What it means
The Terminal Module (TM) raises F35208 — TM: Temperature fault/alarm threshold channel 1 exceeded when its channel 1 temperature evaluation trips: either the alarm threshold has been exceeded for longer than the delay time set in the timer (p4102[2], p4103[1]), or the fault threshold p4102[3] has been exceeded. Depending on how the message is configured, the drive can also issue the same condition as an alarm or with no reaction. This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the Terminal Module.
Why it appears
- The alarm threshold of channel 1 was exceeded longer than the delay time set in the timer (p4102[2], p4103[1]).
- The fault threshold p4102[3] was exceeded.
What to check
- Check the temperature actual value at connector output r4105[1] — it is displayed there and can be interconnected. For the sensor types 'PTC thermistor' and 'Bimetallic NC contact' (p4100[1] = 1, 4), a resistance r4101[1] above 1650 ohms is shown as 250 °C, and one of 1650 ohms or less as -50 °C.
- Allow the temperature sensor to cool down to below the fault threshold p4102[3] minus hysteresis — 5 K; on the TM150 this hysteresis can be set using p4118[1].
- If required, set the fault response to NONE using p2100 and p2101.
Reading the message value
- The fault value in r0949, interpreted decimal, is the temperature actual value at the time the fault was initiated, in 0.1 °C.
Parameters the manual names
- p4102 — holds the channel 1 thresholds: index [2] is the alarm threshold, index [3] the fault threshold that the sensor must cool below.
- p4103 — index [1] sets the delay time for how long the alarm threshold may be exceeded before the fault is initiated.
- p4100 — index [1] sets the sensor type of channel 1; 'PTC thermistor' and 'Bimetallic NC contact' correspond to p4100[1] = 1 and 4.
- r4101 — shows the sensor resistance; for PTC and bimetallic NC contact, 1650 ohms is the switching point between the 250 °C and -50 °C readings.
- r4105 — connector output (CO) with the channel 1 temperature actual value; watch it here to follow the cool-down.
- r0949 — fault value of this message; interpret decimal to read the temperature at initiation in 0.1 °C.
- p4118 — sets the threshold hysteresis of the TM150 (5 K as delivered).
- p2100 — enter the number of the fault whose response is to be changed.
- p2101 — sets the response that then applies; the remedy names NONE.
Acknowledging and restarting
The fault is set up to be acknowledged immediately; a POWER ON also removes it. Before restarting, the temperature must have fallen below the fault threshold p4102[3] minus the hysteresis (5 K, on the TM150 settable via p4118[1]), otherwise the fault is initiated again. As a fault the drive coasts down (OFF2); once the message is acknowledged, the drive can be started again. If the condition is configured as alarm or without reaction, neither reaction nor acknowledgement apply.
What differs between the drive families
Straight from the manuals' own fields — F35208 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (NONE, OFF1, OFF3) Vector: OFF2 (NONE, OFF1, OFF3) Hla: OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3213 |
| G130, G150 | Vector: OFF2 (NONE, OFF1, OFF3) Infeed: OFF2 (NONE, OFF1) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1881 |
The drives this code lives on
F35208 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F35208 mean on a SINAMICS drive?
The Terminal Module's channel 1 temperature evaluation has tripped — either the alarm threshold was exceeded longer than the timer in p4102[2] and p4103[1] allows, or the fault threshold p4102[3] was exceeded.
How do I clear F35208?
Let the temperature sensor cool down below the fault threshold p4102[3] minus hysteresis (5 K; on the TM150 adjustable with p4118[1]), then acknowledge the fault — immediate acknowledgement is set, and a POWER ON also works.
Why does F35208 come with 250 °C or -50 °C as the value?
With the sensor types PTC thermistor and Bimetallic NC contact (p4100[1] = 1, 4), a resistance r4101[1] above 1650 ohms is displayed as 250 °C and one of 1650 ohms or less as -50 °C. Otherwise r0949 holds the temperature actual value at initiation in 0.1 °C.
Does F35208 always shut the drive down?
No — the fault only causes a shutdown if at least one BICO interconnection exists between the drive and the Terminal Module, and the drive can also be configured to issue the same condition only as an alarm or with no reaction.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F35xxx group · SINAMICS manuals · Siemens manuals