Fault · SINAMICS G120, G130, G150, S120, S150

F30659SI P2: Write request for parameter rejected

What it means

F30659 means that a write request for one or several Safety Integrated (SI) parameters in monitoring channel 2 — on a G120, on processor 2 — was rejected. The drive raises the fault when commissioning or parameterization tries to enable a safety function that the connected hardware cannot support; the decimal fault value in r0949 identifies the rejected function. The manual notes that this fault does not result in a safety stop response.

Why it appears

  • One or several Safety Integrated parameters were written in monitoring channel 2 and the drive rejected the write request.
  • Behind every fault value stands the same situation: a safety function (STO, SS1, SBC, motion monitoring, PROFIsafe, Basic Functions, the ESR delay for pulse suppression) was to be enabled although the Control Unit, Motor Module, Hydraulic Module or power unit cannot support it.

What to check

  1. Read the decimal fault value in r0949 to identify the rejected function.
  2. For fault values 10, 11, 13, 14, 15, 16, 18, 19 and 27 (on a G120: 10, 15, 16, 18), check whether there are faults in the safety function alignment between the two monitoring channels (F01655, F30655) and, if required, carry out the diagnostics for the faults involved.
  3. If the alignment is fault-free, use a Motor Module that supports the required function and upgrade the Motor Module software and the Control Unit software; on Hydraulic Module drive objects use a Hydraulic Module and upgrade its software, and on a G120 use a Control Unit that supports the required function.
  4. Fault value 28: use the power unit with the feature "STO via terminals at the Power Module".
  5. Fault value 29: use a Motor Module or Hydraulic Module that supports the required function, upgrade the module software and the Control Unit software and, if required, parameterize the stop response for PROFIsafe failure to STOP A (p9612 = p9812 = 0); on Hydraulic Module drive objects first check whether p9612 and p9812 are set and correct the settings if required.

Reading the message value

  • 10 — STO was to be enabled although this cannot be supported.
  • 11 — SBC was to be enabled although this cannot be supported (Motor Module drive objects).
  • 13 — SS1 was to be enabled although this cannot be supported.
  • 14 — safe motion monitoring with the higher-level control was to be enabled although this cannot be supported.
  • 15 — the motion monitoring functions integrated in the drive were to be enabled although these cannot be supported.
  • 16 — PROFIsafe communication was to be enabled although this cannot be supported, or the version of the PROFIsafe driver used on the two monitoring channels is different.
  • 18 — the PROFIsafe function for Basic Functions was to be enabled although this cannot be supported.
  • 19 — for ESR, the delay for pulse suppression was to be enabled although this cannot be supported.
  • 20 — G120 only: drive-integrated motion monitoring via the integrated F-DI and STO via terminals were to be enabled at the same time, which is not supported.
  • 27 — Basic Functions were to be activated by controlling via TM54F although this cannot be supported.
  • 28 — "STO via terminals at the Power Module" was to be enabled although this cannot be supported.
  • 29 — STOP B was to be parameterized as the stop response for PROFIsafe failure although this cannot be supported.
  • 33 — Hydraulic Module drive objects only: safety functions without selection are not supported (p9601.5, p9801.5).

Parameters the manual names

  • r0949 — read the fault value here and interpret it as a decimal number to find which function was rejected.
  • r9771 — shows the SI common functions the Control Unit supports, so you can compare them with the function you tried to enable.
  • r9871 — shows the SI common functions the Motor Module supports, for the same comparison.
  • p9612 / p9812 — SI PROFIsafe failure response of the Control Unit and Motor Module; with fault value 29, set both to 0 so the response is STOP A.
  • p9601 / p9801 — SI enable functions integrated in the drive (Control Unit / Motor Module); fault value 33 on Hydraulic Module drive objects points to p9601.5 and p9801.5.

Acknowledging and restarting

Once the unsupported request has been removed as described above, the fault is acknowledged with POWER ON: switch the drive off and on again before the drive will restart.

What differs between the drive families

Straight from the manuals' own fields — F30659 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150OFF2IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1684
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2984
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2985
G120OFF2IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 923

The drives this code lives on

F30659 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does F30659 mean on a SINAMICS drive?

A write request for one or several Safety Integrated parameters in monitoring channel 2 was rejected because the requested function cannot be supported. The decimal fault value in r0949 names the rejected function.

Does fault F30659 trigger a safety stop?

No. The manual states explicitly that this fault does not result in a safety stop response.

How do I fix F30659 with fault value 29?

Use a Motor Module or Hydraulic Module that supports the function or upgrade the module and Control Unit software, and if required set the PROFIsafe failure stop response to STOP A (p9612 = p9812 = 0).

What does fault value 28 in F30659 mean?

The function "STO via terminals at the Power Module" was enabled although the power unit cannot support it. The remedy is to use a power unit with this feature.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.