What it means
F35207 comes from the temperature evaluation of a Terminal Module (TM). It is initiated when, on channel 0, the alarm threshold has been exceeded for longer than the timer allows, or when the fault threshold has been exceeded outright. The same condition can also be reported as an alarm (A) or as a message without reaction (N), depending on how the drive is configured.
The manual emphasises that this fault only causes the drive to shut down if at least one BICO interconnection exists between the drive and the Terminal Module. The temperature actual value that the TM determines is output at connector output r4105[0] and can be interconnected.
Why it appears
- The alarm threshold (p4102[0]) has been exceeded for longer than the time set in the timer (p4103[0]).
- The fault threshold (p4102[1]) has been exceeded.
For the sensor types PTC thermistor and Bimetallic NC contact (p4100[0] = 1, 4), the temperature is derived from the measured sensor resistance r4101[0]: if r4101[0] is greater than 1650 ohms, the temperature at r4105[0] is 250 °C; if r4101[0] is less than or equal to 1650 ohms, it is -50 °C.
What to check
- Read the temperature that was present when the fault was initiated: the fault value r0949, interpreted as a decimal number, holds it in 0.1 °C. Compare it with the alarm threshold p4102[0] and the fault threshold p4102[1].
- With sensor type PTC thermistor or Bimetallic NC contact (p4100[0] = 1, 4), read the sensor resistance r4101[0]: more than 1650 ohms is displayed as 250 °C at r4105[0], 1650 ohms or less as -50 °C.
- Allow the temperature sensor to cool down until it falls below p4102[1] minus the hysteresis; the hysteresis is 5 K and can, on a TM150, be set using p4118[0].
- If the temperature evaluation should not shut the drive down, set the fault response to NONE using p2100 and p2101.
Reading the message value
- Fault value r0949, interpret decimal: the temperature actual value at the time the fault was initiated, given in 0.1 °C.
- The temperature actual value currently derived is available via connector output r4105[0].
Parameters the manual names
- p4102 — the alarm threshold (p4102[0]) and the fault threshold (p4102[1]) of the temperature channel; the fault clears only once the temperature drops below p4102[1] minus the hysteresis.
- p4103 — the delay time (p4103[0]): how long the alarm threshold may be exceeded before the fault is initiated.
- p4100 — the sensor type (p4100[0]); 1 = PTC thermistor, 4 = Bimetallic NC contact — for these types the temperature is derived from the resistance.
- r4101 — the sensor resistance (r4101[0]); for PTC or bimetallic contact, more than 1650 ohms is reported as 250 °C, 1650 ohms or less as -50 °C.
- r4105 — CO connector output with the temperature actual value (r4105[0]); it can be interconnected.
- r0949 — the fault value; interpreted decimal it shows the temperature at the time of initiation in 0.1 °C.
- p4118 — the hysteresis (p4118[0]) of the fault/alarm threshold on a TM150; otherwise the hysteresis is 5 K.
- p2100 / p2101 — set the fault response for this fault to NONE if the temperature evaluation should not shut the drive down.
Acknowledging and restarting
Acknowledge the fault immediately once the sensor has cooled below the fault threshold p4102[1] minus the hysteresis; a POWER ON also removes the fault. Only then will the drive restart. If the drive is configured to report the condition as an alarm (A) or as a message without reaction (N), the manual specifies no acknowledgement for these variants (NONE).
What differs between the drive families
Straight from the manuals' own fields — F35207 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (NONE, OFF1, OFF3) Vector: OFF2 (NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3212 |
| G130, G150 | Vector: OFF2 (NONE, OFF1, OFF3) Infeed: OFF2 (NONE, OFF1) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1880 |
The drives this code lives on
F35207 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does the fault value of F35207 tell me?
Interpreted as a decimal number, r0949 holds the temperature actual value at the moment the fault was initiated, in 0.1 °C. The temperature currently derived by the Terminal Module is at connector output r4105[0].
Why is F35207 shown but the drive keeps running?
The fault only causes the drive to shut down if at least one BICO interconnection exists between the drive and the Terminal Module. Without such an interconnection the message is raised but the drive is not shut down.
How do I clear F35207?
Let the temperature sensor cool down below p4102[1] minus the hysteresis — 5 K, on a TM150 settable with p4118[0] — and then acknowledge the fault immediately; a POWER ON also removes it.
Why does F35207 report 250 °C or -50 °C for a PTC sensor?
With sensor type PTC thermistor or Bimetallic NC contact (p4100[0] = 1, 4), a resistance r4101[0] above 1650 ohms is reported as 250 °C, and one of 1650 ohms or less as -50 °C.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F35xxx group · SINAMICS manuals · Siemens manuals