signalled as an alarm (A) or with no reaction (N).

Why it appears

Both manuals describing this code state the same two initiating conditions for the temperature evaluation via the Terminal Module, so there is no difference between the drive families:

  • The alarm threshold of channel 2 (p4102[4]) has been exceeded for longer than the delay time set in the timer p4103[2].
  • The fault threshold of channel 2 (p4102[5]) has been exceeded.

What to check

  1. Read the temperature of channel 2 at the connector output r4105[2]; the value can also be interconnected. The fault value stored in r0949 tells you which temperature was present when the fault was initiated.
  2. If a PTC thermistor or a bimetallic NC contact is connected (p4100[2] = 1, 4), interpret the displayed value as a resistance state: if r4101[2] > 1650 ohms, the drive outputs 250 °C at r4105[2]; if r4101[2] ≤ 1650 ohms, it outputs -50 °C.
  3. Compare the value against the alarm threshold p4102[4] and the fault threshold p4102[5], and check the delay time in p4103[2] that applies when only the alarm threshold is exceeded.
  4. Allow the temperature sensor to cool down until the value lies below the fault threshold p4102[5] minus the hysteresis of 5 K - on the TM150 this hysteresis can be set with p4118[2].
  5. If a shutdown is not wanted for this signal, set the fault response to NONE for this fault using p2100 and p2101.

Reading the message value

  • The fault value (r0949, interpret decimal) contains the temperature actual value at the time the fault was initiated, in 0.1 °C.
  • The message value %1 carries this temperature, so the stored number directly reflects how warm channel 2 was when the fault tripped.

Parameters the manual names

  • p4100 - sensor type of channel 2; values 1 and 4 correspond to PTC thermistor and bimetallic NC contact, for which the drive evaluates resistance rather than a linear temperature.
  • p4102 - thresholds of channel 2: index [4] holds the alarm threshold, index [5] the fault threshold the sensor must cool below again.
  • p4103 - delay time of channel 2 (p4103[2]): how long the alarm threshold may be exceeded before the fault is initiated.
  • r4101 - sensor resistance of the channel; for PTC thermistor and bimetallic NC contact it is compared against 1650 ohms.
  • r4105 - (CO) temperature actual value of channel 2, displayed via this connector output and available for interconnection.
  • r0949 - fault value; read as a decimal number it gives the temperature at fault initiation in 0.1 °C.
  • p4118 - on the TM150, sets the hysteresis of the fault/alarm thresholds (5 K by default).
  • p2100 - enter the number of the fault whose response you want to change.
  • p2101 - sets the new response (for example NONE) for the fault number entered in p2100.

Acknowledging and restarting

With the standard response the drive trips: the pulses are cancelled immediately (OFF2) and the drive coasts down. Acknowledgement is IMMEDIATELY (POWER ON), i.e. the fault is cleared by switching the drive on again. Before restarting, the sensor must have cooled so that the value at r4105[2] lies below the fault threshold p4102[5] minus the hysteresis (5 K; TM150 via p4118[2]). If the message is configured as an alarm (A) or with no reaction (N), the manual specifies reaction NONE and acknowledgement NONE, so no automatic shutdown occurs and nothing needs to be acknowledged.

What differs between the drive families

Straight from the manuals' own fields — F35209 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (NONE, OFF1, OFF3) Vector: OFF2 (NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3)External measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3213
G130, G150Vector: OFF2 (NONE, OFF1, OFF3) Infeed: OFF2 (NONE, OFF1)IMMEDIATELY (POWER ON)External measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1881

The drives this code lives on

F35209 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F35209 mean on a SINAMICS drive?

It is a Terminal Module message: during temperature evaluation of sensor channel 2, either the alarm threshold was exceeded longer than the timer p4103[2] allows, or the fault threshold p4102[5] was exceeded. The drive only shuts down if a BICO interconnection exists between the drive and the Terminal Module.

Why does channel 2 show 250 °C or -50 °C?

With a PTC thermistor or bimetallic NC contact (p4100[2] = 1, 4), the drive derives the displayed temperature from the resistance: r4101[2] above 1650 ohms is shown as 250 °C, r4101[2] at or below 1650 ohms as -50 °C.

What is stored in the fault value of F35209?

The fault value in r0949, interpreted as a decimal number, is the temperature actual value of channel 2 at the time the fault was initiated, in 0.1 °C.

How do I clear and restart after F35209?

Let the sensor cool below the fault threshold p4102[5] minus the hysteresis (5 K, on the TM150 settable via p4118[2]), then acknowledge IMMEDIATELY with POWER ON. Configured as an alarm or with no reaction, the message requires no acknowledgement.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.