What it means
F30655 is raised when an error occurs while the drive aligns the Safety Integrated (SI) monitoring functions of its two monitoring channels: no common set of supported SI monitoring functions was able to be determined
. The two channels differ by drive construction: on the G120 they are processor 1 and processor 2, while on the modular drives the channels reside in the Control Unit and the Motor Module/Hydraulic Module, which exchange data over DRIVE-CLiQ. Because the fault lies in Safety Integrated, it forces a STOP A that cannot be acknowledged.
Why it appears
- The alignment of the Safety Integrated monitoring functions of the two monitoring channels failed, so no common set of supported SI monitoring functions could be determined.
- On the drives whose channels sit in the Control Unit and the Motor Module/Hydraulic Module (S120, S150, G130, G150): there is either a DRIVE-CLiQ communication error or communication has failed, or the Safety Integrated software releases on the Control Unit and on the Motor Module/Hydraulic Module are not compatible with one another.
- On the G120, where the channels are processor 1 and processor 2: there is a communication error between processor 1 and processor 2 or communication has failed.
What to check
- Carry out a POWER ON (switch-off/switch-on); on the modular drives this means for all components.
- Still present on the modular drives: upgrade the Motor Module/Hydraulic Module software.
- Upgrade the Control Unit software.
- Check the electrical cabinet design and cable routing for EMC compliance — the manual names this step for every drive described.
Reading the message value
- The drive stores the fault value of F30655 in r0949; interpret it hexadecimal.
- The manual prints no decoding of the value into bits or meanings — the fault value is intended only for internal Siemens troubleshooting.
Parameters the manual names
- r0949 — holds the fault value of this message; read it hexadecimal if the value is evaluated at all, keeping in mind it serves only for internal Siemens troubleshooting.
Acknowledging and restarting
The fault triggers a Safety Integrated STOP A that cannot be acknowledged, so it does not clear with a simple acknowledgement from the operator panel or the commissioning tool. The message belongs to the IMMEDIATELY acknowledgement class: it is removed with a POWER ON, i.e. the drive is switched off and on again — on the modular drives, all components. Once the cause has been remedied and the POWER ON carried out, the fault is acknowledged and the drive can be restarted.
What differs between the drive families
Straight from the manuals' own fields — F30655 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2983 |
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1683 |
| G120 | OFF2 | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 922 |
The drives this code lives on
F30655 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30655 mean on a SINAMICS drive?
The drive could not align its two Safety Integrated monitoring channels — no common set of supported SI monitoring functions was able to be determined. On a G120 this concerns processor 1 and processor 2; on the modular drives it concerns the Control Unit and the Motor Module/Hydraulic Module.
How do I clear fault F30655?
Carry out a POWER ON (switch-off/switch-on), on the modular drives for all components. If the fault returns, upgrade the Motor Module/Hydraulic Module and Control Unit software and check the electrical cabinet design and cable routing for EMC compliance.
Why can fault F30655 not be acknowledged?
The fault results in a Safety Integrated STOP A that cannot be acknowledged. The fault message itself is only removed by a POWER ON (switch-off/switch-on) once the cause has been remedied.
What is the fault value of F30655 in r0949?
It is stored in r0949 and is interpreted hexadecimal. The manual provides no user decoding — the value is meant only for internal Siemens troubleshooting.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F30xxx group · SINAMICS manuals · Siemens manuals