Fault · SINAMICS G130, G150, S120, S150

F32120Encoder 2: Encoder power supply fault

What it means

F32120 tells you the drive has detected a fault in the power supply of encoder 2. The list manuals print it under slightly different titles — «Encoder 2: Encoder power supply fault» and «Encoder 2: Power supply voltage fault» — but describe the same condition and the same remedies. The drive writes the cause into the fault value r0949, which is interpreted as a binary number: each set bit names one supply problem, from an undervoltage on the sense line to a hardware fault at the EnDat connection. Depending on how the drive is configured, the same monitoring can also be output as an alarm (A) or with no reaction (N).

Why it appears

  • An encoder power supply fault was detected on encoder 2; the binary fault value in r0949 shows which condition tripped the monitoring (see the bit list below).
  • If the encoder cables 6FX2002-2EQ00-.... and 6FX2002-2CH00-.... are interchanged, this can result in the encoder being destroyed because the pins of the operating voltage are reversed.

What to check

  1. Read the fault value in r0949 as a binary number and note which bit is set.
  2. Bit 0 set (undervoltage on the sense line): check that the correct encoder cable is connected, check the plug connections of the encoder cable, and on an SMC30 check the parameterization in p0404.22.
  3. Bit 1, 2 or 3 set (overcurrent in the encoder power supply or on the resolver excitation cables): check that the correct encoder cable is connected, then replace the encoder or the encoder cable.
  4. Bit 4 set (the 24 V power supply through the Power Module (PM) is overloaded): the manuals list no separate remedy for this bit.
  5. Bit 5 set (overcurrent at the EnDat connection of the converter): check that the measuring unit is correctly connected at the converter; replace the measuring unit or the cable to the measuring unit.
  6. Bit 6 or 7 set (overvoltage or hardware fault at the EnDat connection): replace the defective EnDat 2.2 converter.

Reading the message value

The message value is the fault cause. The drive stores it in r0949 and it must be interpreted binary:

  • Bit 0: undervoltage condition on the sense line.
  • Bit 1: overcurrent condition for the encoder power supply.
  • Bit 2: overcurrent condition for encoder power supply on cable resolver excitation negative.
  • Bit 3: overcurrent condition for encoder power supply on cable resolver excitation positive.
  • Bit 4: the 24 V power supply through the Power Module (PM) is overloaded.
  • Bit 5: overcurrent at the EnDat connection of the converter.
  • Bit 6: overvoltage at the EnDat connection of the converter.
  • Bit 7: hardware fault at the EnDat connection of the converter.

Parameters the manual names

  • r0949 — fault value of this message: read it as a binary number; the set bits identify which encoder 2 supply fault occurred.
  • p0404.22 — effective encoder configuration: when bit 0 (sense-line undervoltage) is set and an SMC30 is connected, check this parameterization.

Acknowledging and restarting

The fault is acknowledged with pulse inhibit (PULSE INHIBIT): bring the drive into the pulse-inhibited state, acknowledge F32120 and then restart the drive. Where the same condition is configured as an alarm (A) or with no reaction (N), there is neither reaction nor acknowledgement (NONE).

What differs between the drive families

Straight from the manuals' own fields — F32120 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Hla: OFF1 (NONE, OFF2, OFF3)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 2SINAMICS S120, S150 List Manual · p. 3088
G130, G150OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 2SINAMICS G130, G150 List Manual · p. 1769

The drives this code lives on

F32120 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F32120 mean on a SINAMICS drive?

The drive has detected a power supply fault on encoder 2. The binary fault value in r0949 shows the exact condition — from an undervoltage on the sense line (bit 0) to a hardware fault at the EnDat connection (bit 7).

How do I clear fault F32120?

Read r0949 and work through the remedy for the set bit: check or replace the encoder cable, check p0404.22 on an SMC30, or replace the measuring unit or the EnDat 2.2 converter. Then acknowledge the fault with pulse inhibit and restart the drive.

Why does F32120 warn about destroyed encoders?

The manuals warn that interchanging the encoder cables 6FX2002-2EQ00-.... and 6FX2002-2CH00-.... reverses the pins of the operating voltage, which can result in the encoder being destroyed.

Can F32120 also appear as an alarm?

Yes. Depending on the drive configuration, the same monitoring can also be output as an alarm (A) or with no reaction (N); in those cases there is no reaction and no acknowledgement.