What it means
F30656 is raised when the drive hits an error while reading the Safety Integrated (SI) parameters of monitoring channel 2 out of the non-volatile memory — on G120 the affected unit is the second parameter processor, which is why its manual titles the code SI P2: Parameter processor 2 parameter error
. On G130, G150, S120 and S150 the channel belongs to the Motor Module (MM). The fault forces a STOP A that can be acknowledged, and the drive only comes back after a POWER ON.
Why it appears
- An error occurred while the Safety Integrated parameters for monitoring channel 2 (on G120: for processor 2) were being accessed in the non-volatile memory.
- What exactly failed is told by the fault value in r0949: corrupted SI parameters (129) or an internal software error on the Control Unit, on the Motor Module/Hydraulic Module or — on G120 — on one of the two processors (131, 255).
What to check
- Re-commission the safety functions.
- Upgrade the Control Unit software and, on the Motor Module variant, the Motor Module/Hydraulic Module software as well — the G120 manual does not list this step.
- Replace the memory card or the Control Unit.
- If the fault value (r0949, read as a decimal number) is 129, run this sequence:
- Activate the safety commissioning mode (p0010 = 95).
- Adapt the PROFIsafe address (p9610) — this step is printed for the Motor Module variant only.
- Start the copy function for SI parameters (p9700 = D0 hex).
- Acknowledge the data change (p9701 = DC hex).
- Leave the safety commissioning mode (p0010 = 0).
- Save all parameters (p0977 = 1, or "copy RAM to ROM"; G120 saves with p0971 = 1).
- Carry out a POWER ON (switch-off/switch-on) for all components — on G120 for the Control Unit.
Reading the message value
The message value carries the fault value, which r0949 shows as a decimal number:
- 129 — the safety parameters of monitoring channel 2 (G120: of processor 2) are corrupted; for the Motor Module variant the manual adds that a drive with enabled safety functions may have been copied offline in the commissioning tool and the project downloaded.
- 131 — internal software error on the Control Unit (G120: on processor 1).
- 255 — internal software error on the Motor Module/Hydraulic Module (G120: on processor 2).
Parameters the manual names
- r0949 — read the fault value here, interpreted as a decimal number, to see whether case 129, 131 or 255 applies.
- p0010 — set to 95 to enter the safety commissioning mode and back to 0 to leave it.
- p9610 — adapt the PROFIsafe address of the Control Unit here (Motor Module variant, fault value 129).
- p9700 — set to D0 hex to start the copy function for SI parameters.
- p9701 — set to DC hex to acknowledge the changed SI data.
- p0977 — set to 1, or run "copy RAM to ROM", to save all parameters after the copy (Motor Module variant).
- p0971 — the G120 performs the same save with this parameter set to 1.
Acknowledging and restarting
Once the remedy is done, the fault clears only on a POWER ON (switch-off/switch-on) of all components — on G120 of the Control Unit. The STOP A produced by the fault can then be acknowledged.
What differs between the drive families
Straight from the manuals' own fields — F30656 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | None | SINAMICS S120, S150 List Manual · p. 2983 |
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | None | SINAMICS G130, G150 List Manual · p. 1683 |
| G120 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | — | SINAMICS G120 · p. 923 |
The drives this code lives on
F30656 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F30656 mean in SINAMICS?
The drive found an error while reading the Safety Integrated parameters of monitoring channel 2 (parameter processor 2 on G120) from the non-volatile memory. The fault value in r0949 tells which of the cases 129, 131 or 255 applies.
How do I clear F30656 with fault value 129?
Activate the safety commissioning mode (p0010 = 95), adapt the PROFIsafe address p9610 where the manual provides it, copy the SI parameters with p9700 = D0 hex and acknowledge with p9701 = DC hex. Then exit the mode, save all parameters and POWER ON the components.
Why does F30656 appear after I copied a project offline?
Fault value 129 means the SI parameters of monitoring channel 2 are corrupted — possibly a drive with enabled safety functions was copied offline in the commissioning tool and its project downloaded.
How is F30656 acknowledged?
By a POWER ON (switch-off/switch-on) of all components once the safety functions have been re-commissioned and the parameters saved; on G120 the POWER ON concerns the Control Unit.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.