What it means
F30665 reports that the SI P2 system has found a defect — either before the previous boot or within the one in progress; the system may also have rebooted itself (reset). The fault value, which you read in r0949 and interpret as a hexadecimal number (the manual prints it as the placeholder %1 in the message value), tells you which situation applies and which setting, if any, is wrong. On a G120 Power Module with "STO via terminals at the Power Module" (STO_A/STO_B), value 40 hex says: the STO terminals are active because the DIP switch sits in the "ON" position, while the function is not yet enabled (p9601.7 = p9801.7 = 0). On a Power Module of the S120, S150, G130 and G150, value 2 hex says: p9500 and p9300 do not match — you recognise this because Safety message C30711 appears at the same time. Values 200000 hex and 400000 hex (on the G120 also 4000yy hex) describe a fault inside the current booting/operation; every other value means the defect was already present before the drive last booted.
Why it appears
- A system defect was found either before the previous boot or within the one in progress; the system may have rebooted itself (reset).
- On a G120 Power Module with "STO via terminals at the Power Module": the STO_A/STO_B terminals are active (DIP switch "ON"), but the function is not enabled (p9601.7 = p9801.7 = 0) — this is fault value 40 hex.
- On a Power Module of the S120, S150, G130 and G150: p9500 and p9300 are not identical, which shows up together with Safety message C30711 — this is fault value 2 hex.
- For 200000 hex or 400000 hex (G120 additionally 4000yy hex): a fault during the running booting/operation; further values indicate a defect that already existed before the previous boot.
What to check
- Read the fault value in r0949 as a hexadecimal number and find your case below.
- Perform a POWER ON: switch the converter off and back on. This step belongs to every fault value.
- For 40 hex: either move both DIP switches on the Power Module to "OFF" — this deactivates the STO_A/STO_B terminals — or enable the "STO via terminals at the Power Module" function.
- For 2 hex: compare p9500 with p9300; both must carry the same value (this applies when Safety message C30711 appears alongside).
- For 400000 hex: make sure the Control Unit is physically connected to the Power Module.
- For 4000yy hex on the G120: make sure the Control Unit is physically connected to the Power Module and deselect the "STO via terminals at the Power Module" function.
- Should the fault return: update the firmware to a newer version and then get in touch with Technical Support.
Reading the message value
- The message value is the fault value; it appears as the placeholder %1 and you read it in r0949, interpreted as a hexadecimal number.
- 40 hex — G120 Power Module with "STO via terminals at the Power Module" (STO_A/STO_B): the STO terminals are active because the DIP switch is in the "ON" position, while the function is not enabled (p9601.7 = p9801.7 = 0).
- 2 hex — Power Module of the S120, S150, G130 and G150: p9500 and p9300 do not match; Safety message C30711 then appears at the same time.
- 200000 hex and 400000 hex (G120: 200000 hex and 4000yy hex) — a fault inside the current booting/operation.
- Additional values — the defect was already present before the drive last booted.
Parameters the manual names
- r0949 — displays the fault value of F30665; read it as a hexadecimal number to identify your case.
- p9601 — SI enable functions, processor 1: bit p9601.7 belongs to enabling the STO terminal function on the G120; with 40 hex it still reads 0.
- p9801 — SI enable functions, processor 2: bit p9801.7 goes together with p9601.7; for fault value 40 hex both bits read 0 while the terminals are already active.
- p9500 — SI Motion monitoring clock cycle of the Control Unit: with fault value 2 hex compare it against p9300.
- p9300 — SI Motion monitoring clock cycle of the Motor Module: it must have the same value as p9500 (relevant when C30711 is shown as well).
Acknowledging and restarting
The drive coasts down (OFF2) and the fault must be acknowledged immediately before a restart is possible. Start with a POWER ON — switch the converter off and back on. If the cause for 40 hex, 2 hex, 400000 hex or 4000yy hex was removed beforehand, the drive should restart normally. If F30665 returns, update the firmware to a newer version and get in touch with Technical Support.
What differs between the drive families
Straight from the manuals' own fields — F30665 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120 | OFF2 | IMMEDIATELY | Hardware/software error (1) | — | SINAMICS G120 · p. 924 |
| S120, S150 | OFF2 | IMMEDIATELY | Hardware/software error (1) | Power Module | SINAMICS S120, S150 List Manual · p. 2987 |
| G130, G150 | OFF2 | IMMEDIATELY | Hardware/software error (1) | Power Module | SINAMICS G130, G150 List Manual · p. 1685 |
The drives this code lives on
F30665 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30665 in SINAMICS drives mean?
The SI P2 system has detected a defect before the previous boot or during the one in progress, and the system may have rebooted itself. The hexadecimal value in r0949 tells you which case applies.
How do I fix F30665 with fault value 40 hex on a G120?
The STO_A/STO_B terminals on the Power Module are active (DIP switch "ON") while the function is not enabled. Either move both DIP switches to "OFF" or enable the "STO via terminals at the Power Module" function, then perform a POWER ON.
Why does message C30711 appear together with F30665?
Then p9500 and p9300 — the SI Motion monitoring clock cycles of Control Unit and Motor Module — do not match. Make both parameters identical and acknowledge the fault.
What if F30665 keeps coming back?
Carry out a POWER ON first; if the fault returns anyway, update the firmware to a newer version and get in touch with Technical Support.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.