What it means
F35229 ("TM: Time slice deactivated") means that a time slice of a TM was not activated because the cycle time required for it in p4099[0...2] has an invalid value. The drive stores a decimal alarm value in r2124 that identifies which function lost its time slice — from the digital input/outputs and analog inputs through the encoder emulation to the internal sequence control of the TM41.
Why it appears
- The value of a cycle time required in p4099[0...2] is invalid, so the corresponding time slice was not activated.
- An internal error in the sequence control of the TM41 can deactivate its time slice (alarm value 6 in r2124).
What to check
- Read the alarm value in r2124 and interpret it as a decimal number to identify the affected time slice.
- Change the sampling time in p4099 for the index that the alarm value names.
- Observe that
the sampling time p4099[0] may not be zero
.
Reading the message value
- The drive stores the alarm value in r2124; interpret the value as a decimal number.
- 0: Digital input/outputs (p4099[0])
- 1: Analog inputs (p4099[1])
- 3: Encoder emulation (p4099[3])
- 4: Encoder emulation speed setpoint (p4099[3])
- 5: Encoder emulation speed setpoint (p4099[3])
- 6: Internal sequence control of the TM41 (internal error)
Parameters the manual names
- p4099 (Inputs/outputs sampling time / I/O t_samp): holds the cycle time of the affected time slice — set the sampling time here as the alarm value indicates, and never with index [0] at zero.
- r2124 (Alarm value): read the decimal value here to find out which time slice was deactivated.
Acknowledging and restarting
The fault is not cleared by acknowledgment alone: change the sampling time in p4099 according to the alarm value in r2124 and then acknowledge the fault. The manual describes no further reset or restart steps for this code.
The same on every family
Every manual that describes F35229 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF1 (NONE, OFF2) Servo: NONE Vector: NONE Hla: NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 3221 |
The drives this code lives on
F35229 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F35229 mean on a SINAMICS S120 or S150?
The drive reports "TM: Time slice deactivated": a cycle time required in p4099[0...2] is invalid, so the corresponding time slice was not activated.
How do I fix fault F35229?
Read the decimal alarm value in r2124 to identify the affected function and change the corresponding sampling time in p4099. The sampling time p4099[0] may not be zero.
What does alarm value 6 mean for F35229?
It stands for an internal error in the internal sequence control of the TM41. The values 0, 1, 3, 4 and 5 instead point to the time slices for digital input/outputs, analog inputs and encoder emulation.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F35xxx group · SINAMICS manuals · Siemens manuals